Hitachi L200 Series Instruction Manual page 249

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Hide thumbs Also See for L200 Series:
Table of Contents

Advertisement

Func.
Name
Code
B021
Overload restriction
operation mode
B022
Overload restriction
setting
B023
Deceleration rate at
overload restriction
B031
Software lock mode
selection
B032
Reactive current setting
B080
[AM] analog signal
gain
B082
Start frequency adjust-
ment
B083
Carrier frequency
setting
"B" Group Fine Tuning Functions
R/W
Description
R/W Select the operating mode
during overload conditions,
three options, option codes:
00... Disabled
01... Enabled for acceleration
and constant speed
02... Enabled for constant
speed only
R/W Sets the level for overload
restriction, between 20% and
150% of the rated current of
the inverter, setting resolution
is 1% of rated current
R/W Sets the deceleration rate when
inverter detects overload, range
is 0.1 to 30.0, resolution is 0.1
R/W Prevents parameter changes, in
four options, option codes:
00... all parameters except
B031 are locked when [SFT]
terminal is ON
01... all parameters except
B031 and output frequency
F001 when [SFT] terminal is
ON
02... all parameters except
B031 are locked
03... all parameters except
B031 and output frequency
F001 setting are locked
R/W Calibrate detection of motor's
reactive (no load) current for
current monitor, electric
thermal setting, and overload
restriction setting
R/W Adjust of analog output at
terminal [AM],
range is 0 to 255
R/W Sets the starting frequency for
the inverter output, range is 0.5
to 9.9 Hz
R/W Sets the PWM carrier (internal
switching frequency), range is
2.0 to 14.0 kHz
B–33
L200 Inverter
Network Data
Reg.
Range
Res.
0092h
0, 1, 2
0093h
2000 to
0.01%
15000
0094h
1 to 300
0.1 sec
0095h
0, 1, 2, 3
00E8h
50 to
1%
200
0096h
0 to 255
0098h
5 to 99
0.1 Hz
0099h
20 to
0.1 Hz
140