Omron EJ1 User Manual page 102

Modular temperature controllers
Hide thumbs Also See for EJ1:
Table of Contents

Advertisement

Setting Control Specifications
■ MV at Stop
This parameter sets the MV when control is stopped.
For heating/cooling control, the MV at Stop parameter applies to the cooling
side if the MV is negative and to the heating side if the MV is positive.
The default is 0.0, so an MV will not be output for either standard or heating/
cooling control with the default setting.
Variable type
Parameter name
D5/95
MV at Stop (Channel)
Conditions for use
The order of priority is as follows: Manual MV > MV at Stop > MV at PV
Error.
■ MV at PV Error
This parameter sets the MV when an input error or remote SP input error
occurs.
Variable type Parameter name
D5/95
MV at PV Error
(Channel)
Conditions for use
The order of priority is as follows: Manual MV > MV at Stop > MV at PV
Error.
■ MV Limiter
This function limits the MV output by applying upper and lower limits to the
calculated MV.
• The following MVs take priority over the MV limits.
• Manual MV
• MV at Stop
• MV at PV Error
Output
MV Upper Limit
MV Lower Limit
0%
Output Mode Selection = Standard control
• For heating/cooling control, upper and lower limits are set on overall heat-
ing/cooling control.
(They cannot be set separately for heating and cooling.)
Setting range
5.0 to 105.0 (for standard control) %
105.0 to 105.0 (for heating/cooling control) %
The control method must be set to 2-PID control.
Setting range
5.0 to 105.0 (for standard control) %
105.0 to 105.0 (for heating/cooling control) %
The control method must be set to 2-PID control.
100%
Section 4-3
Default
0
Default
0
77