Stopping Methods
This section explains methods of stopping the Inverter.
Selecting the Stopping Method when a Stop Command is Input
There are four methods of stopping the Inverter when a stop command is input:
Deceleration to stop
•
•
Coast to stop
DC braking stop
•
Coast to stop with timer
•
Set parameter b1-03 to select the Inverter stopping method.
Related Parameters
Parameter
Number
b1-03
Stopping method selection
Zero speed level (DC injection braking starting fre-
b2-01
quency)
b2-02
DC injection braking current
b2-04
DC injection braking time at stop
Name
Stopping Methods
Change
Setting
Factory
during
Range
Setting
Operation
0 to 3
0
No
0.0 to
0.5 Hz
No
10.0
0 to
50%
No
100
0.00
to
0.50 sec.
No
10.00
Access
Level
Q
A
A
A
6-11