9-3. Communication Speed and Format Setting

Sets communication method for the Ethernet port (LINK1, LINK2) by the switch on the NCW-3DNIP's rear panel.
"AUTO (automatic detection)" is set before the shipment, so setting usually isn't
required.
Set it manually (MANUAL) if the communication method of the PLC (EtherNet/IP master) cannot be changed.
*: The setting should be same as the communication method of the PLC (EtherNet/IP master).
The communication won't be available or will be unstable if the settings aren't matched between devices.
Switch
No.
LINK1
1
method
LINK1
2
speed
LINK1
3
format
4
Reserved
LINK2
5
method
LINK2
6
speed
LINK2
7
format
8
Reserved
Rear panel of converter
Item
c
OFF: AUTO (automatic detection)
ommunication
ON : MANUAL(Sets the switch No.2 and 3 manually.)
c
OFF: 100Mbps
ommunication
ON: 10Mbps
c
OFF: Full-Duplex
ommunication
ON: Half-Duplex
Fixed at OFF
(Don't turn "ON".)
c
OFF: AUTO (automatic detection)
ommunication
ON : MANUAL(Sets the switch No.6 and 7 manually .)
c
OFF: 100Mbps
ommunication
ON: 10Mbps
c
ommunication
OFF: Full-Duplex
ON: Half-Duplex
Fixed at OFF
(Don't turn "ON".)
Communication
setting switch
Setting description
26
Factory
setting
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF