Device Programming,
Other Programming
Tips
Continued
At any time during programming, you can access the Data Clear function by pressing the
<MODE> key. If you press the <ENTER> key in response to the "Clear All Codes" screen, you
effectively start over. You do get a second chance, however. If you press the <ENTER> key, a
second message on the LCD display asks you to "VERIFY CLEAR ALL CODES". If you select
"Y" with the cursor, all programming will be erased and you will be returned to the original LCD
display shown below.
If extra devices are programmed (meaning that more codes are programmed at the decoder than
MBZAM devices are programmed in the 4100 Programming Unit), the decoder will accept the
programmed codes, but will report EXTRA MAPNET DEVICE troubles for all of the extra
points.
If the same code is programmed twice (meaning two addresses represent a single code), the
decoder indicates this error by displaying a "DUPLICATE CODE" message. For example, if you
enter a code for a device that is a duplicate of the code entered for Device A-001 and press the
<ENTER> key, the decoder responds with the message shown below.
DUPLICATE CODE.
SAME AS A-001_
You must either change the entry, or use the <INC> or <DEC> key to scroll to the other entry.
CHNL A DEV 001