Item
Baseline Built for
Aging Reference
(Continued)
7.6.5

Parallel Setting

Path:
→ Parallel Setting
Item
Parallel Group ID
Parallel ID
Common Battery
Ultron DPM Gen2 Series
When the test is failed, the following screen will pop up.
Click 'YES' to go back to the original screen and contact
service personnel for failure reasons.
The UPSs in parallel connection must be assigned the
same parallel group ID no. in order to let the outputs of the
parallel UPSs be put in parallel connection and let the
loads be evenly distributed among the parallel units.
If the parallel UPSs have different parallel group ID no.,
their output signals might be synchronized but their
outputs cannot be connected in parallel.
The UPSs that need to be paralleled must be assigned the
same parallel group ID no. and different parallel ID no. in
order to let the parallel function work.
If the parallel UPSs that have the same parallel group ID
no. need to share common batteries, please select 'Enable'
for the 'Common Battery' setup item. Otherwise, the
function of battery abnormality detection will fail. For more
information about common battery, please refer to
External Battery Cabinet Connection Warnings
144