Step-by-Step Basic Installation
Please use the terminal arrangement below corresponding to your inverter model.
Inverter models L200–002NFEF/NFU, –004NFEF/NFU, –005NFEF
NFEF, NFU
LFU, HFEF, HFU
NOTE: An inverter powered by a portable power generator may receive a distorted
power waveform, overheating the generator. In general, the generator capacity should be
five times that of the inverter (kVA).
CAUTION: Be sure that the input voltage matches the inverter specifications:
• Single/Three phase 200 to 240 V 50/60 Hz (up to 2.2kW) for NFEF/NFU models
• Three phase 200 to 240V 50/60Hz (above 2.2kW) for LFU models
• Three phase 380 to 480 V 50/60Hz for HFEF models
CAUTION: Be sure not to power a three-phase-only inverter with single phase power.
Otherwise, there is the possibility of damage to the inverter and the danger of fire.
Jumper
+1
L1
L2 N/L3
Inverter models L200–007NFEF to –022NFEF,
–037LFU, –004HFEF/HFU to –040HFEF/HFU
+1
+
L1
L2 N/L3
L1
L2
Inverter models L200–055LFU, –075LFU, –055HFEF/HFU,
–075HFEF/HFU
L1
L2
+1
+
+
U/T1 V/T2 W/T3
Chassis
Ground
Jumper
U/T1
V/T2 W/T3
U/T1 V/T2 W/T3
L3
U/T1 V/T2 W/T3
L3
Jumper
Chassis
Ground
Chassis
Ground