Software Lock

When the terminal [SFT] is turned ON, the data of all the parameters and functions
(except the output frequency, depending on the setting of B031) is locked (prohibited
from editing). When the data is locked, the keypad keys cannot edit inverter parameters.
To edit parameters again, turn OFF the [SFT] terminal input.
Use parameter B031 to select whether the output frequency is excluded from the lock
state or is locked as well.
Option
Terminal
Code
Symbol
15
SFT
Software Lock
Valid for inputs:
C001~C005
Required settings
B031 (excluded from lock)
Notes:
When the [SFT] terminal is turned ON, only the
output frequency can be changed.
Software lock can include the output frequency
by setting B031.
Software lock by the operator is also possible
without the [SFT] terminal being used (B031).
Function Name
State
ON
OFF
Description
The keypad and remote programming devices are
prevented from changing parameters
The parameters may be edited and stored
Example (requires input configuration—
see
page
3–49):
SFT
5
4
3
See I/O specs on
page 4–6.
4 − 21
4 21
2
1
L PCS P24