11-5. NCW-3DNIP Indicator
11-5-1. Status indicator (MS/NS)
Error contents can be checked by lighting status of the status indicator (MS/NS) when an error occurs.
Check the contents and take appropriate measures.
Light status
MS
NS
Green
Green
Flashing
Flashing
Green/
Green/
Red
Red
OFF
OFF
Flashing
OFF
Green
Flashing
-
Red
Red
-
Flashing
Green
Green
Flashing
Green
Red
Green
Red
Name
Normal operation
Indicates that it is in the normal communication.
Self-test
MS/NS indicators alternately blink each 0.25s.
The power doesn't supply to NCW-3DNIP.
- Check wirings of the power supply terminal block of NCW-3DNIP.
No power
- Check that the power voltage is within the range of specification.
- Check whether the power supply capacities are enough or not.
The converter cannot get a valid IP address.
No IP address
(This error is detected only when the automatic IP address setting is selected.)
Check the BOOTP or DHCP server operates in the network system.
Major Recoverable
The sensor error (SE) occurred.
Fault
For more details, refer to "11-5-3".
NCW-3DNIP has the internal error (RDY LED is OFF).
Major Unrecoverable
Restart the power supply. Hardware might have a malfunction if the
Fault
operation is not back to normal. Thus, replace the converter.
No connections
Communication is available, but a connection is not established.
Detects one or more connection is timeout during the communication.
- The communication band width of the whole network system might be
lack. Reallocate the communication band width of the whole network
Connection timeout
system including NCW-3DNIP RPI setting by the configuration tool.
- Irregular communication interrupt might have occurred. Investigate a
conceivable cause in the system.
Duplicate IP address
The IP address is duplicated in the network.
Cause and Countermeasure
82
Need help?
Do you have a question about the ABSOCODER NCW-3DNIPLW and is the answer not in the manual?