Hitachi L200 Series Instruction Manual page 171

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Hide thumbs Also See for L200 Series:
Table of Contents

Advertisement

The alarm relay output can be configured in two main ways:
• Trip/Power Loss Alarm – The alarm relay is configured as normally closed
(C036=1) by default, shown below (left). An external alarm circuit that detects broken
wiring also as an alarm connects to [AL0] and [AL1]. After powerup and short delay
(< 2 seconds), the relay energizes and the alarm circuit is OFF. Then, either an inverter
trip event or an inverter power loss will de-energize the relay and open the alarm
circuit.
• Trip Alarm – Alternatively, you can configure the relay as normally open (C036=0),
shown below (right). An external alarm circuit that detects broken wiring also as an
alarm connects to [AL0] and [AL2]. After powerup, the relay energizes only when an
inverter trip event occurs, opening the alarm circuit. However, in this configuration, an
inverter power loss does not open the alarm circuit.
Be sure to use the relay configuration that is appropriate for your system design. Note
that the external circuits shown assume that a closed circuit = no alarm condition (so that
a broken wire also causes an alarm). However, some systems may require a closed
circuit = alarm condition. In that case, then use the opposite terminal [AL1] or [AL2]
from the ones shown.
N.C. contacts (C036=01)
During normal operation
AL0
AL1
AL2
Power
Alarm
supply
device
Run
Power
Mode
ON
Normal Closed
ON
Trip
OFF
When an alarm occurs
or when power is OFF
AL1
AL2
AL0
Power
Alarm
supply
device
AL0–
AL0–
AL1
AL2
Open
Open
Closed
Open
Closed
N.O. contact (C036=00)
During normal operation
or when power is OFF
AL1
AL2
AL0
Power
Alarm
supply
device
Run
Power
Mode
ON
Normal
ON
Trip
OFF
4–43
L200 Inverter
When an alarm occurs
AL1
AL2
AL0
Power
Alarm
supply
device
AL0–
AL0–
AL1
AL2
Open
Closed
Closed
Open
Open
Closed

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents