Software Lock Mode

The software lock function keeps personnel from accidentally changing parameters in
the inverter memory. Use B031 to select from various protection levels.
The table below lists all combinations of B031 option codes and
the ON/OFF state of the [SFT] input. Each Check
indicates whether the corresponding parameter(s) can be edited.
The Standard Parameters column below shows access is permit-
ted for some lock modes. These refer to the parameter tables
throughout this chapter, each of which includes a column titled
Run Mode Edit as shown to the right. The marks (Check
Ex ) under the "Run Mode Edit" column title indicate whether access applies to each
parameter as defined in the table below. In some lock modes, you can edit only F001 and
the Multi-speed parameter group that includes A020, A220, A021–A035, and A038
(Jog). However, it does not include A019, Multi-speed operation selection. The editing
access to B031 itself is unique, and is specified in the right-most two columns below.
B031
Lock
Intelligent
Mode
00
01
02
03
NOTE: Since the software lock function B031 is always accessible, this feature is not
the same as password protection used in other industrial control devices.
[SFT]
Standard Parameters
Input
Stop
OFF
ON
OFF
ON
(ignored)
(ignored)
or Ex
or
F001 and
Multi-Speed
Run
Stop & Run
Run mode
edit access
Run mode
edit access
3–35
L200 Inverter
Run
Mode
Edit
B031
Stop
Run