Speed Limit; (Frequency Reference Limit Function); Limiting Maximum Output Frequency; Limiting Minimum Frequency - Omron VARISPEED E7 User Manual

Variable torque frequency inverter
Hide thumbs Also See for VARISPEED E7:
Table of Contents

Advertisement

Speed Limit

(Frequency Reference Limit Function)

This section explains how to limit the motor speed.

Limiting Maximum Output Frequency

If the motor should not rotate above a given frequency, use parameter d2-01.
Set the upper limit value of the frequency reference as a percentage, taking E1-04 (Maximum Output Fre-
quency) to be 100%.
Related Parameters
Parameter
Number
d2-01

Limiting Minimum Frequency

If the motor should not rotate below a given frequency, use parameters d2-02 or d2-03.
There are two methods of limiting the minimum frequency, as follows:
Adjust the minimum level for all frequencies.
Adjust the minimum level for the master speed frequency (i.e., the lower levels of the jog frequency, multi-
step speed frequency, and auxiliary frequency will not be adjusted).
Related Parameters
Parameter
Number
d2-02
d2-03
6-24
Name
Frequency reference upper limit
Name
Frequency reference lower limit
Master speed reference lower limit
Change
Setting
Factory
during
Range
Setting
Operation
0.0 to
100.0%
No
110.0
Change
Setting
Factory
during
Range
Setting
Operation
0.0 to
0.0%
No
110.0
0.0 to
0.0%
No
110.0
Access
Level
A
Access
Level
A
A

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading