Analog Output Units
GRT1-DA2C
Wiring
Output Range and
Conversion Data
Output Range: 0 to 5 V
Base block
Internal
circuits
The terminal wiring varies according to whether voltage or current output is
used.
Voltage Input (GRT1-DA2V)
RSV RSV
RSV RSV
RSV RSV
V0+ V1+
V0− V1−
RSV RSV
Note
An internal signal is connected to the RSV terminal to dissipate heat. Do not
wire the RSV terminal.
The digital values that are output are converted to analog data according to
the output range used, as shown below. When the value exceeds the output
range, the DA conversion data is fixed at the High Limit or Low Limit set value.
The values 0000 to 1770 hex (0 to 6,000) correspond to the voltage range 0 to
5 V. The output range is
Voltage
5.25 V
5 V
0 V
8000
FED4 (−300)
−0.25 V
0000 (0)
Main block
Photo-
coupler
Internal
Isolated
circuits
power
supply
circuit
Current Input (GRT1-DA2C)
RSV RSV
RSV RSV
RSV RSV
I0+
I1+
+
I0−
I1−
RSV RSV
0.25 to 5.25 V.
1770
189C
(6000)
(6300)
Section 5-5
Terminal block
RSV × 6
I0+
I0−
AG
I1+
I1−
AG
RSV × 2
+
Conversion data
Hexadecimal (decimal)