Omron GRT1 - 11-2007 Operation Manual page 129

Slice i/o units
Table of Contents

Advertisement

Analog Input Units
Selecting the Analog Data (Example: DeviceNet Configurator)
1,2,3...
108
4. Click the General Tab and select the desired I/O data from the pull-down
menu on the Default Connection Path (In) Field. In the following example
Analog Data is selected.
5. Return to the General Tab Page, click the Download Button, and then click
the Reset Button to reset the Unit.
6. Click the OK Button to exit.
■ Selecting the Analog Data Type
The analog data type can be selected from up to six types of data (analog
input value, peak value, bottom value, top value, valley value, and rate of
change) obtained from math operations. The selected data can be allocated
for the Master either individually or in combination with Status Flags.
Use the following method to select the analog data type.
1. In the Network Configuration Window for the Slice I/O Terminal, double-
click the icon of the Slice I/O Terminal that is to be set. Alternatively, right-
click the icon and select Parameters - Edit. The Edit Device Parameters
Window will be displayed.
2. Click the Edit Button on the I/O Module Tab Page. The Edit Unit Parame-
ters Window will be displayed.
Section 5-4