Technical Manual
Glass Push Button II Lite [BE-GTLxxx.x1]
ETS Text
Time for long keypress
Time for extra long
keypress
Table 11: Settings – Switch
Innovative group control
With this function, it is possible to send to up to three different group addresses by pressing a button for a
longer time. The time for the long and the extra-long keystroke is set individually.
Two-button function: The sending behaviour for the long and the extra-long group can be set
■
individually.
Single-button function: The value defined in the sub-function is always sent for the long and the
■
extra-long group.
Notes:
All groups are always sent one after the other.
Example:
Time for long keypress:
If the key is now pressed for at least 4 seconds, the first value is transmitted immediately, after 2 seconds
the value for "group long" and after 4 seconds the value for "group extra long".
4.3.2.1 Switching with two-button function
Two-button function
With the two-button function, the value (ON/OFF) can be assigned to the upper/left and lower/right button.
Thus, the upper/left or lower/right button sends the set, fixed value.
Button assignment ON/OFF: The upper/left button sends the value "ON", the lower/right button sends
■
the value "OFF".
Button assignment OFF/ON: The upper/left button sends the value "OFF", the lower/right button sends
■
the value "ON".
Note:
For details on the Innovative group control, see
The following table shows the available communication objects:
No.
Name/Object function
0
PB1/2: – Switch
2
PB1/2 Group long: – Switch
4
PB1/2 Group extra long: – Switch
Table 12: Communication objects – Two-button function: Switch
MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany
Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de
Dynamic range
Comment
[Default value]
basic setting
Setting from when a long keypress is detected.
0,1 s - 30,0 s
Basic setting refers to the time at menu "Button
functions".
0,1 s - 30,0 s
Setting from when an extra long keypress is
[2,0 s]
detected.
2 s
Time for extra long keypress:
4.3.2 Switch
Length
Usage
1 Bit
Switch function.
1 Bit
Switch function for long keypress.
1 Bit
Switch function for extra long keypress.
4 s
(General).
24 / 63