Chapter 8 Appendix
8.1 Specification
8.1.1 System Specification
◼ Specification for Fluorinated Fluid (Wide Temperature)
Table 8-1
Model
Cooling Method
*1
Cooling Capacity
(50Hz/60Hz)
Operating Temperature Range
Temperature Stability
Circulating Fluid
Refrigerant
Quantity of Refrigerant
*4
Pump Capacity
*5
Main Tank Capacity
*6
Sub-tank Capacity
Circulating Fluid Port
Facility Water
Rated
Facility Water
Condition
Required Flow
Temp. Changing
Rate
Condition
Facility Water Port
Power Supply
Breaker Size
*7
Dimensions
*8
Weight
Communication
*1: The capacity is derived under the conditions that the circulating fluid temp is 20 deg. C, the facility water temp. is 25 deg.
C and that the circulating fluid flow rate is obtained at a specified flow rate of pump capacity.
*2: This is a system output temperature, with flow rate defined in pump capacity secured, when stabilized with no disturbance.
Its upper limit may be violated if an insufficient amount of the circulating fluid is present or a disturbance to flow rate is
observed.
®
*3: Galden
is a registered trademark of Solvay, and Fluorinert
*4: The capacity is derived at the Outlet of this system when the circulating fluid temp. is at 20 deg. C and maximum frequency
operation by inverter.
*5: This is a minimum amount of the fluid for operation of the Thermo Chiller outfitted with internal piping and heat exchanger
in this system. Circulating fluid temp.: 20deg. C
*6: For circulating fluid containment during line purge back or back flow. This is the volume of free space in Sub-Tank when
fluid level is at "High" level. Main-Tank capacity is excluded.
*7: This is the dimensions of panels, which is derived without protrusions such as a breaker handle.
*8: This is the mass of the system when it contains no circulating fluid.
*9: The required flow rate when the cooling capacity load is applied under the condition in *1.
*10: Temporarily required flow rate when set temperature is changed under the facility water temp.25 deg. C.
*11: The value of IPCC (Intergovernmental Panel on Climate Change) Forth Assignment Report: Climate Change 2007 (AR4).
HRZF Series
Specification for Fluorinated Fluid (Wide Temperature)
kW
deg. C
deg. C
Galden
Galden
kg
MPa
L
L
deg. C
/MPa
*9
L/min
*10
A
mm
kg
Serial RS-485 (Dsub-9pin), Contact Signal (Dsub-25pin)
HRZF010-WS
Water Cooled Refrigerant
10
-20.0 to 90.0
±0.1
®
*3
TM
HT135
Fluorinert
®
*3
HT200
Fluorinert
(No Intrusion of Foreign Body)
R454C (HFO/HFC, GWP148)
1.5
0.72 (At 20L/min)
(104[PSIG] At 5.3 [gal/min])
Approx.15 (4 [gal])
Approx.16 (4.2 [gal])
Rc 3/4
10 to 30 / 0.3 to 0.7 (45 to 100 [PSIG])
15
15
Rc 1/2
3-phase 50/60Hz AC200/200 to 208V±10%
30
W380D870H950
(W14.96xD34.25xH37.40[inch])
165 (364 [lbs.])
TM
is a trademark of U.S. 3M.
DOC1046494-2
Chapter 8 Appendix
*2
*3
FC-3283
(-20 to 40 deg. C)
TM
*3
FC-40
(20 to 90 deg. C)
*11
8.1 Specification
8-1