Software Lock

When the terminal [SFT] is turned ON, the data of all the parameters and functions
(except the output frequency, depending on the setting of B_31) is locked (prohibited
from editing). When the data is locked, the keypad keys cannot edit inverter parameters.
To edit parameters again, turn OFF the [SFT] terminal input.
Use parameter B_31 to select whether the output frequency is excluded from the lock
state or is locked as well.
Option
Terminal
Code
Symbol
15
SFT
Software Lock
C_01, C_02, C_03, C_04,
Valid for inputs:
C_05
B_31 (excluded from lock)
Required settings:
Notes:
When the [SFT] terminal is turned ON, only the
output frequency can be changed.
Software lock can include the output frequency by
setting B_31.
Software lock by the operator is also possible
without the [SFT] terminal being used (B_31).
Input
Function Name
State
ON
OFF
L100 Inverter
Description
The keypad and remote programming devices
are prevented from changing parameters
The parameters may be edited and stored
Example (requires input configuration—