Write in Coils [0Fh]:
This function writes data in consecutive coils. An example follows:
• Change the state of intelligent input terminal [1] to [5] of an inverter having a slave
address "5."
• This example assumes the intelligent input terminals have terminal states listed below.
Item
Intelligent input terminal
Coil number
Terminal status
Query:
No.
Field Name
1
Slave address *1
2
Function code
3
Coil start number
(high order)
4
Coil start number
(low order)
5
Number of coils
(high order)
6
Number of coils (low
order)
7
Byte number *2
8
Change data
(high order) *2
9
Change data
(low order) *2
10
CRC-16 (high order)
11
CRC-16 (low order)
Note 1:
Broadcasting is disabled.
Note 2:
The change data is a set of
high-order data and low-order
data. So when the size (in
bytes) of data to be changed is
an odd number, add "1" to the
data size (in bytes) to make it
an even number.
Data
[1]
[2]
[3]
7
8
9
ON
ON
ON
Response:
Example
No.
(Hex)
05
1
0F
2
00
3
4
07
5
00
6
06
7
8
02
17
00
DA
EF
L200 Inverter
[4]
[5]
10
11
OFF
ON
Example
Field Name
Slave address
Function code
Data size (in bytes)
Coil data *3
Number of coils
(high order)
Number of coils
(low order)
CRC-16 (high order)
CRC-16 (low order)
B–15
(Hex)
05
0F
00
07
00
06
65
8C

Hide quick links: