Terminal Tightening Torque And Wire Size; Wire Connectors - Hitachi L200 Series Instruction Manual

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Hide thumbs Also See for L200 Series:
Table of Contents

Advertisement

Terminal Tightening Torque and Wire Size

The wire size range and tightening torque for field wiring terminals are presented in the
tables below.
Motor Output
Input
Voltage
kW
0.2
0.4
0.55
0.75
1.1
200V
1.5
2.2
3.7
5.5
7.5
0.4
0.75
1.5
2.2
400V
3.0
4.0
5.5
7.5
Terminal Connector
Logic/Analog connector
Relay connector

Wire Connectors

WARNING: Field wiring connections must be
made by a UL Listed and CSA Certified ring lug
terminal connector sized for the wire gauge being
used. The connector must be fixed using the
crimping tool specified by the connector
manufacturer.
Inverter Model
HP
1/4
L200-002NFEF/NFU
1/2
L200-004NFEF/NFU
3/4
L200-005NFEF
1
L200-007NFEF/NFU
1 1/2
L200-011NFEF
2
L200-015NFEF/NFU
3
L200-022NFEF/NFU
5
L200-037LFU
7 1/2
L200-055LFU
10
L200-075LFU
1/2
L200-004HFEF/HFU
1
L200-007HFEF/HFU
2
L200-015HFEF/HFU
3
L200-022HFEF/HFU
4
L200-030HFEF
5
L200-040HFEF/HFU
7 1/2
L200-055HFEF/HFU
10
L200-075HFEF/HFU
Wiring Size
Range (AWG)
30—16
30—14
L200 Inverter
Power Terminal
Wiring Size
ft-lbs
Range (AWG)
16
0.6
14
12
0.9
10
12
10
1.5
8
16
0.9
14
12
1.5
Torque
ft-lbs
(N-m)
0.16—0.19 0.22—0.25
0.37—0.44
0.5—0.6
Terminal (ring lug)
xiii
Torque
(N-m)
0.8
1.2
2.0
1.2
2.0
Cable support
Cable

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents