J-Srx210 Services Gateway Cabinet Requirements - Dell PowerConnect J-SRX210 Hardware Manual

Powerconnect j-series services gateway
Hide thumbs Also See for PowerConnect J-SRX210:
Table of Contents

Advertisement

PowerConnect J-SRX210 Services Gateway Hardware Guide

J-SRX210 Services Gateway Cabinet Requirements

Related Topics
48
J-SRX210 Services Gateway Rack Requirements on page 49
Site Preparation Checklist for the J-SRX210 Services Gateway on page 45
Clearance Requirements for Airflow and Hardware Maintenance of the J-SRX210
Services Gateway on page 50
The J-SRX210 Services Gateway can be installed in a standard 800 mm (31.5 in.) or larger
enclosed cabinet. Table 20 on page 48 provides the details on cabinet size, clearance,
and airflow requirements.
Table 20: J-SRX210 Services Gateway Cabinet Requirements
Cabinet
Requirements
Specifications
Cabinet size
19 in. (48.3 cm) as defined in Cabinets, Racks, Panels, and Associated
Equipment (document number EIA-310–D) published by the Electronics
Industry Association (
You can mount the services gateway horizontally in the cabinet.
Clearance
The cabinet is at least 1 U (1.75 in. or 4.5 cm) high.
requirements
The outer edges of the mounting brackets extend the width of either chassis
to 19 in. (48.2 cm), and the front of the chassis extends approximately 0.5
in. (1.27 cm) beyond the mounting brackets.
The minimum total clearance inside the cabinet is 30.7 in. (78 cm) between
the inside of the front door and the inside of the rear door.
NOTE: The holes for the mounting brackets chassis are spaced 1.25 in. (3.2
cm) apart, measured from the center of the hole.
Cabinet airflow
Ensure sufficient ventilation through the cabinet is sufficient to prevent
requirements
overheating.
Ensure adequate cool air supply to dissipate the thermal output of the
device.
Install the device as close as possible to the front of the cabinet so that
the cable management system clears the inside of the front door. Installing
the chassis close to the front of the cabinet maximizes the clearance in
the rear of the cabinet for critical airflow.
Route and dress all cables to minimize the blockage of airflow to and from
the chassis.
NOTE: A cabinet larger than the minimum required provides better airflow
and reduces the chance of overheating.
General Site Guidelines for Installing the J-SRX210 Services Gateway on page 47
Site Preparation Checklist for the J-SRX210 Services Gateway on page 45
J-SRX210 Services Gateway Rack Requirements on page 49