Omron EJ1G Datasheet
Omron EJ1G Datasheet

Omron EJ1G Datasheet

Ej1g series modular temperature controller for gradient temperature control
Hide thumbs Also See for EJ1G:

Advertisement

Modular Temperature Controller for Gradient Temperature Control
EJ1G
Gradient Temperature Control to Achieve
Consistent Layer Temperature
• Perform gradient temperature control ranging from 2 to 32
channels.
• Perform 2-channel gradient temperature control for up to 16
groups, or 32-channel gradient temperature control for up to 2
groups.
• Set gradient temperature control or 2-PID control for each
group.
• Reduce design work for ladder programming with programless
connections to Programmable Controllers. (The same feature
as Standard-control EJ1 Models.)
• Connect directly to the G3ZA Multi-channel Power Controller
using optimum cycle control for high-accuracy control with
minimal noise.
Refer to the "Safety Precautions" on page 18.

Ordering Information

■ Temperature Controllers
Gradient Temperature Control
Name
Power
No. of
supply
con-
voltage
trol
points
Basic Unit
24 VDC
2
Voltage
(gradient
supplied
output:
tempera-
from the
2 points (for
ture
End Unit
SSR drive)
control)
(See note
4
(See note
2.)
1.)
HFU
None
None
(gradient
tempera-
ture con-
trol)
(See note
1.)
End Unit
24 VDC
(See note
1.)
Note: 1. An End Unit is required to connect an HFU to a Basic Unit. A Gradient Temperature Control HFU and a Gradient Temperature Control
Basic Unit must be used together to achieve gradient temperature control. The Gradient Temperature Control HFU and Gradient
Temperature Control Basic Unit are used exclusively for gradient temperature control, but the End Unit is the same as that used for the
Standard-control EJ1 Models.
The Basic Unit cannot communicate externally by itself.
2. Heating/cooling control is not supported for gradient temperature control.
3. When using the heater burnout alarm, use a Current Transformer (E54-CT1 or E54-CT3) (sold separately).
Refer to the following manual for precautionary information and other information necessary to use the EJ1G:
EJ1G Modular Temperature Controller Operation Manual (Cat. No. H143)
Control
Control
Auxiliary
outputs
outputs
output
1 and 2
3 and 4
Transistor
None
output: 2
points
(sourcing)
Voltage out-
put: 2 points
(for SSR
drive) (See
note 2.)
None
Transistor
output:
4 points
(sourcing)
Transistor
output:
2 points
(sourcing)
Modular Temperature Controller for Gradient Temperature Control
Functions
Communications
functions
Heater
Event
burnout
inputs
alarm
2
None
G3ZA connection
(See
port: RS-485
note 3.)
From End Unit:
Port A: RS-485
None
4
From End Unit:
Port A: RS-485
Port C: RS-485 or
RS-232C
selectable.
From End Unit:
Port A: RS-485
Port C: RS-422
None
Port A: RS-485
Connector: Port A
Input type
Terminal
Thermocou-
M3 terminal EJ1G-TC2A-QNH
ple, platinum
Screw-less
EJ1G-TC2B-QNH
resistance
clamp
thermometer,
analog voltage,
M3 terminal EJ1G-TC4A-QQ
and analog
current select-
Screw-less
EJ1G-TC4B-QQ
able for each
clamp
channel.
No input
M3 terminal EJ1G-HFUA-NFLK
Screw-less
EJ1G-HFUB-NFLK
clamp
M3 terminal EJ1G-HFUA-NFL2
Screw-less
EJ1G-HFUB-NFL2
clamp
M3 terminal EJ1C-EDUA-NFLK
EJ1G
Model
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EJ1G and is the answer not in the manual?

Questions and answers

Summary of Contents for Omron EJ1G

  • Page 1: Ordering Information

    (sourcing) Note: 1. An End Unit is required to connect an HFU to a Basic Unit. A Gradient Temperature Control HFU and a Gradient Temperature Control Basic Unit must be used together to achieve gradient temperature control. The Gradient Temperature Control HFU and Gradient Temperature Control Basic Unit are used exclusively for gradient temperature control, but the End Unit is the same as that used for the Standard-control EJ1 Models.
  • Page 2: Specifications

    Setting method Via communications Operating: − 10 ° C to 55 ° C, Stored: − 25 ° C to 65 ° C (with no icing or condensation) Ambient temperature range Ambient humidity range Operating: 25% to 85% (with no condensation) Note: Inputs are fully multi-input.
  • Page 3 The indication of R and S thermocouples at a temperature of 200 ° C or less is ± 3 ° C ± 1 digit max. W = ( ± 0.5% of indication value (PV) or ± 3 ° C, whichever is greater) ± 1 digit max. PLII = ( ± 0.5% of indication value (PV) or ± 2 ° C, whichever is greater) ±...
  • Page 4: Communications Specifications

    3. For the number of Units that can be connected, refer to “Connection Precautions” on page 9. 4. When performing gradient temperature control, the number of control channels is limited by the group setting. For details, refer to “Gradient Group Settings” on page 11.
  • Page 5 ■ Input Ranges Sensor inputs are fully multi-input. Therefore, platinum resistance thermometer, thermocouple, infrared thermosensor, and analog input can be selected. Inputs can be set for each channel using multi-inputs. Input type Platinum resistance thermometer Name Pt100 JPt100 Tem- 2300...
  • Page 6 ON: 1 k Ω max., OFF: 100 k Ω min. Inputs with contacts Inputs without contacts ON: Residual voltage of 1.5 V max., OFF: Leakage current of 0.1 mA max. Short-circuit current: Approx. 4 mA (per contact) Programless Programless downloading...
  • Page 7 2. For the number of Units that can be connected, refer to “Connection Precautions” on page 9. 3. When performing gradient temperature control, the number of control channels is limited by the group setting. For details, refer to “Gradient Group Settings”...
  • Page 8 E58-CIFQ1 (sold separately). Port B Use port B for configurations with distributed placement. Port C ■ Basic Configuration for Connection to G3ZA Multi-channel Power Controllers Up to 8 G3ZA Controllers can be connected to each Basic Unit. EJ1G-TC4 EJ1G-HFU EJ1G-TC2 EJ1C-EDU COM1...
  • Page 9: Connection Precautions

    • One EJ1G-HFU can manage up to 16 Basic Units (EJ1G-TC4/ TC2). 24 VDC • Up to 16 Units can be connected side by side including the EJ1G- HFU. The End Unit is not included in the 16 Units. Note: When performing gradient temperature control, the number of control channels is limited by the group setting.
  • Page 10: Programless Communications

    Functional insulation is applied between the power supply, input, output, and communications terminal sections. If reinforced double insulation is required, use power supplies that comply with IEC60664 for reinforced double insulation for the EJ1G's external power supply and for power supplies connected to the EJ1G.
  • Page 11 The HFU handles all of the operations for gradient temperature control and 2-PID control. The maximum number of enabled channels that can be controlled is selected at the HFU from 4, 8, 16, or 32 channels, and that number of channels is allocated for the CH2 CH2 CH2 CH2 CH2 CH2 number of groups used.
  • Page 12 Not usable The HFU can control up to 64 channels, but when the maximum number of enabled channels is a number other than 4, 8, 16, or 32 channels, non-usable channels result as shown in this example. This limits the number of controllable channels and connectable Units.
  • Page 13 • Use a SELV power supply. An SELV circuit is one separated from the power supply with double insulation or reinforced insulation, that does exceed an output voltage of 30 V r.m.s. and 42.4 V peak or 60 VDC max. The OMROM S8VS Series is recommended for the power supply.
  • Page 14 End Unit. COM 2 (orange) Flashes when the EJ1G system is in operation. COM 3 (orange) Flashes during communications via port C. Note: Some time is required for the indicators to light after the power is turned ON. EJ1G Modular Temperature Controller for Gradient Temperature Control...
  • Page 15 Meaning switches midway between settings. 2 to 6 Not used (OFF) • SW1 is set to 1 and SW2 pins are all set to OFF in the default ON: G3ZA in operation settings. Use when Units are distributed. (Refer to the operation manual for details.)
  • Page 16 End Plate PFP-M M4 × 8 panhead screw 35.5 35.3 11.5 Note: Two screws are included with the EJ1C-EDU for the End Plate. Always attach End Plates to both sides. M4 spring washer EJ1G Modular Temperature Controller for Gradient Temperature Control...
  • Page 17 G3NA The number of SSRs that can be 240 VAC, 5 A, 10 A, 20 A, 40 A, 75 A, or 90 A connected for each channel is listed 480 VAC, 10 A, 20 A, 40 A, 75 A, or 90 A on the right.
  • Page 18: Safety Precautions

    21.Do not use port B on the end product when using port C on HFUs. ■ Precautions for Safe Use 22.Install the product only after reading the manual provided with the End Unit.
  • Page 19: Precautions For Operation

    1. Align the connectors and connect the Units to each other. 1. Use the product within the following temperature and humidity Connect an End Unit to the Unit on the right end. (Up to 16 Units ranges: can be connected side by side.) Temperature: −...
  • Page 20 Applicable DIN Rail (sold separately): PFP-100N (100 cm), Refer to the “G3ZA Instruction Manual” for wiring methods. PFP-50N (50 cm) Refer to the following manual for precautionary information and other information necessary to use the EJ1G: EJ1G Modular Temperature Controller Operation Manual (Cat. No. H143) EJ1G...
  • Page 21 EJ1G Modular Temperature Controller for Gradient Temperature Control...
  • Page 22 EJ1G Modular Temperature Controller for Gradient Temperature Control...
  • Page 23 EJ1G Modular Temperature Controller for Gradient Temperature Control...
  • Page 24 CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE...

Table of Contents