Omron VARISPEED E7 User Manual page 287

Variable torque frequency inverter
Hide thumbs Also See for VARISPEED E7:
Table of Contents

Advertisement

Display
OPE09
PI Selection
OPE10
V/f Ptrn Setting
OPE11
CarrFrq/On-Delay
ERR
EEPROM R/W Err
7-12
Table 7.3 Operator Programming Errors
Meaning
PI Control Setup Error
V/f Parameter Setting Error
Carrier Frequency Parameter Set-
ting Error
EEPROM write error
The NV-RAM data do not match
the EEPROM data
Probable Causes
The following settings have been
made at the same time.
• b5-01 (PI Control Mode Selection)
has been set to a value different
from 0.
• b5-15 (PI Sleep Function Opera-
tion Level) has been set to a value
different from 0.
• b1-03 (Stopping Method Selection)
has been set to 2 or 3.
Parameters E1-04, E1-06, E1-07, E1-
09 and E1-11 do not satisfy the fol-
lowing conditions:
• E1-04 (FMAX) ≥ E1-11 (FMID2)
> E1-06 (FA) > E1-07 (FB) ≥ E1-
09 (FMIN)
One of the following parameter set-
ting errors exists:
• Carrier frequency Gain C6-05 > 6
and C6-03 (Carrier Frequency
Upper Limit) < C6-04 (Carrier Fre-
quency Lower Limit)
• Upper/lower limit error in C6-03
and C6-04.
A verification error occurred when
writing EEPROM.
Corrective Action
Check the settings of
parameters b5-01, b5-15
and b1-03
• Check the parameter
settings of E1-
• A frequency/voltage
value might be set
higher than the maxi-
mum frequency/volt-
age.
Check the parameter set-
tings of C6-02 to C6-05.
• Cycle the Inverter
power supply.
• Try to initialize the
Inverter.

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents