Run Command

This section explains input methods for the run command.

Selecting the Run Command Source

Set parameter b1-02 to select the source for the run command.
Related Parameters
Parameter
Number
b1-02
Operation method selection
Performing Operations Using a Digital Operator
When b1-02 is set to 0, the Inverter can be operated using the Digital Operator keys (RUN, STOP, and FWD/
REV). For details on the Digital Operator, refer to
Performing Operations Using Control Circuit Terminals
When b1-02 is set to 1, Inverter operation can be performed using the control circuit terminals.
Performing Operations Using a 2-wire Control
The factory setting is set to a 2-wire control. When control circuit terminal S1 is set to ON, forward operation
will be performed, and when S1 is turned OFF, the Inverter will stop. In the same way, when control circuit
terminal S2 is set to ON, reverse operation will be performed, and when S2 is turned OFF, the Inverter will
stop.
Name
Forward/Stop
Reverse/Stop
SN
Fig 6.11 2-Wire Control Wiring Example with Positive Logic