Download Print this page

Submenu - Logic 1 - 4 - MDT Technologies KNX Glass Push Button II Lite Technical Manual

Advertisement

Technical Manual
Glass Push Button II Lite [BE-GTLxxx.x1]
Sending condition
If a logic operation is fulfilled, the corresponding value is sent.
If the object type is "Switch", the
not automatic:
The output value is not sent automatically.
on incoming telegram: The output value is sent with every input telegram, regardless of whether the
output value has changed or not.
on change of output: The output value is only sent if the output value has changed.
on change of output (send only "0"): The output value is only sent if the output value changes and the
result of the logic operation is "0".
on change of output (send only "1"): The output value is only sent if the output value changes and the
result of the logic operation is "1".
Invert output
With the "switch" object type, the output can be inverted, thus turning a "0" into a "1" and a "1" into a "0".
The following table shows the associated communication objects:
No.
Name/Object function
52
Logic 1 – Output:
Switch, Value, Scene
+3
next Logic – Output
Table 49: Communication objects – Logic: Output objects
4.5.3 Submenu – Logic 1 - 4
A submenu is displayed for each activated logic. The following table shows all available settings:
ETS Text
Logic object A/B
(external)
Internal Input 1/2
MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany
Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de
"Sending conditions"
Length
Usage
Output of the logic operation.
DPT according to parameter setting.
Dynamic range
[Default value]
not active
normally active,
with preallocation "0"
inverted active,
with preallocation "0"
normally active,
with preallocation "1"
inverted active,
with preallocation "1"
not active
button 1 - 4
are as follows:
Comment
Activation of external logic objects. The
preallocation defines the value of the
external logic object after a bus power
return, up to a value being received.
Activation of the internal logic objects.
The number of buttons depends on the
device type.
56 / 63