■ Controller Performance Specifications

Indication accuracy
Temperature variation
influence (See note 3.)
Voltage variation
influence (See note 3.)
Control mode
Control period
Proportional band (P)
Integral time (I)
Derivative time (D)
Hysteresis
Manual reset value
Alarm setting range
Input sampling period
Insulation resistance
Voltage resistance
Vibration resistance
Shock resistance
Inrush current
Weight
Degree of protection
Memory protection
Note 1. K, T, N at 100 C max.: 2 C 1 digit max.
U and L: 2 C 1 digit max.
B at 400 C max. is not specified.
R and S at 200 C max.: 3 C 1 max.
W: (Larger of 0.3%PV and 3 C) 1 digit max.
2. U and L: 1 C 1 digit
R and S at 200 C max.: 1.5 C 1 digit
3. Ambient temperature: 10 C to 23 C to 55 C
Voltage range: 15% to +10% of rated voltage
4. EU stands for Engineering Unit and is the unit after scaling. For a temperature sensor, it is C or F.
Thermocouple input:
( 0.1% of indicated value or 1 C, whichever is greater) 1 digit max. (See note 1.)
[Not using internal cold junction compensation]
( 0.1% of indicated value or 1 C, whichever is smaller) 1 digit max. (See note 2.)
Analog input: (0.1% FS) 1 digit max.
Platinum resistance temperature sensor input:
( 0.1% of indicated value or 0.5 C, whichever is greater) 1 digit max.
Position-proportional potentiometer input:
( 5% FS)
1 digit max.
R, S, B, or W thermocouple input:
( 1% of PV or 10 C, whichever is greater)
Other thermocouple input:
( 1% of PV or 4 C, whichever is greater)
*K thermocouple at 100 C max: 10 C max.
Platinum resistance thermometer:
( 1% of PV or 2 C, whichever is greater)
Analog input: ( 1% FS) 1 digit max.
Standard Control (Heating Control or Cooling Control), Heating/cooling Control
Standard Control with Remote SP (Models with 2 Input Channels only)
Heating/Cooling Control with Remote SP (Models with 2 Input Channels only)
Cascade Standard Control (Models with 2 Input Channels only)
Cascade Heating/Cooling Control (Models with 2 Input Channels only)
Proportional Control (Models with 2 Input Channels only)
Position-proportional Control (Position-proportional Control Model only)
0.2 to 99.0 s (increments of 0.1 seconds): During time-divided proportional control output
0.00% to 999.99% FS (increments of 0.01% FS)
0.0% to 3999.9 s (increments of 0.1 second)
0.0% to 3999.9 s (increments of 0.1 second)
0.01% to 99.99% FS (increments of 0.01% FS)
0.0% to 100.0% (increments of 0.1% FS)
*4
19999 to 99999
(Decimal point position depends on input type and decimal point position setting)
50 ms
20 M
or higher (at 500 VDC)
2,000 VAC 50/60 Hz 1 min (charged terminals of different polarity)
Vibration frequency: 10 to 55 Hz
2
Acceleration: 20 m/s
2
150 m/s
(relay contacts: 100 m/s
3 times each on 3 axes and in 6 directions
100 to 240 VAC Model: 50 A max.
24 VAC/VDC Model: 30 A max.
Approx. 450 g (Controller only), Fittings: Approx. 60 g,
E5AR-T
Terminal cover: Approx. 30 g
Approx. 330 g (Controller only), Fittings: Approx. 60 g,
E5ER-T
Terminal cover: Approx. 16 g
Front: NEMA4X indoor, rear case: IP20, terminal plate: IP00
EEPROM (Write count: 100,000 times)
1 digit max.
1 digit max.
1 digit max.
2
)