5.2 Installation Environment maintenance. Please refer to • Only authorized Delta engineers or service personnel can perform installation and maintenance. If you want to install the UPS by yourself, please install it under the supervision of authorized Delta engineers or service personnel.
Page 8
Application of the protective devices shall be in accordance with local installation codes. 1200kW 1500kW 690V/ 2000A 690V/ 2500A 5. Each protective device should have the functions of overcurrent protection, short circuit protection, insulating protection and shunt trip feature. Delta UPS DPM Gen2 1200/ 1500 kVA...
• Do not open or remove the covers or panels of the UPS to avoid high-voltage electric shock. Only authorized Delta engineers or service personnel can do so for installation or maintenance. If you want to open or remove the covers or panels, do it only under the supervision of authorized Delta engineers or service personnel.
Page 10
Please note that the battery grounds mean any battery pole (+/ -) connecting to the ground. • You must contact Delta customer service if any of the following events occurs: 1. Any liquid is poured or spilled on the UPS.
Storage Warnings • Use the original packing materials to pack the UPS to prevent any possible damage from rodents. • If the UPS needs to be stored prior to installation, it should be placed in a dry indoor area. The allowable storage temperature is below 158°F (70°C) and relative humidity is below 95%.
Please check if any item is missing according to the following package list. If the UPS needs to be returned, carefully repack the UPS and all of the accessories using the original packing materials that came with the unit. 1200kW UPS Pallet Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 13
Item Q’ty UPS System Cabinet 1 PC ❶ User Manual 1 PC ❷ RS-232 Cable 1 PC ❸ Parallel Cable 1 PC ❹ Key (for the UPS system cabinet) 2 PCS ❺ Key (for the power modules) 4 PCS ❻ Rodent Shield 14 PCS ❼...
Functions & Features • True on-line double-conversion UPS adopts DSP chip and IGBT technology to protect your sensitive electronic equipment from power interruption. • Wide AC input voltage range (360 Vac ~ 552 Vac) reduces frequent transfer from On-Line mode to Battery mode to save battery consumption and prolong battery life.
& cover removal, maintenance and operation. If you want to execute any action mentioned above by yourself, the action must be under the supervision of authorized Delta engineers or service personnel. Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 19
After you remove the UPS system cabinet’s right and left front panels, you will see Figure 2-5 the wiring terminals that need to connect to the power modules (see (UPS System Cabinet) Wiring Terminals that Need to Connect to the Power Modules (Figure 2-5: 1200/ 1500kW UPS_ Wiring Terminals that Need to Connect to the Power Modules) For wiring terminals that need to connect to the input power, external battery cabinet...
Page 20
(UPS System Cabinet) Battery Terminals (+/ -) UPS Output Terminals (L1/ L2/ L3) (Figure 2-6: 1200/ 1500kW UPS_ Wiring Terminals that Need to Connect to the Input Power, External Battery Cabinet and Critical Loads) Delta UPS DPM Gen2 1200/ 1500 kVA...
Power Modules 2.6.1 Front View For 1200kW UPS, there are four power modules, two of which must be installed at the right-hand side of the UPS system cabinet and the remaining two at the left-hand side of the UPS system cabinet. For 1500kW UPS, there are five power modules, three of which must be installed at the right-hand side of the UPS system cabinet and the remaining two at the left-hand side of the UPS system cabinet.
Page 22
Power Modules Power Modules (Figure 2-8: 1500kW UPS_ Front View of the Power Modules) Power Module Unscrew the Eight Screws (Figure 2-9: How to Remove the Power Module’s Front Door) Delta UPS DPM Gen2 1200/ 1500 kVA...
& cover removal, maintenance and operation. If you want to execute any action mentioned above by yourself, the action must be under the supervision of authorized Delta engineers or service personnel. The power modules must be connected with the UPS system cabinets. Please refer to the following figures for details.
Page 24
Input Terminals (L3) Output Terminals (L3) GND ( ) Terminals Connect to the UPS System Cabinet (Figure 2-11: 1200kW UPS_ Wiring Terminals that Need to Connect to the Right-hand Side of the UPS System Cabinet) Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 25
Power Modules Input Terminals (L1) Output Terminals (L1) Battery Input Terminals + Input Terminals (L2) Output Terminals (L2) Battery Input Terminals - Input Terminals (L3) Output Terminals (L3) GND ( ) Terminals Connect to the UPS System Cabinet (Figure 2-12: 1500kW UPS_ Wiring Terminals that Need to Connect to the Right-hand Side of the UPS System Cabinet)
For information about the 10” color touch panel, please refer to & Settings The buzzer is located at the rear of the UPS system cabinet’s middle front door. Please refer to the figure below. (UPS System Cabinet) Buzzer (Figure 2-14: Buzzer Location) Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 27
Table 2-1: Tri-color LED Indicator, UPS Operation Mode & Buzzer Tri-color LED Status Meaning Indicator It indicates that the UPS is operating in one of the • following modes. Text on the LCD Screen UPS Operation Mode (upper-right corner) Green On-Line Mode ‘On-Line’...
Bypass mode, Manual Bypass mode, ECO mode, Green mode, Clean mode and Energy Recycle mode. NOTE: The UPS must be connected with an external maintenance bypass cabinet (user-supplied, handled and configured by Delta service personnel). For information regarding the external maintenance bypass 1.2 Connection Warnings cabinet, please refer to 2.
On-Line Mode In On-Line mode, the main AC source supplies AC power via the external maintenance bypass cabinet’s Input Breaker (Q1) to the rectifier, and the rectifier converts the AC power to DC power and supplies the DC power to the inverter. In the meantime, the rectifier provides charging power to the batteries.
Battery mode, the UPS’s tri-color LED illuminates yellow and the text ‘Battery’ appears in the upper right corner of the LCD screen. External Maintenance Bypass Cabinet Static Switch BYPASS Inverter LOAD MAIN Rectifier Batteries Converter (Figure 3-2: Battery Mode Diagram) Delta UPS DPM Gen2 1200/ 1500 kVA...
Bypass Mode When the inverter encounters abnormal situations such as over temperature, overload, short circuit, abnormal output voltage or low battery, it will automatically shut itself down. If the UPS detects the bypass input is normal, it will automatically switch to Bypass mode to protect the connected critical loads from power interruption.
UPS’s input power is completely cut off, and the critical loads are not protected. At the moment, the UPS’s tri-color LED and LCD screen are both off. External Maintenance Bypass Cabinet Static Switch BYPASS Rectifier Inverter LOAD MAIN Batteries Converter Figure 3-4: Manual Bypass Mode Diagram) Delta UPS DPM Gen2 1200/ 1500 kVA...
ECO Mode After the UPS is manually set as ECO mode via the LCD, the UPS will work in Bypass mode if bypass input voltage and frequency are within ± 10% of the rated voltage and ± 5 Hz of the rated frequency respectively. Otherwise, the UPS will run in On-Line mode.
UPS. During Green mode, the UPS’s tri-color LED illuminates green and the text 'Green' appears in the upper right corner of the screen. External Maintenance Bypass Cabinet Static Switch BYPASS Rectifier Inverter MAIN LOAD Batteries Converter (Figure 3-6: Green Mode) Delta UPS DPM Gen2 1200/ 1500 kVA...
Clean Mode After the UPS is manually set as Clean mode via the LCD, the system will automatically detect the output status to let the inverter provide active filter function to compensate harmonics, correct power factor and reduce bypass reactive current to improve overall power quality.
Recycle mode, the UPS’s tri-color LED illuminates yellow and the text 'Energy Recycle' appears in the upper right corner of the screen. External Maintenance Bypass Cabinet Static Switch BYPASS Rectifier Inverter LOAD MAIN Batteries Converter (Figure 3-8: Energy Recycle Mode) Delta UPS DPM Gen2 1200/ 1500 kVA...
Chapter 4 : Communication Interfaces The communication interfaces are located at two different places. One is on the front of the UPS system cabinet with its middle front door open and the other is at the rear of the touch panel. (UPS System Cabinet) Communication Interfaces (I)
Page 38
Contacts Contacts Contacts RS-485 RS-232 Synchronization Port Port Connector Auxiliary Power Card Slot Auxiliary Power Card Auxiliary Power Card (Reserved) Auxiliary Power Card’s Switch Auxiliary Power Card’s Switch (Figure 4-2: Communication Interfaces (I)) Delta UPS DPM Gen2 1200/ 1500 kVA...
4.1.1 USB Port & RS-232 Port The USB port & RS-232 port are available for authorized service personnel. USB Port RS-232 Port (Figure 4-3: USB Port & RS-232 Port) 4.1.2 Parallel Communication Cards The UPS has two parallel communication cards, which are master parallel communication card and backup parallel communication card.
Please refer to to route the parallel cables. WARNING: One parallel cable is provided in each UPS’s accessory package. Using non- Delta parallel cables to parallel the UPSs may cause failure, malfunctions and accidents. Parallel Port Parallel Port (Figure 4-5: Parallel Ports) 4.1.4...
4.1.5 Display Port Before shipment, the display port has been connected to the 10” touch panel with the designated cable in Delta factory. Display Port (Figure 4-7: Display Port) 4.1.6 REPO Dry Contacts Connect the REPO dry contacts to a user-supplied switch so you can remotely shut down the UPS when an emergency occurs.
(NO) or normally closed (NC). Each dry contact can be assigned a specific event. Six out of twenty-four events can 7.6.6 be assigned according to your applications. Please refer to the table below and Dry Contact Setting Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 43
NOTE: Since the output dry contacts belong to the secondary circuit, the voltage of each dry contact’s connected device should not exceed 30 Vdc to avoid electric shock or insufficient insulation. (Figure 4-11: Output Dry Contacts & Schematic)
Page 44
UPS transfers to Manual Bypass mode. The external battery cabinet’s temperature Battery Over Temperature is too high. Output Voltage Abnormal The output voltage is abnormal. Battery Need Replacement The battery replacement date is due. Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 45
Event Description The bypass static switch temperature is too Bypass Over Temperature high. The bypass static switch has an open/ short Bypass Static Switch Fault issue. UPS Over Temperature The UPS temperature is too high. When the EPO button is pressed, the UPS Battery Breaker Shunt Trip will send a signal to the connected external via EPO...
Six out of fourteen events can be assigned according to your 7.6.6 Dry Contact Setting applications. Please refer to the table below and (Figure 4-12: Input Dry Contacts & Schematic) Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 47
Event Description None No set-up. Generator Status Generator status detection. Battery Ground Fail Battery leakage detection. External Battery Breaker Status detection of the external battery Detection cabinet’s breaker. Charger Off Turn off the charger. In Bypass mode: the UPS will remain to run in Bypass mode.
NOTE: If you use non-Delta lithium-ion batteries, you must use the LCD to set up 7.6.6 Dry Contact Setting Charger Off; please refer to . For settings relevant to 7.6.4 Battery & Charging the non-Delta lithium-ion batteries, please refer to Setting .
4.1.13 Auxiliary Power 48 Vdc For application, you can use the interfaces to either provide 48 Vdc isolated power (Max. 2A) for external use or connect an external device to cut off its circuit breaker. Connect to an External Device (Figure 4-15: Auxiliary Power 48 Vdc Application &...
(ex. generator, UPS, grid, etc.). The signal cables used for connection must have a minimum rating of 600V and need connecting to phase L1 (red wire) and phase L2 (white wire). Below figure is an example. Delta UPS DPM Gen2 1200/ 1500 kVA...
Please refer to Interfaces 2. If you use the Delta lithium-ion batteries, you must install the optional multifunctional communication card (MFC) into the SMART slot to monitor the battery status. For settings and information relevant to the Delta lithium-ion 7.6.4 Battery &...
When replacing, remove only one auxiliary power card at a time to avoid power interruption. Auxiliary Power Card Auxiliary Power Card Auxiliary Power Card Slot (Reserved) Auxiliary Power Card's Auxiliary Power Card's Switch Switch (Figure 4-22: Auxiliary Power Cards) Delta UPS DPM Gen2 1200/ 1500 kVA...
❷ (RS-485 Port) 2. Connect the port to a user-supplied monitoring system. Connect the port to the Delta battery management system (optional). The BMS function is only ❸ applicable to lead-acid batteries. Before shipment, the DISPLAY port has been DISPLAY ❹...
(Figure 4-24: Open the Middle Front Door & Remove the Top Cover) Step 2 Connect the cables to the communication interfaces and route the cables through the snap bushings and the top of the cabinet. Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 55
Top Cable Entry Route the Cables through the Snap Bushings and the Top of the Cabinet (UPS System Cabinet) Snap Bushings Connect the Cables to the Communication Interfaces (Figure 4-25: Top Cable Entry for the Communication Interfaces) Bottom Cable Entry: Step 1 Open the UPS system cabinet’s middle front door, and remove the left front door, top cover and bottom cover shown below.
Page 56
Please follow local and national electrical codes to select cable sizes and install proper conduits and bushings for cable protection. 5.3 UPS Installation 2. Only when is completed can you perform wiring. 3. Cable ties are user-supplied and the quantity depends on on-site requirements. Delta UPS DPM Gen2 1200/ 1500 kVA...
& cover removal, maintenance and operation. If you want to execute any action mentioned above by yourself, the action must be under the supervision of authorized Delta engineers or service personnel. If you use a forklift or other equipment to move the UPS, please make sure its load bearing is Table 5-1 sufficient.
Page 58
90%. The highest operating altitude is 3280 ft (1000 m) above sea level. For safety concerns, we suggest that you: • 1. Equip surroundings of the installation area with CO or dry powder fire extinguishers. Delta UPS DPM Gen2 1200/ 1500 kVA...
2. Install the UPS in an environment where fireproof materials are used to construct the walls, floors and ceilings. 3. Install the UPS on a floor that is made from noncombustible materials. Do not allow unauthorized personnel entering the installation area and assign •...
Page 60
(Power Modules) Left Right (Figure 5-3: 1200kW UPS_ Power Modules) (Power Modules) Left Right (Figure 5-4: 1500kW UPS_ Power Modules) Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 61
Step 3 Use the provided M10 screws (tightening torque: 217 ± 8 lb-in (250 ± 10 kgf-cm)) to join the UPS system cabinet and power modules. The joining points are shown in the figure below. Joining Points for the UPS System Cabinet &...
Page 62
(Front of the UPS System Cabinet) Balance Bracket Floor M12 Expansion Bolt (UltimateTensile Force: 3413 lbf (1548 kgf) & Ultimate Shear Force: 6477 lbf (2938 kgf)) (Figure 5-8: Fix the Stands on the Ground_ System Cabinet) Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 63
(Front of the Power Module) Balance Bracket Floor M12 Expansion Bolt (UltimateTensile Force: 3413 lbf (1548 kgf) & Ultimate Shear Force: 6477 lbf (2938 kgf)) (Figure 5-9: Fix the Stands on the Ground_ Power Module) WARNING: If you don’t fix the UPS stands on the ground, the UPS might topple over. For safety concerns, please fix the UPS stands on the ground firmly.
Page 64
Connect 32YL signal wire to the CNY1 port. 2. Connect 33YL signal wire to the CNY2 port. 3. Connect 32YR signal wire to the CNY1 port. 4. Connect 33YR signal wire to the CNY2 port. Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 65
CNY1 Port CNY2 Port Y Interface Boad 32YL Signal Wire 33YL Signal Wire CNY1 Port CNY2 Port Y Interface Boad 32YR Signal Wire 33YR Signal Wire (Figure 5-13: 1500kW UPS_ Connect the Four Signal Wires to the Four CNY Ports)
Step 7 It is suggested that you install the external maintenance bypass cabinet (user- supplied, handled and configured by Delta service personnel) next to the UPS or align it with the UPS for convenient operation. Step 8 5.4 Wiring Follow the instructions in...
Page 67
(1) default input/ output voltage: 480V, (2) default battery Q’ty: 40 PCS and (3) maximum charge current. For other Table 5-2 conditions different from , please contact Delta service personnel for relevant values. Table 5-2: Specifications of Input/ Output/ Battery Cables (Copper) and Breakers UPS Capacity...
Page 71
If you want to adopt the configuration of 1200kW with a 1600A input breaker or 1500kW with a 2000A input breaker, please contact Delta service personnel. The suggested manufacturer is Thomas & Betts. You may use equivalent terminals provided by other manufacturers.
Single Input to Dual Input Modification NOTE: 1. Only authorized Delta engineers or service personnel can modify single input to dual input setup. The UPS default setting is single input. If you want to modify it into dual input, please follow the steps below.
Page 73
Step 2 There are three copper bars in total. Each copper bar has 8 M12 screws, 16 Belleville washers, 16 flat washers and 8 M12 nuts. Use a socket wrench to remove 24 screws and 24 nuts for the removal of 3 copper bars.
Please contact Delta service personnel Terminals (+/ -) for battery configurations. Connect the terminal to the external maintenance bypass cabinet’s GND terminal ( ) and the PE (protective earth) external battery cabinet’s PE terminal ( Terminal Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 75
NOTE: The terminals listed in the above 'Item' column are all located at the front Figure 2-6 of the UPS system cabinet. Please refer to Table 5-5: External Maintenance Bypass Cabinet’s Breakers, Switches & Wiring Information Item* Description Input Breaker (Q1) including L1/ Connect the breaker to the main AC L2/ L3 terminals source.
For top wiring, remove the UPS system cabinet’s two front doors and remove the top cover. Remove Two Top Covers (Figure 5-17: 1500kW UPS_ Remove the Front Doors & Remove the Top Covers) Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 77
Route the cables from the top of the cabinet and connect the cables to the wiring terminals. Top Cable Entry (Figure 5-18: 1500kW UPS_ Top Cable Entry for the Wiring Terminals) Bottom Wiring ⚫ A. For bottom wiring, remove the UPS system cabinet’s two front doors and two bottom covers.
Page 78
UPS Output Terminals Loads (Q4) (L1/ L2/ L3/ N) Battery Input Terminals (+/ -) Connect to the Same Model of UPS(s) for Parallel Application External Battery Cabinet (Figure 5-21: Single Unit Single Input Wiring Diagram) Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 79
Step 7 Follow the table below to select proper Protective Earth (PE) cables to ground the UPS, external battery cabinet(s) and connected critical loads. The table is in accordance Table 250.122 with NEC . The grounding diagram below is for reference. UPS Capacity DPM 1200kW DPM 1500kW...
Connect the cables of the main AC source, bypass source, output and external battery cabinet(s) to the UPS and the external maintenance bypass cabinet. Please refer to Table 5-2 ~ Table 5-5 5.5 External Battery Cabinet Connection Warnings and the following diagrams to perform wiring. Delta UPS DPM Gen2 1200/ 1500 kVA...
Please adopt the Daisy Chain method shown in the figure below. For the parallel port Figure 4-2 4.3 Cable Routing location, refer to . For top or bottom cable entry, refer to for the Communication Interfaces NOTE: One parallel cable is provided in each UPS’s accessory package. Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 83
UPS) (Middle UPS(s)) (Last UPS) Parallel Ports Parallel Ports Parallel Ports Parallel Cable (Figure 5-24: Parallel Port Connection_ Daisy Chain Method) Step 3 Follow the table below to select proper Protective Earth (PE) cables to ground the parallel UPS units, external battery cabinet(s) and connected critical loads. The table Table 250.122 is in accordance with NEC .
Page 84
Before start-up of the parallel units, qualified service personnel must set each UPS’s 'Parallel Group ID' (1 or 2) and 'Parallel ID' (1 ~ 8) through the 7.6.5 LCD. Otherwise, the parallel UPSs cannot be started. Please refer to Parallel Setting Delta UPS DPM Gen2 1200/ 1500 kVA...
For relevant information, please refer to the manual of the lithium-ion batteries. 2. Whether you use lead-acid batteries or lithium-ion batteries, please contact Delta service personnel for any battery/ battery cabinet’s setup and configurations. WARNING: ...
Page 86
The default battery quantity is 40 PCS of 12V batteries connected in series. You • should use battery cables to connect the external battery cabinet(s) with the ‘+’ and ‘-’ terminals marked on the UPS system cabinet. Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 87
Ups System Cabinet's Battery Input Terminals Protective Device External Battery Cabinet (Figure 5-26: External Battery Cabinet Connection) WARNING: The electrolyte leakage of the batteries can lead to serious accidents. For safety concerns, you must insulate the batteries properly (using insulated trays or boxes) from the metal cabinets and racks.
Page 88
• breaker and/ or fast-acting DC fuse. If you want to buy any of them, please contact Delta service personnel. When choosing the protective device, follow the instructions below. (1) The protective device’s rated current must comply with the current values...
Page 89
External Battery Cabinet’s Protective Device (Option 1) Final Positive and Negative Poles’ Voltage ≥ 600 Vdc External Battery Cabinet DC Fuses 2-Pole DC Circuit Breaker or DC Isolated Switch (Figure 5-27: Installation of a 2-pole DC Circuit Breaker or DC Isolated Switch Connected in Series with a DC Fuse Fuse) External Battery Cabinet’s Protective Device (Option 2) Final Positive...
Page 90
Series with Two DC Fuses) External Battery Cabinet’s Protective Device (Option 4) Final Positive and Negative Poles’ Voltage ≥ 600 Vdc External Battery Cabinet 3-Pole DC Circuit Breaker (Figure 5-30: Installation of a 3-pole DC Circuit Breaker) Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 91
External Battery Cabinet’s Protective Device (Option 5) Final Positive and Negative Poles’ Voltage ≥ 600 Vdc External Battery Cabinet 4-Pole DC Circuit Breaker DC Fuses or DC Isolated Switch (Figure 5-31: Installation of a 4-pole DC Circuit Breaker or DC Isolated Switch Connected in Series with Two DC Fuses) External Battery Cabinet’s Protective Device (Option 6) Final Positive...
Page 92
For relevant information, please refer to the user manual of the lithium-ion batteries. Whether you use the lead-acid batteries or the lithium-ion batteries, please contact Delta service personnel for any battery/ battery cabinet’s setup and configurations. For common battery application, please install a protective device between each parallel UPS and its connected external battery cabinet(s).
Page 93
External Maintenance Bypass Cabinet BYPA. Static Switch Rectifier Inverter MAIN Converter LOAD External Maintenance Bypass Cabinet Batteries BYPA. Static Switch Rectifier Inverter MAIN Converter (Figure 5-33: Common Battery Diagram) External Battery Cabinet Alarm • When any external battery cabinet connected to the UPS has the following problems, the UPS system will sound an alarm.
Page 95
Step 1 Install the rodent shields at the front bottom of the UPS. Front of the UPS Front of the Front of the System Cabinet Power Modules Power Modules (Figure 5-34: 1500kW UPS_ Install the Rodent Shields) Step 2 Install the rodent shields G at the bottom of the two sides. Front of the Power Modules...
Page 96
Install the rodent shields at the rear bottom of the UPS. Rear of the UPS Rear of the Rear of the System Cabinet Power Modules Power Modules (Figure 5-36: 1500kW UPS_ Install the Rodent Shields) Delta UPS DPM Gen2 1200/ 1500 kVA...
4. The external battery cabinet’s breaker (Q5) shown on the LCD is always ON by default. To enable the detection of the Q5 status via the LCD, please contact Delta customer service for additional configurations. • Pre Start-up Warnings 1. Before UPS operation, ensure that installation and wiring have been completely 5.
Switch ON the external maintenance bypass cabinet’s Output Breaker (Q4). Step 6 After the inverter turns on, the UPS will run in On-Line mode, the LCD screen will show as below, and the tri-color LED indicator will illuminate green. Delta UPS DPM Gen2 1200/ 1500 kVA...
6.2.2 Battery Mode Start-up Procedures WARNING: 6.1 Pre Start-up & Pre Turn-off Before turning on the UPS, please read Warnings thoroughly and ensure that the precautions and instructions have been followed. Step 1 Ensure that the external maintenance bypass cabinet’s Manual Bypass Breaker (Q3) is in the OFF position.
Switch ON the external maintenance bypass cabinet’s Bypass Breaker (Q2) and Output Breaker (Q4). Step 3 Now, the UPS runs in Bypass mode, the LCD screen shows as below, and the tri-color LED indicator illuminates yellow. Delta UPS DPM Gen2 1200/ 1500 kVA...
6.2.4 Manual Bypass Mode Start-up Procedures WARNING: 6.1 Pre Start-up & Pre Turn-off 1. Before turning on/ off the UPS, please read Warnings thoroughly and ensure that the precautions and instructions have been followed. 2. In Manual Bypass Mode, make sure that all the switches and breakers (except for the external maintenance bypass cabinet’s Manual Bypass Breaker (Q3)) are in the OFF position before working on the UPS’s internal circuits to prevent electric shock.
Page 102
) on the LCD screen. Step 6 After the inverter turns on, the UPS will run in On-Line mode, the LCD screen will show as below, and the tri-color LED indicator will illuminate green. Delta UPS DPM Gen2 1200/ 1500 kVA...
6.2.5 ECO Mode Start-up Procedures WARNING: 6.1 Pre Start-up & Pre Turn-off Before turning on the UPS, please read Warnings thoroughly and ensure that the precautions and instructions have been followed. Step 1 Ensure that the external maintenance bypass cabinet’s Manual Bypass Breaker (Q3) is in the OFF position.
Page 104
After the inverter turns on and the system confirms that the bypass voltage is normal, the UPS will automatically transfer to ECO mode to let the bypass supply power, the LCD screen will show as below, and the tri-color LED indicator will illuminate green. Delta UPS DPM Gen2 1200/ 1500 kVA...
6.2.6 Green Mode Start-up Procedures WARNING: 6.1 Pre Start-up & Pre Turn-off Before turning on the UPS, please read Warnings thoroughly and ensure that the precautions and instructions have been followed. Step 1 Ensure that the external maintenance bypass cabinet’s Manual Bypass Breaker (Q3) is in the OFF position.
Page 106
(i.e. total load capacity %) to decide which specific power module(s) should be fully powered on or idle in order to achieve higher efficiency of the UPS. The LCD screen shows as below, and the tri-color LED indicator illuminates green. Delta UPS DPM Gen2 1200/ 1500 kVA...
6.2.7 Clean Mode Start-up Procedures WARNING: 6.1 Pre Start-up & Pre Turn-off Before turning on the UPS, please read Warnings thoroughly and ensure that the precautions and instructions have been followed. Step 1 Ensure that the external maintenance bypass cabinet’s Manual Bypass Breaker (Q3) is in the OFF position.
Page 108
The LCD screen shows as below, and the tri-color LED indicator illuminates green. Delta UPS DPM Gen2 1200/ 1500 kVA...
6.2.8 Energy Recycle Mode Start-up Procedures WARNING: 6.1 Pre Start-up & Pre Turn-off Before turning on the UPS, please read Warnings thoroughly and ensure that the precautions and instructions have been followed. NOTE: Energy Recycle mode is only applicable to single unit application. 2.
Page 110
Now, the UPS automatically transfers to run in Energy Recycle mode. The LCD screen shows as below, and the tri-color LED indicator illuminates yellow. For Energy Recycle mode application, please contact Delta customer service. Delta UPS DPM Gen2 1200/ 1500 kVA...
Turn-off Procedures 6.3.1 On-Line Mode Turn-off Procedures WARNING: 6.1 Pre Start-up & Pre Turn-off Before turning off the UPS, please read Warnings thoroughly and ensure that the precautions and instructions have been followed. Step 1 Tap the ON/ OFF Button ( ) to shut down the UPS’s inverter.
Wait for the UPS to complete the DC BUS discharging and switch OFF each external battery cabinet's breaker (Q5). Now, the LCD and tri-color LED indicator will be off. Step 3 Switch OFF the external maintenance bypass cabinet’s Output Breaker (Q4). Delta UPS DPM Gen2 1200/ 1500 kVA...
6.3.4 Manual Bypass Mode Turn-off Procedures WARNING: 1. Ensure that the LCD, all LED indicators and fans are OFF. 2. Check that all the switches, breakers and power are OFF. In Manual Bypass mode, the LCD and tri-color LED indicator are both OFF. To completely shut down the UPS, switch OFF the external maintenance bypass cabinet’s Manual Bypass Breaker (Q3).
) to shut down the UPS’s inverter. After that, the UPS will let the bypass AC source supply power. At the moment, if the bypass is abnormal, three is a risk of output interruption. Delta UPS DPM Gen2 1200/ 1500 kVA...
Step 2 Switch OFF the external maintenance bypass cabinet’s Input Breaker (Q1) and Bypass Breaker (Q2). After that, the UPS will transfer to Standby mode. Step 3 Wait for the UPS to complete the DC BUS discharging and switch OFF each external battery cabinet's breaker (Q5).
Page 116
Ensure that the output voltage difference between each parallel UPS is below 3V. Only authorized Delta engineers or service personnel can check the output voltage difference, or it must be done under the supervision of authorized Delta engineers or service personnel.
Chapter 7 : LCD Display & Settings LCD Display Hierarchy Figure 7-1 Please refer to for an overview of all the LCD items. For some of the items marked with an asterisk, they will show up only under certain conditions. Please refer to the note below for details.
Page 118
Subnet Mask High Temperature Alarm Gateway IP Installation Date/ Next Replacement Date DNS 1 IP Aging Test Current (C) DNS 2 IP End of Testing Voltage (V) Search Domain Baseline Built for Aging Reference Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 119
(Level 1) (Level 2) Service SNTP SETUP Time Zone Primary Time Server (Level 2) Secondary Time Server Ethernet Period Time Daylight Saving IPV6 Daylight Saving Current Status Daylight Saving From Daylight Saving To DHCPv6 SNMP DNS 1 IP SNMP/ SNMP Server Port DNS 2 IP Context Name Search Domain...
To display the item, go to BMS Setting and select ‘Main’ from the Module list. This function is optional. If you need to activate it, please contact Delta customer service. 3. The LCD screen diagrams in the user manual are for reference only. The actual display depends on the operation situation.
Administrator Login ON/ OFF Button Introduction of Touch Panel and Function Keys Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 123
Text/ Button Symbol Digital Function Display Icon/ Text Display Description (Yes or (Yes or (Yes or Tap the button to go back to the Main Screen. The figure ( ) below the UPS-1.1 icon ( ) indicates the parallel group ID no.
Page 124
Tap the button to check the power flow diagram and the operation status ✓ of the UPS. Tap the button to check the Input, Output, and Battery summary status of ✓ the UPS. Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 125
Text/ Button Symbol Digital Function Display Icon/ Text Display Description (Yes or (Yes or (Yes or Tap the button to check the system status, including auxiliary power card ✓ status, system control card status and parallel communication card status. Tap the button to check the EMS status.
Page 126
2. White with arrows: energized with power flow direction. Only when the UPS is overloaded and going to shut down will this ✓ countdown timer show up. It informs users how much time is left before shutdown. Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 127
Text/ Button Symbol Digital Function Display Icon/ Text Display Description (Yes or (Yes or (Yes or Only when the UPSs are connected in parallel will these two buttons appear. Tap the buttons to switch pages ✓ between the corresponding UPS and paralleled UPSs’...
→ Language. 7.3.1 Parallel System The two buttons will appear only when the UPSs are connected in parallel. Tap the button to see the corresponding UPS’s power flow as shown in the figure below. Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 129
Tap the button to see the paralleled UPSs’ status as shown in the figure below. Meaning Bypass breaker ❶ Input breaker ❷ Manual bypass breaker ❸ Output breaker and single UPS’s load capacity ❹ Total load capacity of the parallel system ❺...
→ Admin Password (4 digits). Check Kilowatt-Hour Path: → UPS Output → kWh icon ( Tap the kWh icon ( ), and you can check the kWh statistics of the UPS output in the following window. Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 131
kWh Icon Item Description Sheet Tabs Tap the sheet tabs to view the kWh statistics and (Day/ Week/ Month/ column charts of different time scales. Year/ Since Reset) 1. Shows the UPS’s output kWh statistics, with time on X-axis and kWh on Y-axis. Column Chart 2.
Bypass Voltage (Max.) Set up the bypass output’s maximum voltage. Bypass Voltage (Min.) Set up the bypass output’s minimum voltage. Set up the bypass output’s voltage range in ECO ECO Voltage Range mode. Delta UPS DPM Gen2 1200/ 1500 kVA...
7.6.2 Mode Setting Path: → Mode Setting Item Description Set up the UPS in On-Line mode. In On-Line mode, it is On-Line Mode the inverter to supply power to the connected loads. Set up the UPS in Green mode. In Green mode, it is the inverter to supply power to the connected loads and the Green Mode power modules take turn to rest according to the...
Page 134
Set up the output voltage. When the UPS is distant from the loads and Output Voltage there is a voltage drop in the output, you can Compensation adjust the INV output voltage amplitude for voltage compensation. Delta UPS DPM Gen2 1200/ 1500 kVA...
If you use the Delta lithium-ion batteries, please set up the battery type as 'LiB (Integration)'. The item 'LiB (Integration)' will appear on the LCD only if you use the Delta lithium-ion batteries with the optional multifunctional communication card (MFC) being installed in the SMART slot.
Page 136
Set up the maximum charge current. Auto Equalized Charge Enable or disable the auto-equalized charge. Auto Equalized Charge Set up the auto equalized charge interval. Interval Equalized Charge Time Set up the equalized charge time. Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 137
Item Description Set up the charging current limit. The charging current will be limited on this value when the generator is turned Reduce Charging NOTE: While on DG This setup item will only appear after you select → Dry Contact Setting → Event → Input → Generator Status.
Page 138
Battery status doesn't meet the testing conditions. c. Load status doesn't meet the testing conditions. d. Utility status doesn't meet the testing conditions. e. Please check if every UPS has any alarm. Baseline Built For Aging Reference Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 139
Item Description 2. After the Aging Test Current and End of Testing Voltage are set, press the start button under Baseline Built for Aging Reference. Baseline Built For Aging Reference (continued) (1) After you tap yes to build the Baseline for Aging Reference, the following screen will pop up and ask you if you want to abort baseline establishment.
Page 140
Baseline Built For Aging Reference (continued) When the test is failed, the following screen will pop up. Click 'YES' to go back to the original screen and contact service personnel for failure reasons. Delta UPS DPM Gen2 1200/ 1500 kVA...
7.6.5 Parallel Setting Path: → Parallel Setting Item Description The UPSs in parallel connection must be assigned the same parallel group ID no. in order to let the outputs of the parallel UPSs be put in parallel connection and let the Parallel Group ID loads be evenly distributed among the parallel units.
Page 142
Output Dry Contact 5 contact. 10. Output Overload Output Dry Contact 6 11. EPO Activated 12. Load On Manual Bypass 13. Battery Over Temperature 14. Output Voltage Abnormal 15. Battery Need Replacement Delta UPS DPM Gen2 1200/ 1500 kVA...
Output Dry Event Selection Type Contact No. 16. Bypass Over Temperature 17. Bypass Static Switch Fault Output Dry Contact 1 18. UPS Over Temperature Set up NO Output Dry Contact 2 19. Battery Breaker Shunt Trip Via (normally open) Output Dry Contact 3 or NC (normally Output Dry Contact 4 20.
Page 144
NOTE: The screen ( ) shown in the following figure will only appear on the LCD if you use the Delta lithium-ion batteries with the optional multifunctional Figure communication (MFC) card being installed in the smart slot shown in 4-21 .
Item Sub Item Description Set up the MODBUS ID for the optional MODBUS ID multifunctional communication card (MFC). Set up the MODBUS baud rate for the MODBUS Baud optional multifunctional communication card Rate (MFC). 7.6.8 Ethernet Path: → Ethernet Item Sub Item Description Set up the host name.
Page 146
DNS 2 IP IPV6 which can be updated by DHCP. Status Search Current IPv6 domain address. Length: Domain 32 characters max. IP Address Current IPv6 address. Route Entries Current route’s destination and gateway. Delta UPS DPM Gen2 1200/ 1500 kVA...
Item Sub Item Description Enable or disable DHCP client to obtain DHCP Client the IPv6 address. IP Address Set up the static IPv6 address. Set up the static IPv6 prefix length. Prefix Length: 1 ~ 128 bits. IPV6 Setting (continued) Gateway IP Set up the IPv6 gateway IP address.
Primary Time Set up the primary NTP server. Server SNTP Secondary Set up the secondary NTP server. Time Server Set up how long the system will automatically Period Time synchronize the time with servers. Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 149
Item Sub Item Description Daylight Saving Enable or disable the daylight saving function. Daylight Saving DAYLIGHT Set up the daylight saving beginning time. From SAVING Daylight Saving Set up the daylight saving ending time. SNMP Enable or disable the SNMP function. SNMP Server Set up the SNMP server port No.
Set up the SMTP server’s port No. Port MAIL Sender Set up the sender’s email address. SERVER Account Set up the sender’s email login account. Password Set up the sender’s email login password. Enable or disable the TLS function. Delta UPS DPM Gen2 1200/ 1500 kVA...
Item Sub Item Description Receiver Set up the receivers’ email address. Select the event level. Event Level MAIL LIST If the event’s level is higher than this setting, this event log will be sent. Test if the sample event log will be sent or not. Email Test System Maintenance 7.7.1...
You can perform the manual battery test and battery aging test via the LCD screen. 7.7.5 Battery Discharge Curve Path: → Battery Discharge Curve For relevant information, please refer to Baseline Built for Aging Reference stated in 7.6.4 Battery & Charging Setting Delta UPS DPM Gen2 1200/ 1500 kVA...
Path: → Advanced Diagnosis This is an optional function. Please contact Delta customer service for more information. If you are able to access to the Advanced Diagnosis screen, you can obtain the system and the specific power module’s relevant readings of the following items.
PM #_ MCU/ MCU2/ firmware version of a specific power module’s FPGA PFC. Check and update the MCU, MCU2 or FPGA PM #_ MCU/ MCU2/ firmware version of a specific power module’s FPGA Delta UPS DPM Gen2 1200/ 1500 kVA...
For details, please refer to Management Screen 7.6.4 Battery & Charging Setting System (BMS) NOTE: The quantity of BMS to be installed depends on how many external battery cabinets (lead-acid batteries) are connected to the UPS. For BMS installation, please contact Delta customer service.
Item Function If you use the Delta lithium-ion batteries, you must purchase and install the multifunctional communication Figure 4-2 card (MFC) in the SMART slot shown in monitor the battery status via the UPS’s LCD. For 8.3 MFC Function relevant information, please refer to...
Page 157
Color Item Descriptions (Status) 1. ID # represents each EMS 1000 Green (EnviroProbe) device which is connected (Normal) and set as 'Enable'. Yellow 2. Shows the integrated status of each EMS (Warning) 1000 (EnviroProbe) device. The integrated Red (Alarm) status is determined by the most severe status among Temperature (°C), Humidity Gray (Off) (%) and DI1 ~ DI4.
Page 158
4. To enable the EMS function, you have to set up relevant items on the LCD after connecting the optional EMS 1000 (EnviroProbe) to the UPS. Path: → EMS Setting (Administrator login required) • Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 159
NOTE: The default values are shown in the figures above. Item Sub Item Description Set the ID # (ID 0/ ID 1/ …/ ID 15) according to the ID DIP switch setting of the EMS 1000 (EnviroProbe) device. NOTE: If the ID # setting is wrong, the warning message 'The EMS 1000 ID # Communication Fail' will appear.
Cell Voltage* , String Voltage* and Ambient Temperature* You can also set up the following items. These settings must be carried out by qualified service personnel. Please contact Delta customer service for assistance. Delta UPS DPM Gen2 1200/ 1500 kVA...
MFC Function on the LCD Screen The PAGE 3 & MFC screens (see the figures below) will appear on the LCD only if you use the Delta lithium-ion batteries with the optional multifunctional communication Figure 4-2 (MFC) card being installed in the SMART slot (see ).
Page 162
Sub Item Description Set up the MODBUS ID for the optional MODBUS ID multifunctional communication card (MFC). Set up the MODBUS baud rate for the MODBUS optional multifunctional communication card Baud Rate (MFC). Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 163
Path: → Version & S/N • Item Sub Item Description Check and update the MCU firmware version of the optional multifunctional communication card (MFC).
Higher temperature will shorten fan life. When the UPS is running, please check if all fans work normally and make sure if air can move freely around and through the UPS. If not, please replace abnormal fans. Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 165
Color Touch Panel LCD • " The LCD replacement procedures are as follows. Step 1 Open the UPS system cabinet’s middle front door, press the power button once to let it in the OFF status and disconnect the LCD cable connected the LCD and the display port.
Page 166
LCD and the display port and press the power button once to let it in the ON status. Unscrew the Six Screws to Remove the LCD & Install a New One (UPS System Cabinet) (Figure 9-2: Unscrew the Six Screws to Remove the LCD & Install a New One) Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 167
Dust Filters • To replace the UPS system cabinet’s dust filters, open its middle front door, remove the four dust filters located at the rear of the door and install new ones. (UPS System Cabinet) Remove the Four Dust Filters & Install New Ones (Figure 9-3: Remove the Four Dust Filters &...
Page 168
(Power Module) Remove the Two Dust Filters & Install New Ones (Figure 9-4: Remove the Two Dust Filters & Install New Ones) Delta UPS DPM Gen2 1200/ 1500 kVA...
Appendix 1 : Technical Specifications Model DPM-1200K DPM-1500K UPS Capacity 1200kVA/ 1200kW 1500kVA/ 1500kW Nominal 480 Vac (3P3W + PE) Voltage 408 ~ 552 Vac (100% load) ; Input Voltage Range 360 ~ 408 Vac (70% ~ 100% load) Frequency 45 ~ 65 Hz Nominal 480 Vac (3P3W + PE)
Page 170
Degree (PD) Over Voltage Category OVC III Compliance (OVC) Type of System TN-S, TN-C, TN-C-S, IT Earthing Operating 3280 ft (1000 m) (without derating) Altitude Environment Operating 32 ~ 104°F (0 ~ 40°C) Temperature Delta UPS DPM Gen2 1200/ 1500 kVA...
The User Manual must be carefully followed. Seller makes no representation or warranty as to the suitability or fitness of this product for any specific application. No. : 501330360102 Version : V 1.2 Release Date : 2024_02_27 Delta UPS DPM Gen2 1200/ 1500 kVA...
Page 173
T +81-3-5733-1111 T +82-2-515-5303 E jpstps@deltaww.com E ups.south.korea@deltaww.com Singapore Thailand Delta Electronics Int’l (Singapore) Pte Ltd. Delta Electronics (Thailand) Public Co.,Ltd. 17 Kallang Junction, #01-01, TRION, 909 Soi 9, Moo 4, E.P.Z., Bangpoo Industrial Estate, Tambon Phraksa, Singapore 339274 Amphur Muang-samutprakarn, Samutprakarn Province 10280,...