Temperature Input Units; Grt1-Ts2@ Temperature Input Units - Omron GRT1 - 11-2007 Operation Manual

Slice i/o units
Table of Contents

Advertisement

Temperature Input Units

Error History Tab
Page
6-4
Temperature Input Units
6-4-1

GRT1-TS2@ Temperature Input Units

General Specifications
Performance Specifications
GRT1-TS2P/TS2PK
(2) When either of the comparison inputs is disconnected (off-wire detected),
the result value will be set to 0.00 and a yellow alarm icon will be dis-
played to the left of the comparison number.
For details on the Error History Tab Page, refer to 4-5-1 Checking Mainte-
nance Information.
Item
Model
Unit power supply voltage
I/O power supply voltage
Noise immunity
Vibration resistance
Shock resistance
Dielectric strength
Ambient temperature
Ambient humidity
Operating environment
Storage temperature
Mounting
Item
Model
Input
Number of I/O points
Input type
Indication accuracy
Specifications
GRT1-TS2P/-TS2PK/-TS2T
24 VDC (24 VDC –15% to +10%)
I/O power supply not required.
Conforms to IEC 61000-4-4. 2.0 kV (power lines)
10 to 60 Hz, 0.7-mm double amplitude, 60 to 150 Hz,
2
50 m/s
2
150 m/s
500 VAC for 1 min. with 1-mA sensing current
(between isolated circuits)
–10 to 55°C (with no icing or condensation)
25% to 85%
No corrosive gases
–25 to 65°C (with no icing or condensation)
35-mm DIN Track mounting
Specifications
GRT1-TS2P
Platinum resistance thermometer
2 inputs (Two input words are allocated in the Master
when normal display mode is selected or 4 input
words are allocated when 1/100 display mode is
selected.)
°
PT100 (
200 to 850
C) or
°
PT100 (
200 to 200
C);
switching possible.
Using Setting Tool: Can
be set separately for each
input.
Using DIP switch: Both
inputs are set together.
°
200 to 850
C input range:
(±0.3% of indication value or ±0.8
larger) ±1 digit max.
°
200 to 200
C input range:
(±0.3% of indication value or ±0.5
larger) ±1 digit max.
Section 6-4
GRT1-TS2PK
°
PT1000 (
200 to 850
C)
or PT1000 (
200 to
°
200
C); switching possi-
ble.
Using Setting Tool: Can
be set separately for each
input.
Using DIP switch: Both
inputs are set together.
°
C, whichever is
°
C, whichever is
167