Trip History And Inverter Status - Hitachi L200 Series Instruction Manual

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Hide thumbs Also See for L200 Series:
Table of Contents

Advertisement

Trip History and Inverter Status

We recommend that you first find the cause of the fault before clearing it. When a fault
occurs, the inverter stores important performance data at the moment of the fault. To
access the data, use the monitor functions (Dxxx) and select D081 for details about the
present fault (E
E
). Each error shifts D081–D082 to D082–D083, and writes the new error to D081.
n-2
The following Monitor Menu map shows how to access the error codes. When fault(s)
exist, you can review their details by first selecting the proper function: D081 is the most
recent, and D083 is the oldest.
). The previous two faults are stored in D082 and D083, with D(E
n
2
1
d
0 8 1
Error
exists?
Yes
2
E 0 9
2
1
1 0.0
2
1
2.5
2
1
28 4.0
2
1
1 5
2
1
1 8
1
Monitor Menu
2
1
d
0 8 3
2
d
0 8 2
FUNC.
No error
No
Trip
Conditions
Error Code
Output frequency
at trip point
Motor current
at trip point
DC bus voltage
at trip point
Cumulative inverter
operation time at
trip point
Cumulative power-
ON time at trip point
FUNC.
6–7
L200 Inverter
and
n-1
2
FUNC.