Omron E5AR - MANUAL 2 User Manual

Digital controller
Hide thumbs Also See for E5AR - MANUAL 2:
Table of Contents

Advertisement

Quick Links

Cat. No. Z182-E1-03
Note: Specifications subject to change without notice.
OMRON Corporation
Industrial Automation Company
Control Devices Division H.Q.
Analog Controller Division
Shiokoji Horikawa, Shimogyo-ku,
Kyoto, 600-8530 Japan
Tel: (81)75-344-7080/Fax: (81)75-344-7189
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69, NL-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
1 East Commerce Drive, Schaumburg, IL 60173
U.S.A.
Tel: (1)847-843-7900/Fax: (1)847-843-8568
OMRON ASIA PACIFIC PTE. LTD.
83 Clemenceau Avenue,
#11-01, UE Square,
239920 Singapore
Tel: (65)6835-3011/Fax: (65)6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Road (M),
Shanghai, 200120 China
Tel: (86)21-5037-2222/Fax: (86)21-5037-2200
Authorized Distributor:
Printed in Japan
0505-0.5M (0305) (B)
Digital Controller
User's Manual
Cat. No. Z182-E1-03

Advertisement

Table of Contents
loading

Summary of Contents for Omron E5AR - MANUAL 2

  • Page 1 Regional Headquarters OMRON EUROPE B.V. Wegalaan 67-69, NL-2132 JD Hoofddorp The Netherlands Tel: (31)2356-81-300/Fax: (31)2356-81-388 OMRON ELECTRONICS LLC 1 East Commerce Drive, Schaumburg, IL 60173 U.S.A. Tel: (1)847-843-7900/Fax: (1)847-843-8568 OMRON ASIA PACIFIC PTE. LTD. 83 Clemenceau Avenue, #11-01, UE Square,...
  • Page 2: Introduction

    • This product is designed for use by qualified personnel with a knowledge of electrical systems. • Read this manual carefully and make sure you understand it well to ensure that you are using the E5AR/ E5ER Digital Controllers correctly.
  • Page 3 The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products.
  • Page 4 PERFORMANCE DATA Performance data given in this manual is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application requirements.
  • Page 5: Precautions

    Precautions Definition of Safety Notices and Information The following notation is used in this manual to provide precautions required to ensure safe usage of the product. The safety precautions that are provided are extremely important to safety. Always read and heed the information provided in all safety precautions.
  • Page 6 ● Precautions CAUTION Do not touch any of the terminals or terminal blocks while power is being supplied. Doing so may occasionally result in minor injury due to electric shock. Do not touch the terminals, or electronic components or patterns on the PCB within 1 minute after turning OFF the power.
  • Page 7: Precautions For Safe Use

    Take this into consideration when setting up the control system. (12) Allow the product to warm up for at least 30 minutes after the power is turned (13) Install surge absorbers or noise filters in devices near the product that generate noise (in particular, devices with an inductance component, such as motors, transformers, solenoids, and magnetic coils).
  • Page 8: Precautions For Correct Use

    To prevent inductive noise, separate the wiring for the product's terminal block and connector from high-voltage, high-current power lines. Do not run the wiring parallel to or in the same cable as power lines. The influence of noise can also be reduced by using separate wiring ducts or shield lines.
  • Page 9: About This Manual

    Section 10 Troubleshooting encounter a problem. Product specifications. List of set- tings. Appendix Can be used to make a copy of your settings. For details on using DeviceNet communications functions, refer to the E5AR/E5ER Digital Controller DeviceNet Communications User’s Manual (H124). VIII...
  • Page 10 Unit of industrial quantity* Channel * Data after scaling is shown in industrial units such as °C, m, and g, and "EU" is used to indicate the minimum increment of such a quantity. For example, the minimum increment of 50.02 m is 0.01 m, and thus 1 EU would be equal to 0.01 m.
  • Page 11 Page 2-10: E5ER graphic on the right side deleted and “E5ER” on the left graphic changed to “E5ER-@4@@.” Page 2-11: “Event inputs 3 to 7” corrected to “event inputs 3 to 6” in two paragraphs under Event inputs (terminals). Page 3-11 (and throughout the manual): “Control initial setting level 2” corrected to “Control initial setting 2 level.”...
  • Page 12 Page 4-10: Information added on direct/reverse operation, alarms, input shift, SP ramp, and PID. Page 5-6: “0.0000” corrected to “0.000” and “210.0 C” corrected to “190.0 C” in text and graph. Pages 5-13 and 8-32: Setting range changed from “10% to 110% of setting range” to “ 19999 to 99999”...
  • Page 14: Table Of Contents

    Contents Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - I Precaution in using the product - - - - - - - - - - - - - I...
  • Page 15 Setting and changing the SP ............4-17 Performing ON/OFF control ..............4-18 ON/OFF Control ................4-18 Settings ..................... 4-19 4.10 Determining the PID constants (AT, manual settings) ......4-20 AT (Auto-tuning) ................4-20 Manual settings ................. 4-22 4.11 Using auxiliary output ................4-23 Auxiliary output assignment ..............
  • Page 16 Setting data compound write (Communication/CompoWay/F) ..6-18 Monitor value / setting data compound read store (write) ....6-19 Monitor value / setting data compound read store check (read) ..6-20 Monitor value / setting data compound store read ......6-20...
  • Page 17 Commands and responses (Communication/Modbus) ......7-17 Monitor value read (Communication/Modbus) ........7-17 Read setting data (Communication/Modbus) ........7-18 Write setting data to protect level ............7-19 Write setting data (Communication/Modbus) ........7-19 Write via communication ..............7-21 Control Run / Control Stop ..............7-21 Bank change ..................
  • Page 18 Section 10 Troubleshooting 10.1 Troubleshooting checklist ................. 10-2 10.2 Error messages ..................10-3 10.3 Inferring causes from conditions (abnormal measured values) ....10-4 10.4 Inferring causes from conditions (abnormal control) ........ 10-5 10.5 Inferring causes from conditions (abnormal output) ......... 10-7 10.6 Inferring causes from conditions...
  • Page 19 XVIII...
  • Page 20 Section 1 Overview Main Features of the E5AR/ER ......... 1-2 Part Names and Functions ..........1-4 Input/output Configuration and Main Functions ....1-7...
  • Page 21: Main Features Of The E5Ar/Er

    Voltage inputs: 1 to 5 V, 0 to 5V, 0 to 10V ● Multi-point inputs • A 2-input type and a 4-point input type are available for the E5AR. A 2-point input type is available for the E5ER. • All multi-point inputs also support multi-input, eliminating the need for an externally connected converter.
  • Page 22: Outputs

    Two-input types can use an external input for the set point. • SP ramp function This limits the amount of change of the set point based on the rate of change (SP ramp value). This function is useful for control applica- tions such as firing ceramics where sudden changes in temperature are not desirable.
  • Page 23: Part Names And Functions

    Channel indication 8.8.8.8.8 Indicator 1 Bar graph 8.8.8.8.8 Indicator 2 Operation indicator 8.8.8.8 Indicator 3 OUT1 OUT2 OUT3 OUT4 STOP RSP Function key 1 Auto/Manual key PF 1 PF 2 /CH Up key Down key Function key 2 Channel key...
  • Page 24: How To Read The Display

    (orange) Otherwise is off. ● : Indicates that the model has the function. Note that function may be disabled depending on the settings, and in this case the indicator is always off. – : Indicates that the model does not have the function.
  • Page 25: Explanation Of The Keys

    Section 1 Overview When the control output is current output, the indicator turns off when the MV is 0% or less, and turns on when the manipulated variable is greater than 0%. ■ Explanation of the keys Name Explanation Level key Press to change setting levels.
  • Page 26: Input/Output Configuration And Main Functions

    MNAT.1 Channel 1 manual/auto Multi-point input types have the same setting data for channels 2 to 4 depending on the number of input points. * Cascade standard control, Cascade heating/cooling control, position proportional control and ratio control are also available. See "Section 3, Typical Control Examples" (page 3-1).
  • Page 27: Main Functions

    If the input type SW is set to temperature input (resistance temper- ature input sensor or thermocouple), the temperature unit can be set. If the input type SW is set to analog input (current input or voltage input), scaling and the decimal point position can be set.
  • Page 28 (When the present value (PV) is lower than the set point (SP), the MV is increased in proportion (heating) to the difference between the PV and the SP.) • When pulse output is used, the control period must be set for each channel.
  • Page 29 Floating control allows position propor- tional control without a potentiometer. ● Control / Transfer Use this setting to assign what type of data is output from each output. output allocation For the multi-point input type, assignment data can be set for channels 2 and higher as needed for the number of channels.
  • Page 30 For outputs supporting multi-output, specify pulse voltage output or linear current output according to the multi-output output type. For linear current output, 0 to 20 mA or 4 to 20 mA can be selected. Pulse voltage output is 12 V DC, 40 mA.
  • Page 31: Explanation Of Model Numbers

    CompoWay/F DeviceNet The above is an explanation based on functionality. There may be some differences from the product line depending on the combination of features selected. Please check the catalogue when ordering. For details on using DeviceNet communications functions, refer to the E5AR/E5ER Digital Controller DeviceNet Communications User’s Manual (H124).
  • Page 32 Section 2 Preparations Installation ................. 2-2 How to Use the Terminals..........2-4...
  • Page 33: Installation

    PF 1 PF 2 /CH E5ER 11.5 SUB1 SUB2 SUB3 SUB4 8. 8 . 8 . 8 . 8 8. 8 . 8 . 8 . 8 8. 8 . 8 . 8 MANU OUT1 OUT2 STOP RSP ■ Installation ●...
  • Page 34 ● Pulling the unit out Normally there is no need to pull out the unit, however, it can be pulled out if needed for maintenance purposes. When pulling the unit out, place a cloth over the screwdriver to prevent...
  • Page 35: How To Use The Terminals

    Section 2 Preparations 2.2 How to Use the Terminals Verify the layout of the terminals (A - , 1 - ) using the engravings on the top and sides of the case ■ E5AR E5AR-Q4B E5AR-C4B E5AR-A4B-500 E5AR-A4B-500 E5AR-A4B-500 E5AR-A4B-500...
  • Page 36 2.2 How to Use the Terminals E5AR-Q43DB-FLK E5AR-C43DB-FLK E5AR-A4B-500 E5AR-A4B-500 E5AR-A4B-500 E5AR-A4B-500 Auxiliary outputs Auxiliary outputs 100-240 VAC 100-240 VAC (Relay outputs) (Relay outputs) SUB1 SUB1 SUB2 SUB2 SUB3 SUB3 E53-ARQC3 SUB4 SUB4 B(+) RS-485 E53-ARB4 E53-ARB4 A(-) OUT2 Event inputs...
  • Page 37 A(-) E53-ARB4 E53-ARB4 OUT2 Current output Event inputs Event inputs Voltage output 4-20 mA DC, 500 max. 12 V 40 mA 0-20 mA DC, 500 max. OUT1 (Switch using output Voltage output type setting.) 12 V 40 mA or OUT1...
  • Page 38 2.2 How to Use the Terminals E5AR-CC43DWW-FLK (4-loop Control) E5AR-QQ43DWW-FLK (4-loop Control) E5AR-A4WW-500 E5AR-A4W-500 E5AR-A4WW-500 E5AR-A4WW-500 Auxiliary outputs 24 VAC/DC 100-240 VAC Auxiliary outputs 100-240 VAC (Relay outputs) (Relay outputs) SUB1 Input power supply depends SUB1 on the model. SUB2...
  • Page 39: E5Er

    E53-ARCC Event inputs Event inputs OUT2 OUT2 Voltage output Current output 12 V 40 mA 4-20 mA DC, 500 max. 0-20 mA DC, 500 max. OUT1 (Switching by output Voltage output type setting) 12 V 40 mA or OUT1 Current output...
  • Page 40 2.2 How to Use the Terminals E5ER-QT3DB-FLK E5ER-CT3DB-FLK E5ER-AB-500 E53-ARB4 E5ER-AB-500 E53-ARB4 100-240 VAC 100-240 VAC Event inputs Event inputs E53-ARQC3 E53-ARCC3 B(+) B(+) RS-485 RS-485 A(-) A(-) OUT2 OUT2 Current output Voltage output 4-20 mA DC, 500 max. 12 V 40 mA 0-20 mA DC, 500 max.
  • Page 41 (Relay outputs) Input power supply depends Input power supply depends SUB1 on the model. on the model. 100 to 240 VAC 100 to 240 VAC or 24 VAC/DC SUB2 or 24 VAC/DC (no polarity) (no polarity) E53-ARRR3 E53-ARRR SUB3 B(+)
  • Page 42: Precautions When Wiring

    2.2 How to Use the Terminals ■ Precautions when wiring • To avoid the effects of noise, wire the signal wires and the power line separately. • Use crimp terminals to connect to the terminals. • Tighten screws to a torque of 0.40 to 0.56 N •...
  • Page 43 Section 2 Preparations ● Inputs (terminals) • For Input 1 (IN1), connect terminals K4 to K6 on the E5AR, or E4 to E6 on the E5ER, as follows according to the input type. E5AR • For a multi-point input type, connect inputs 2 to 4 (IN2 to IN4) in the same way according to the number of input points.
  • Page 44 2.2 How to Use the Terminals • Control outputs that are not used for control can be used for transfer output with the "control output / transfer output assignment" setting. • Specifications for each output type are as follows: Output type Specifications Output voltage: 12 V DC+15%, –20%(PNP)
  • Page 45 Residual voltage 1.5 V max. Leakage current 0.4 mA max. ● Potentiometer • If you wish to use a position proportional control type to monitor the inputs (terminals) amount of valve opening or perform closed control, connect a poten- tiometer (PMTR) as shown in the following.
  • Page 46 • To use event input on the E5ER, connect event inputs 1 and 2 (EV1 and EV2) to terminals E2 to E3 and event inputs 3 to 6 (EV3 to EV6) to terminals numbers B2 to B6. The number of event input points varies depending on the model.
  • Page 47 Section 2 Preparations • The number of input points of each model is as follows: E5AR-@@@B, E5ER-@@@B: 2 points, EV1 and EV2 E5AR-@@D@, E5ER-@@D: 4 points, EV3 to EV6 E5AR-@@DB: 6 points, EV1 to EV6 E5AR Using contact Using non-contact...
  • Page 48 RS-485 RS-485 A(-) A(-) • The connection type is 1:1 or 1:N. In a 1:N installation, up to 32 RS485 units, including the host computer, can be connected. • The maximum total cable length is 500 m. • Use a shielded twisted pair cable (AWG28 or higher).
  • Page 49 Section 2 Preparations Insulation blocks As shown in the following diagram, each function block of the E5AR/ ER is electrically insulated. <Input> <event input · voltage output · current output> <communi- cation> are insulated from each other with functional insulation.
  • Page 50 Section 3 Typical Control Examples Standard control ..............3-2 Heating/cooling control of a chemical reaction device..3-5 Position proportional control of a ceramic kiln ....3-9 Cascade control of reflow ovens........3-13 Ratio control of dyeing machines........3-18...
  • Page 51: Standard Control

    Section 3 Typical Control Examples 3.1 Standard control The following is an example of basic, single-loop control whereby temperature control of a heater plate for semiconductors is carried out (example of combined sensor and heater). ■ Application When controlling a heater plater for semiconductor wafers with the...
  • Page 52: Settings

    The following explains how to set the input type, the output type of output 1, the SP, and the control period (heat), and how to check the control mode. 1. Before turning on the power, check that the input 1 type switch is set to TC. Input 1 type switch TC.PT...
  • Page 53: Adjustment

    Section 3 Typical Control Examples 6. Press the L key less than 1 second to move from "RUN level" to Adjustment level "Adjustment level". bank l.adj Control period 7. Press the M repeatedly to select "cp: Control period (heat)", and then ( Heat ) press the D key to select "0.2".
  • Page 54: Heating/Cooling Control Of A Chemical Reaction Device

    In temperature control of chemical processes where heat is naturally generated by chemical reactions, heating output and natural cooling are not a sufficient means of control, and thus heating/cooling control is used whereby heating output and cooling output are simultaneously manipulated.
  • Page 55: Wiring

    Input initial setting level 1. Turn on the power and then hold down the L key for at least 3 seconds to i1-t move from "RUN level" to "Input initial setting level".
  • Page 56: Adjustment

    Control mode to select "1: Heating/cooling control". RUN level 4. Hold down the L key for at least 1 second to return to "RUN level". "PV/ Present value ( PV ) / SP/ 23.0 SP/MV" will appear. Press the U key to set the value to "250.0".
  • Page 57: Settings For Heating/Cooling Control

    "Cooling coefficient" settings can be used. ● Dead band The dead band is set centered on the SP. The dead band width is set in "Dead band" in the "Adjustment level". Setting a negative value changes the dead band to an overlap band.
  • Page 58: Position Proportional Control Of A Ceramic Kiln

    3.3 Position proportional control of a ceramic kiln The control method whereby a potentiometer is used to read the amount of opening of a valve and then open or close the valve by means of an attached control motor is called position proportional control or on/ off servo control.
  • Page 59: Wiring

    Input initial setting level 1. Turn on the power and then hold down the L key for at least 3 seconds to i1-t move from "RUN level" to "Input initial setting level".
  • Page 60: Adjustment

    5. Press the L key less than 1 second to move from "RUN level to Adjustment level "Adjustment level". bank l.adj 6. Press the M key to select "sprh: SP ramp rise value", and press the U sprh SP ramp rise value key to set the value to "10.0". 10.0 l.adj...
  • Page 61: Settings For Position Proportional Control

    In the event that a break occurs in the O or C wires of the potentiometer, potentiometer errors may not be detect- Important able, thus this function (stop control or switch to floating control) does not operate.
  • Page 62: Cascade Control Of Reflow Ovens

    Cascade control is used to reduce the effects of disturbances in the manipulated system (disturbances in the secondary loop) by adding a second PID loop to the regular PID loop. Cascade control is also used in situations where a sensor is added close to the object to improve control performance.
  • Page 63: Wiring

    The control mode and SP are set in the following, and the initial settings are used for all other parameters. Input initial setting level 1. Turn on the power and then hold down the L key for at least 3 seconds to i1-t move from "RUN level" to "Input initial setting level".
  • Page 64: Adjustment

    Control mode to select "5: Cascade standard control". RUN level 4. Hold down the L at least 1 second to return to "RUN level". "PV/SP/MV" Present value ( PV ) / SP / 23.0 will appear. Press the U key to set the SP to "180.0".
  • Page 65 Ch 2 AT Execute/Cancel 7. Press the M key to select the secondary (ch 2) "at: AT Execute / Cancel". Press the U to change the set value to "0" and run AT. During AT the l.adj automatically selected PID Set No. is displayed and display 1 (at) blinks.
  • Page 66 M repeatedly to select "at: AT SPDTh 9. Press the Execute / Cancel" of the primary loop (ch 1). Press the U key to change AT Execute / Cancel the set value to "0" and run primary AT. During AT the automatically selected PID Set No.
  • Page 67: Ratio Control Of Dyeing Machines

    PF2/CH 4 - 20 mA Settings are shown when 4 to 20 mA is used in the input from the dye flow sensor, 4 to 20 mA is used in the input from the sand weight measurement sensor, and a pump is used that is driven by an inverter with a 4 to 20 mA input is used in the manipulation system.
  • Page 68: Wiring

    The scale of sensor 1, which measures the flow of dye, is 0.0 to 25.0 kg/s, and the scale of sensor 2, which measures the weight of sand, is 0.0 to 500.0 kg/s. The ratio value is set to 0.05 so that the proportion of sand to dye will be 110 : 5.
  • Page 69 Straight-line approximation 1 Straight-line approximation 1 Output First, to make the units of input 2 match the units of input 1, input 2 is converted from normalized data to an industrial quantity using straight- line approximation 1. Convert 0.000 - 1.000 to 0 - 5.000.
  • Page 70: Adjustment

    On the E5AR/ER, use normalized numbers for approxi- mation settings such as broken-line and straight-line Hint approximation. For example, use 0.200 for 20%. Also, if input 1 is K-200.0 to 1300.0°C, use 0% (0.000) for -200.0°C and 100% (1.000) for 1300.0°C. 3-21...
  • Page 71 Section 3 Typical Control Examples 3-22...
  • Page 72 Setting output parameters ..........4-14 Setting and changing the SP ........... 4-17 Performing ON/OFF control ..........4-18 4.10 Determining the PID constants (AT, manual settings)..4-20 4.11 Using auxiliary output ............4-23 4.12 Starting and stopping control........... 4-27 4.13 Performing manual control..........4-29 4.14 Changing channels ............
  • Page 73: Setting Levels And Key Operation

    The settings are grouped into levels and the set values are called setting data. On the E5AR/ER, the settings are grouped into 17 levels as shown below. When the power is turned on, all indicators light up for 1 second. The initial level after power-on is "RUN level".
  • Page 74 Calibration level Calibration by the user. * To move to the special function setting level, set "Initial setting protect" in the "Protect level" to "0". In following each levels, control is stopped, input initial settings, control initial setting, control initial settings 2, alarm settings, display adjustment, communication settings, advanced function settings, expansion control settings and calibration.
  • Page 75: Set Values

    Section 4 Settings Required for Basic Control 4.2 Set values The values selected for each setting are called "set values". There are two types of set values: numbers and characters. Set values are displayed and changed as follows: Changing a numeric set value 1.
  • Page 76: Initial Setting Examples

    This section explains how to configure the initial settings for the sensor input type, alarm type, control period, and other parameters. Use the L key and M key to move through the display screens. The desti- nation screen will vary depending on how long each key is held down.
  • Page 77 3. Refer to alarm type list (page 8-54) 4, Alarm type setting Change the alarm alt2 Alarm 2 type type with the UD 2 8: Absolute-value upper-limit alarm l. 3 Press for at least 1 second to return to RUN level.
  • Page 78 Verify that the display Display bank selection bank selection is 0 l.bnk 0: Bank No. 0 0. a l-1 Bank No. 0 alarm value 1 Set alarm value 1with 6, Set alarm value 1 0.0 5.. 0 :5.0 C the UD keys l.bnk 0.
  • Page 79: Setting The Input Type

    When using a multi-point input type, set input type switches 2 to 4 and configure input type settings 2 to 4 as appropriate for the number of input points.
  • Page 80 Setting the display to show 0.0 for an input value of 5 mA and 100.0 for 20 mA when the input 1 type is set to "4 to 20 mA". 1. Hold the L key down for at least 3 seconds to move from "RUN level" to 25.0 "Input initial setting level".
  • Page 81: Input Type

    The operation of E5AR/ER control functions and alarms is based on the input values. If a value greater than "inp.2: Scaling input value 2" is set for "inp.1: Scaling input value 1," operation will be as follows for the display value: •...
  • Page 82 The upper-limit alarm and lower-limit alarm will be inverted. Therefore, set an alarm type and alarm values that invert the upper limit or lower limit of the display value. For example, if an absolute-value upper limit is set for the alarm type, operation will be as shown in the following figure.
  • Page 83: Selecting The Temperature Units

    When the input type is set to temperature input (input from a thermocouple or a platinum resistance temperature input sensor), "°C" or "°F" can be selected for the temperature units. When using a multi-point input type, set the temperature units separately for each input (2 to 4) as appro- priate for the number of inputs.
  • Page 84: Selecting The Control Mode

    ● Cascade standard • Cascade control is performed using standard control. control • Input 1 is for the primary loop (ch1) and input 2 is for the secondary loop (ch2). ● Cascade heating/ • Cascade control is performed using heating/cooling control.
  • Page 85: Setting Output Parameters

    Set value (in general) Direct action Reverse action • For example, when the present value (PV) is less than the set point (SP) during heating control, the manipulated valuable (MV) is increased in proportion to the difference between the PV and SP. As such, heating control is "reverse operation".
  • Page 86: Output Type

    The E5AR-Q@@@@, output 1 of the E5ER-Q@@@, and outputs 1 and 3 of the E5AR-QQ@@ are multi-outputs. • Linear current output can be set to 4 to 20 mA or 0 to 20 mA in "Linear current output*: Output type".
  • Page 87 Section 4 Settings Required for Basic Control 1-input 4-input Out- Control / Transfer output Control mode 2-input type type type assignment OUT1 Channel 1 control output (heating side) OUT2 Channel 2 control output (heating side) Standard control OUT3 Channel 3 control output (heating side)
  • Page 88: Setting And Changing The Sp

    "ON", the SP cannot be changed. For more information, see "5.5 Protecting settings" (P.5-24). • To change the SP, press the UD keys in "PV/SP" (RUN level) to select the desired value. The new setting becomes effective 2 seconds after the change.
  • Page 89: Performing On/Off Control

    SP during control. When the control output turns off, the temperature begins to fall, and once it falls to a certain point the control output turns on again. This action is repeated around a certain position. ON/OFF control requires setting "Hysteresis (heat)" to the temperature drop from the SP at which it is desired that the control output turn on.
  • Page 90: Settings

    2. "Display PID selection" appears in "PID setting level". If a PID Set No. will not be used, use the initial setting "1". If a PID Set No. will be used, select the PID Set No. for the desired control.
  • Page 91: Determining The Pid Constants (At, Manual Settings)

    • AT cannot be run during STOP or in manual mode. • When running AT, select "0" to run AT for the PID set currently being used for control, or select "1" to "8" as appropriate to run AT for a specific PID set.
  • Page 92 • If "Run/Stop" is set to "Stop" while AT is running, AT will stop and operation will stop. If "Run" is then selected, AT will not resume. • If an input error occurs while AT is running, AT will stop. AT will run again after recovery from the error.
  • Page 93: Manual Settings

    The PID constants are set in "Proportional band (P)", "Integral time (I)", and "Derivative time (D)". • I (Integral time) and D (Derivative time) can be set to "0" to select propor- tional action. In the initial settings, "the manual reset value" is set to 50.0% so that the proportional band is centered on the SP.
  • Page 94: Using Auxiliary Output

    All channels alarm 4 OR output All channels input error OR output All channels RSP input error OR output U-ALM output is an OR output (overall alarm) of alarms 1 to 4 of all channels. The initial settings are as follows:...
  • Page 95: Alarm Types

    ∗6 with standby sequence ∗1: Set values (in general) 1, 4 and 5 allow upper and lower-limits of alarm value to be separately set, and are indicated by L and H. ∗2: Set value (in general) : 1 Upper-and lower-limit alarm...
  • Page 96: Alarm Values

    The following explains how to set "Auxiliary output 2 assignment" to assignment "CH 1 alarm 1" in "Control initial setting level 2" 1. Hold down the L key at least 3 seconds to move from "RUN level" to 25.0 "Input initial setting level".
  • Page 97 Section 4 Settings Required for Basic Control 4. Press the D to set the auxiliary output 2 assignment to "1: CH 1 alarm 1". 5bo.2 5bo.2 Alarm 1 type Set "Alarm 1 type" to "Lower-limit alarm" in "Alarm setting level".
  • Page 98: Starting And Stopping Control

    Stop" to "Stop". ● MV at stop • If you wish to output during stop in standard control, set an MV of - 5.0 to 105.0% in "MV at stop". The initial setting is "0.0%". (In heating/cooling control, set to -105.0 to 105.0%) •...
  • Page 99: Settings

    The procedure for stopping control is as follows: 1. Press the M key repeatedly to select "r-s: Run/Stop". 25.0 2. Press the U key to switch to "stop: Stop". The STOP indicator blinks and control stops. stop To resume control, follow the same steps to switch to "run: Run". The STOP indicator goes off and control resumes.
  • Page 100: Performing Manual Control

    Display 3. When a potentiometer is not connected, Display 2 shows "-----". • To turn on open output, press the U key. To turn on closed output, press the D key. The MV is updated every 50 ms. • When switching between manual mode and auto mode, the action of the MV is balance-less, bumpless.
  • Page 101 25.0 MANU indicator goes off and the mode changes to auto. ◆ When Auto / Manual is not selected with either the PF1 setting or PF2 setting 1. Press the M key repeatedly to select "a-m: Auto / Manual". 25.0 auto 2.
  • Page 102: Changing Channels

    • Only channels that are enabled with the "Number of enabled 2.5.0 channels" setting can be displayed. • If the "Number of enabled channels" setting is set to "2" on a 4-point input type, the display will switch through the channels as follows each time the...
  • Page 103: Operational Considerations

    Section 4 Settings Required for Basic Control 4.15 Operational considerations (1) About four seconds is required for the output to turn on after the power is turned on. Take this into consideration when incorporating the controller into a sequence circuit.
  • Page 104 Section 5 Functions and Operations Input adjustment functions..........5-2 Control functions..............5-8 Output adjustment functions ..........5-16 Display and key adjustment functions......5-19 Protecting settings ............5-24 Alarm adjustment functions ..........5-26 Using event input ............. 5-29 Using transfer output ............5-32...
  • Page 105: Input Adjustment Functions

    "Input shift 2", and thus the slope of the line between the two points may differ before and after correction. • Input shift is set for each channel. The input shift settings for inputs 1 to 4 of a multi-point input type correspond to channels 1 to 4. First...
  • Page 106 SP. Measure the temperature using 2-point of the object when it is near room temperature and when it is near the SP (B), correction and check the corresponding readings of the controller (A).
  • Page 107 Section 5 Functions and Operations ● Example of 2-point The following is an example when the input type is K (-1) -200 to correction 1300°C The temperature of the object will be obtained. Room temperature: When (B) = 25°C the controller reading is (A) = 40°C...
  • Page 108: First Order Lag Operation

    • First order lag operation serves as a filter for each input. For a multi- 1st order lag operation 1: enabled input type, the operation is set for each of inputs 1 to 4 in "First order lag.1 lag operation 1 - 4".
  • Page 109: Broken-Line Approximation

    1 Inputs 1 to 20" and "Broken-line approximation 1 Outputs 1 to 20". Normalized data is used to set the values such that the lower-limit of the input setting range for input 1 is 0.000 and the upper-limit is 1.000.
  • Page 110: Extraction Of Square Root Operations

    Square root extraction cut point, the result is set to "0". The low-cut point is set for each operation input using normalized data such that the lower-limit of the input sqrp.1...
  • Page 111: Control Functions

    During SP ramp, control takes place not by changing the SP, but l.adj rather by using a value that is limited by the set rate of change (this is called the ramp SP). SP ramp rise value On the E5AR/ER, an "SP ramp rise value" and an "SP ramp fall value"...
  • Page 112: Banks

    *2 The decimal point position depends on the input type. ■ Banks • Up to eight banks can be created. Each bank is used to store an SP (local SP), alarm value, and a PID Set No.. Bank No.
  • Page 113 Section 5 Functions and Operations ● PID Set No. • To select and use a PID Set No., select 1 to 8 and then specify one of PID Set No. 1 to 8 for each bank. PID* Set No. • Normally the initial setting "0: Auto selection" is used. To use this 0.pid...
  • Page 114 8. Use the UD keys to select "2" to execute Bank l.adj Present value ( PV ) / SP / Bank No. 9. Press the L key repeatedly to move to RUN level, and then press the M key to move to "PV/SP/Bank No.". 25.0 250.0...
  • Page 115: Sp Limits

    SP setting upper limit setting range. sl-h If SP limits are set and the SP (local SP) falls outside the limits, the SP 1300.0 will be changed to either the upper or lower SP limit. Example: Initially the SP is 200°C, the SP setting upper limit is 300°C, and the SP setting lower limit is 100°C.
  • Page 116 10.00 50.00 l.pid • A PID Set No. (1 to 8) is set in "PID Set No." in "Bank setting level". For this reason, PID control parameters different from the selected bank can be used during operation. • If "PID Set No." is set to "0", the PID set is automatically selected (PID auto selection) according to previously set conditions.
  • Page 117: Disturbance Overshoot Adjustment

    When disturbance gain is 1 Time ● Constant at • The reset time after a disturbance can be lengthened by increasing disturbance the disturbance time contstant. (The default value "1" is normally used for the disturbance time constant. In the event that adjustment of the disturbance gain alone is not sufficient, this value can be adjusted for fine-tuning.)
  • Page 118 • During PD control (I = 0.00) • The units for the "Disturbance rectification band" and "Disturbance Disturbance judgement width judgement width" settings are % FS. As such, if the input type is dojw K(1) -200.0 to 1300.0°C and you wish to set the "Disturbance 0.00...
  • Page 119: Output Adjustment Functions

    • The following MVs take precedence over the MV limit function. Manual MV default MV at stop MV at PV error • The "MV upper limit" and "MV lower limit" can also be set in each Upper limit value of MV limit PID set.
  • Page 120: Mv Change Rate Limit

    • The MV change rate limit is used to set a maximum allowed change MV change rate limit ( heating ) per second in the MV (or in the opening of a valve in the case of a position proportional controll type). If a change occurs in the MV that exceeds this setting, the MV is changed by the set limit each second until the required change is attained.
  • Page 121: Mv At Stop

    In heating/cooling control a negative value is used for the cooling mV-5 MV, thus when "MV at Stop" is positive, the MV will be sent to the heating output, and when negative the MV will be sent to the cooling output.
  • Page 122: Display And Key Adjustment Functions

    Adjustment, Adjustment 2, Bank setting, PID setting, Approximation setting, or Monitor item level. Display 1 starts to blink after the key is held down for 1 second, and after the key is held down for another 2 seconds, the display stops blinking and display scan begins.
  • Page 123 Stop using key Stop display scan 1 second or more Present value (PV) / SP (Display 1) Normal operation 2 0 0 0 Channel indication is not updated when display scan stops (in above example, display remains at channel 2) 5-20...
  • Page 124: Pf Settings (Function Keys)

    Select "Monitor / Setting item 1" to "Monitor / Setting item 5" (Special function level). • Hold down the PF1 or PF2 for at least 1 second to execute the function selected in "PF1 setting" or "PF2 setting". If "Monitor / Setting item" is selected, the display will scroll through monitor/setting items 1 to 5 each time you press the key.
  • Page 125 "PF1 setting" or "PF2 setting" can be set to "Monitor/Settings (pfdp)" to display monitor/settings using a function key. The content to be displayed is set for each channel in "Monitor / Setting item 1" through "Monitor / Setting item 5" of the corresponding function key.
  • Page 126: Other Display And Key Adjustment Functions

    RUN level of the new channel will appear. • If the other function key is pressed and it is also set to "Monitor/ Setting item", the "Monitor/Setting item" of that key will appear.
  • Page 127: Protecting Settings

    Prohibited • When "Initial setting level protect" is set to "2", nothing happens when the level key is held down to move to Input initial setting level from Operation, Adjustment, Adjustment 2, Bank setting, PID setting, Approximation setting or Monitor item level (the blinking display to indicate movement to another level also does not appear).
  • Page 128 This function prevents use of the PF1/PF2 keys. PF key protect Setting Description value pfpt PF1/PF2 keys are enabled. l.prt PF1/PF2 keys are disabled. (Prohibits use as a function key or a channel key.) • The initial setting for "PF key protect" is "OFF". 5-25...
  • Page 129: Alarm Adjustment Functions

    Operation startup (including power on), or when the alarm value (alarm upper- and lower-limit) or input shift (input value for input shift 1, input shift 1, input value for input shift 2, or input shift 2) is changed, or when the SP is changed.
  • Page 130: Alarm Latch

    Alarm 4 latch temperature. a4lt • The alarm latch state can be canceled by turning the power off or by a communication command. • Alarm latch is set separately for each alarm in "Alarm 1-4 latch". • The initial setting is "0: OFF".
  • Page 131 Section 5 Functions and Operations Display Setting data Level characters name (Display 3) Alarms 1 to 4 Alarm setting Sets the alarm type Type (l.3) Alarms 1 to 4 Alarm setting Alarm output latch Latch (l.3) (hold) Alarms 1 to 4...
  • Page 132: Using Event Input

    Channel 2 run/stop Channel 4 auto/manual ● Communication • When the event input is ON, setting data can be written with the write OFF/ON communication function and the "CMW" indicator lights up. The content of the event input is reflected in "Communication OFF/ON"...
  • Page 133 Run Bank No.5 Run Bank No.6 Run Bank No.7 • To use eight banks (Banks 0 to 7), 3 event input points are required. ● Run/Stop • When the event input is ON, operation is stopped and the "STOP" indicator lights up. The content of the event input is reflected in "Run/Stop"...
  • Page 134 • This function is only effective when the control mode is control with remote SP. • When the event input is ON, the remote SP (RSP) is used as the SP and the "RSP" operation indicator lights up. When the event input is OFF, the local SP (LSP) is used as the SP.
  • Page 135: Using Transfer Output

    • For transfer output, use an output that is not used for control output. ● Control / Transfer • Transfer output can be used to output one of the following 6 types of output assignment data as selected in "Control / Transfer output assignment". For more information, see "8.11 Control initial setting 2 level (l.2) Control /...
  • Page 136 5.8 Using transfer output • If the "Input type", "Scaling display value 1, 2", "SP upper and lower limit", or "Temperature units" setting is changed when "SP" or "Ramp SP" is selected, the "Transfer output upper limit" and "Transfer output lower limit"...
  • Page 137: Using Communication Functions

    When performing communication with a host computer, a unit number must be set in each controller to allow the host computer to recognize it. Any number from 0 to 99 can be set. The unit number is initially set to 1. When using multiple controllers, make sure that no units have the same unit number or communication will not take place correctly.
  • Page 138: Write Via Communication

    1. Hold down the L for 3 seconds to move from "RUN level" to "Initial setting level". 2. Press the L key to move from "Input initial setting level" to "Communica- tions setting level".
  • Page 139 Section 5 Functions and Operations 5-36...
  • Page 140 Communication method............. 6-2 Frames (Communication/CompoWay/F)......6-4 FINS-mini text ..............6-6 Variable areas..............6-7 Reading the variable area..........6-9 Writing to the variable area..........6-10 Operation commands (Communication/CompoWay/F) ... 6-11 Setting areas ..............6-13 Commands and responses (Communication/CompoWay/F)........6-14 6.10 Program example ............6-32...
  • Page 141: Communication (Compoway/F)

    The communication function is communication. Featuring a unified frame format and commands that used by creating a program on are compliant with FINS, which has a record of successful use with the host computer. As such, OMRON programmable controllers, CompoWay/F makes communi- the explanations in this section cation easy between multiple components and a computer.
  • Page 142 6.1 Communication method When writing multiple sets of setting data in a row, such as when writing to the variable area or performing a compound write, controlla- bility may be affected. Pay attention to the following points: Maximum of 3 sets of...
  • Page 143: Frames (Communication/Compoway/F)

    02H 30H 30H 30H 30H 30H 30H 35H 30H 30H 03H 36H BCC = 30H + 30H + 30H + 30H + 30H + 30H + 35H + 30H + 30H + 03H = 36H +: XOR (exclusive OR) operation...
  • Page 144: Response Frame

    "0F" FINS command error Could not execute the specified FINS command. Sum of bits that are "1" in received data does not agree "10" Parity error with the set communication parity value. "11" Framing error Stop bit of command frame characters is "0".
  • Page 145: Fins-Mini Text

    Section 6 Communication (CompoWay/F) 6.3 FINS-mini text The FINS-mini command text and FINS-mini response text form the body of command/response commu- nication. FINS-mini command text and FINS-mini response text are configured as follows. Command text FINS-mini command text consists of an MRC (main request code) and an SRC (sub request code), followed by the required data.
  • Page 146: Variable Areas

    The area used for data exchange when communicating with the E5AR/ER is called the "variable area". The PV is read and various setting data are read and written using the variable area of the E5AR/ER. Operation commands and reading of machine attributes do not use the variable area.
  • Page 147 Channel 4 In-area address This is a number that is assigned to each set of data in the variable area. Addresses are assigned in order beginning from the first set. For more information on addresses, see "Appendix Setting list" (P.A- 6).
  • Page 148: Reading The Variable Area

    6.5 Reading the variable area 6.5 Reading the variable area The data area is read by setting the required data in the following FINS-mini command text format. FINS-mini command text Command Variable type Read start address Bit position Number of elements "01"...
  • Page 149: Writing To The Variable Area

    Section 6 Communication (CompoWay/F) 6.6 Writing to the variable area Write to the data area by setting the required data in the following FINS-mini command text format. FINS-mini command text Command Variable Starting address Number of type of write Bit position...
  • Page 150: Operation Commands (Communication/Compoway/F)

    *: When all channels are specified, only enabled channels will respond and processing will begin from Channel 1. If an error is detected on any one channel, an "Operation error" will result. If all channels end normally, "Normal end" results.
  • Page 151 Unable to execute operation command. For more information, see correspond- "2203" Operation error ing operation command explanation in "6.9 Commands and responses (Com- munication/CompoWay/F)". Unit error, unit change, display unit error, internal non-volatile memory error "0000" Normal end 6-12...
  • Page 152: Setting Areas

    When the power is turned on, setting area 0 is selected. To access setting area 1, use the "Move to setting area 1" operation command. To return to setting area 0 from setting area 1, turn off the power or use the "Software reset" operation command.
  • Page 153: Commands And Responses (Communication/Compoway/F)

    Section 6 Communication (CompoWay/F) 6.9 Commands and responses (Communication/CompoWay/F) The E5AR/ER provides a set of applied commands that make use of variable area read/write commands, operation commands, and other services provided by the CompoWay/F communication protocol. E5AR/ER applied commands are explained below.
  • Page 154: Setting Data Read (Communication/Compoway/F)

    When used in setting area 1, the response for the PV and internal SP is "0" and the response for the status is as indicated in the notes in "Appendix Setting list Status" (P.A-8).
  • Page 155: Monitor Value / Setting Data Compound Read (Communication/Compoway/F)

    This command can be used in both setting area 0 and setting area 1. If an area type error or a setting data error occurs in any of the data being read, no data will be read. Response code Variable type...
  • Page 156: Protect Level Setting Data Write

    This command writes protect level setting data. See "5.5 Protecting settings" (P.5-24) for information on protect level. This command is used in setting area 0. An error will result if used in setting area 1. To use this command, use the "Write via communication" operation command to enable "Write via communication", and then use the...
  • Page 157: Setting Data Compound Write (Communication/Compoway/F)

    Section 6 Communication (CompoWay/F) To specify an address, see "Appendix Setting list" (P.A-6). Setting data of setting area 1 can be written in setting area 1. An error will result if written in setting area 0. To use this command, "Write via communication" must be enabled using the "Write via communication"...
  • Page 158: Monitor Value / Setting Data Compound Read Store (Write)

    To specify the variable type or address, see "Appendix Setting list" (P.A-6). The upper limit of an address will vary depending on the variable type. This command can be used in both setting area 0 and setting area 1. Response code Response "01"...
  • Page 159: Monitor Value / Setting Data Compound Read Store Check (Read)

    (write)". This command can be used in both setting area 0 and setting area 1. If an area type error or a setting data error occurs in any of the data being read, no data will be read.
  • Page 160: Write Via Communication

    When write via communication is disabled, communication cannot be used to write setting data or send operation commands such as Run/ Stop. The initial setting is "disabled". This command can be used in both setting area 0 and setting area 1. Response code Response "30"...
  • Page 161: Bank Change

    0 to 7 This command is used to change banks (there are 8 banks numbered 0 to 7). An SP, alarm values, and a PID Set No. are stored in each bank. This command can be used in both setting area 0 and setting area 1.
  • Page 162: At Execute

    "0". This command is used in setting area 0. If used in setting area 1, an operation error will result. An operation error will also result in the following situations: •...
  • Page 163: Write Mode

    Section 6 Communication (CompoWay/F) This command stops AT. This command is used in setting area 0. If used in setting area 1, an operation error will result. An operation error will also result in the following situations: • "Run/Stop" of the specified channel is set to "Stop".
  • Page 164: Ram Data Store

    For information on these levels, see "4.1 Setting levels and key operation" (P.4-2). This command can be used in both setting area 0 and setting area 1. To use this command, "Write via communication" must be enabled using the "Write via communication" operation command.
  • Page 165: Move To Setting Area 1

    Use this command to move to protect level. Protect level is explained in "5.5 Protecting settings" (P.5-24). This command is used in setting area 0. If used in setting area 1, an operation error will result. To use this command, "Write via communication" must be enabled using the "Write via communication"...
  • Page 166: Auto / Manual

    "0B" "00" This returns all settings to the initial settings. This command is used in setting area 1. If used in setting area 0, an operation error will result. To use this command, "Write via communication" must be enabled using the "Write via communication" operation command.
  • Page 167: Cancel Latch

    This command cancels alarm latch. The command is used when the alarm latch function is in use. This command can be used in both setting area 0 and setting area 1. If AT is being run in the specified channel, an operation error will result.
  • Page 168: Read Machine Attributes

    6.9 Commands and responses (Communication/CompoWay/F) Response code Response "30" "05" "0000" Response codes: The above indicates a normal end. For the response codes, see "6.7 Operation commands (Communication/CompoWay/ F)" (P.6-11). ■ Read machine attributes Command "05" "03" This command reads the E5AR/ER model and communication buffer size.
  • Page 169: Controller Status Read (Communication/Compoway/F)

    Not occurred Occurred Blank * OR of channels set in "Number of enabled channels". * When the channel does not exist, is "Not occurred: 0". * If this command is used in setting area 1, the related information is undefined. 6-30...
  • Page 170: Echo Back Test

    "01" 0 to 200 bytes This command is used to perform an echo back test. The command can be used in any state of the E5AR/ER. Keep the test data within the following ranges depending on the communication data length.
  • Page 171: Program Example

    ■ N88Basic This program displays the response from the E5AR/ER on the screen when command data is entered from the keyboard. Command data from the unit number to the number of elements must be entered. The program was created in N88BASIC.
  • Page 172 6.10 Program example ● Operation example Reading the present value of Unit No.01. SEND DATA:010000101C00000000001 RESPONSE:010000010100000000014F SEND DATA: [STX] 01 00 0 0101 C0 0000 00 0001 [ETX] [BCC] Number of elements Bit position Read start address Variable type MRC/SRC Sub-address Node No.
  • Page 173 Section 6 Communication (CompoWay/F) 6-34...
  • Page 174 Section 7 Communication (Modbus) Communication method............. 7-2 Frames................7-4 List of functions..............7-7 Variable area..............7-8 Reading the variable area..........7-10 Writing to the variable area..........7-12 Operation commands (Communication/Modbus) .... 7-14 Setting areas ..............7-16 Commands and responses (Communication/Modbus)..7-17...
  • Page 175: Communication (Modbus)

    ■ Transfer protocol /Modbus) (Communication The host computer sends a command frame, and the E5AR/ER sends a response frame based on the content of the command frame. One response frame is sent in response to one command frame. Host computer E5AR/ER The exchange between the command frame and response frame is explained below.
  • Page 176 7.1 Communication method When writing multiple sets of setting data in a row, such as when writing to the variable area or performing a compound write, controlla- bility may be affected. Pay attention to the following points: Maximum of 3 setting...
  • Page 177: Frames

    The data comprising command frames and response frames are explained below. In the following explanation, an "H'" at the beginning of a numeric value (for example H'02) indicates that the value is a hexadecimal number. A number or letters enclosed in quotation marks (for example "00") is an ASCII character.
  • Page 178: Response Frame

    7.2 Frames (6) If the end of the message has not been reached, perform XOR on the next byte of the CRC register and the message, return the result to the CRC register, and repeat the procedure from step (3).
  • Page 179 The setting information in the written data is not permitted in the current operation mode. ◆ "Write via communication" is OFF (disabled). ◆ Attempted to write to setting data of setting area 1 from set- ting area 0. ◆ Attempted to write to protect setting data from other than...
  • Page 180: List Of Functions

    7.3 List of functions 7.3 List of functions Function codes supported on the E5AR/ER are shown below. Function codes (Communication/Modbus) Function Name Description codes Reads the variable area. Multiple Read variables 03 (H'03) variables that are contiguous can be (multiple) read.
  • Page 181: Variable Area

    The area used for data exchange when communicating with the E5AR/ER is called the "variable area". The PV is read and various setting data are read and written using the variable area of the E5AR/ER. Operation commands do not use the variable area.
  • Page 182 Channel 4 In-area address This is a number that is assigned to each set of data in the variable area. Addresses are assigned in order beginning from the first set. For more information on addresses, see the Modbus section in "Appendix Setting list"...
  • Page 183: Reading The Variable Area

    Section 7 Communication (Modbus) 7.5 Reading the variable area The variable area is read by setting the required data in the following command frame. Command frame Command Slave Function Read start Number of address mode address elements CRC-16 H’03 2 bytes...
  • Page 184 Normal end No error. ◆ Reading non-display data Setting data can be read even if it is set to non-display or is not displayed due to the model. Command response example Reading the PV of channel 1 (Client address: H'01)
  • Page 185: Writing To The Variable Area

    Section 7 Communication (Modbus) 7.6 Writing to the variable area Write to the variable area by setting the required data in the following command frame. Command frame Command Slave Function Write start Number of Byte Write data address mode address...
  • Page 186 Normal end No error ◆ Writing non-display data It is possible to write to setting data even if it is set to non-display or is not displayed due to the model; however, exercise caution when writing continuously. Command/response example Writing to "SP setting upper limit" and "SP setting lower limit" of control initial setting level of channel 1.
  • Page 187: Operation Commands (Communication/Modbus)

    *: When all channels are specified, only enabled channels will respond and processing will begin from Channel 1. If an error is detected on any one channel, an "Operation error" will result. If all channels end normally, "Normal end" results.
  • Page 188 Explanation Client address The value from the command frame appears here. This is the received function code. In an error response frame, "H'80" is added to the received function code to indicate that it is an error Function code response.
  • Page 189: Setting Areas

    When the power is turned on, setting area 0 is selected. To access setting area 1, use the "Move to setting area 1" operation command. To return to setting area 0 from setting area 1, turn off the power or use the "Software reset" operation command.
  • Page 190: Commands And Responses (Communication/Modbus)

    7.9 Commands and responses (Communication/Modbus) 7.9 Commands and responses (Communication/Modbus) The E5AR/ER provides a set of command frames that make use of variable area read/write commands, operation commands, and other services provided by the Modbus communication protocol. E5AR/ER command frames are explained below.
  • Page 191: Read Setting Data (Communication/Modbus)

    This command is used to read setting data. The number of elements can be set from H'0004 to 006A (4 to 106) to allow successive reading of 2 to 53 items of setting data in contiguous addresses. To specify the variable type or address, see "Appendix Setting list"...
  • Page 192: Write Setting Data To Protect Level

    This command writes setting data to Protect level. Protect level is explained in "4.1 Setting levels and key operation" (P.4-2). This command is used in setting area 0. If used in setting area 1, an error will result. To use this command, use the "Write via communication" operation command to enable "Write via communication", and then use the...
  • Page 193 This command is used to write setting data. The number of elements can be set from H'0004 to 0068 (4 to 104) to allow successive writing of 2 to 52 items of setting data in contiguous addresses. To specify the variable type or address, see "Appendix Setting list"...
  • Page 194: Write Via Communication

    When Write via communication is disabled, communication cannot be used to write setting data or send operation commands such as Run/ Stop. The initial setting is "disabled". This command can be used in both setting area 0 and setting area 1. Slave Function Write start...
  • Page 195: Bank Change

    0 to 7 This command is used to change banks (there are 8 banks numbered 0 to 7). An SP, alarm values, and a PID Set No. are stored in each bank. This command can be used in both setting area 0 and setting area 1.
  • Page 196: At Execute

    "0". This command is used in setting area 0. If used in setting area 1, an operation error will result. An operation error will also result in the following situations: •...
  • Page 197: Write Mode

    Section 7 Communication (Modbus) This command stops AT. This command is used in setting area 0. If used in setting area 1, an operation error will result. An operation error will also result in the following situations: • "Run/Stop" of the specified channel is set to "Stop".
  • Page 198: Ram Data Store

    Operation and Adjustment levels are explained in "4.1 Setting levels and key operation" (P.4-2). This command can be used in both setting area 0 and setting area 1. To use this command, "Write via communication" must be enabled using the "Write via communication"...
  • Page 199: Move To Setting Area 1

    Use this command to move to protect level. Protect level is explained in "4.1 Setting levels and key operation" (P.4-2). This command is used in setting area 0. If used in setting area 1, an operation error will result. To use this command, "Write via communication" must be enabled using the "Write via communication"...
  • Page 200: Auto / Manual

    H'F1 Manual Use this command to select auto or manual operation. This command is used in setting area 0. If used in setting area 1, an operation error will result. To use this command, "Write via communication" must be enabled using the "Write via communication"...
  • Page 201: Cancel Latch

    This command cancels alarm latch. The command is used when the alarm latch function is in use. This command can be used in both setting area 0 and setting area 1. If AT is being run in the specified channel, an operation error will result.
  • Page 202: Echo Back Test

    7.9 Commands and responses (Communication/Modbus) When the control mode is set to cascade control, perform the local SP/ remote SP operation command of CH2. Slave Function Write start Instruction Related Response CRC-16 address mode address code information H’06 H’00 H’00 H’0D...
  • Page 203 Section 7 Communication (Modbus) 7-30...
  • Page 204 (l.2) ......8-45 8.12 Alarm setting level (l.3) ......8-53 8.13 Display adjustment level (l.4) ......8-59 8.14 Communication setting level (l.5) ......8-63 8.15 Advanced function setting level (l.adf) ......8-67 8.16 Expansion control setting level (l.exc) ......8-72...
  • Page 205: How To Use This Section

    Reference ● Display conditions for related setting data A setting will only appear in the display of the E5AR/ER when the conditions of use for the setting are satisfied (conditions of use are indicated to the right of each setting in this section). Protected settings are not displayed regardless of the conditions of use, although they are in effect.
  • Page 206: Protect Level

    8.2 Protect level Protect level consists of four types of protection: "Operation adjustment protect", "Initial setting protect", "Setting change protect", and "PF key protect". Each is used to protect the corresponding settings and prevent accidental changes to the settings. Power on Protect levels l.prt...
  • Page 207 • When "Initial setting level protect" is set to "2", nothing happens when the level key is held down for 1 second to move to Input initial setting level from Operation, Adjustment, Adjustment 2, Bank setting, PID setting, Approximation setting, or Monitor item level.
  • Page 208: Operation Level

    8.3 Operation level ( ) 8.3 Operation level Display this level to operate the control system. The SP can be set and the PV monitored in this level. Power on Adjustment Adjustment 2 Operation level level level l. adj l. ad2...
  • Page 209 • In manual mode, operation is performed manually and the "MANU" indicator lights up. • "Manual output method" is used to select the MV that is used when entering manual mode. The MV prior to entering manual mode can be held, or the manual MV default value can be used.
  • Page 210 OUT1 OUT2 OUT3 OUT4 STOP RSP OUT1 OUT2 OUT3 OUT4 STOP RSP • When using a bank in local SP mode, a link is created to the local SP of the selected bank. For example, if Bank 3 is selected, the local SP of Bank 3 appears in Display 2, and when the value is changed, the value of "Bank 3 local SP"...
  • Page 211 Local SP, control mode set to standard control with remote SP • This is used to monitor the remote SP while in local SP mode. • In remote SP mode, the remote SP can be monitored in Display 2 of Function the PV/SP screen.
  • Page 212 • The ramp function limits the rate of change of the SP. Function • The setting is only displayed if a value is entered for "SP ramp rise value" or "SP ramp fall value". • For other than ramp, the SP value is the same as in "PV/SP".
  • Page 213 Monitors the amount of valve opening during operation. • Monitors the amount of valve opening during position proportional control. Function • A potentiometer can be connected and "Motor calibration" can be executed to monitor the amount of valve opening. Control Monitor range...
  • Page 214 • Use to select Auto or Manual. • The initial setting is "auto". Function Press the UD keys to select "auto: Auto" for Auto mode, or "manu: Manual" for Manual mode. When Manual mode is selected, the "MANU" indicator lights up.
  • Page 215: Adjustment Level

    Section 8 Setting data l.adj 8.4 Adjustment level ( This level contains settings for the purpose of adjusting control, such as change bank No., AT (Auto- tuning), enable/disable write via communication, hysteresis adjustment, input shift settings, and SP ramp settings.
  • Page 216 Bank No. • This setting is used to specify a bank (one of Bank Nos. 0 through 7). Each bank contains an SP (local SP), alarm value, and PID set Function number, and these settings are stored using the bank function in Bank setting level.
  • Page 217 • Use this setting to select the SP mode. • In local SP mode, the local SP set in the bank in the controller is Function used for control. In remote SP mode, the remote SP specified by an external signal (4 to 20 mA, etc.) is used.
  • Page 218 Dead band Heating/cooling control This sets an output dead band for heating/cooling control. A negative value can also be set to create an overlap band. Set an area centered on the SP where the control amount is 0 during heating/cooling control.
  • Page 219 Hysteresis (heating) chys ON/OFF Control (P = 0.0) Hysteresis (cooling) This sets the Hysteresis to enable stable operation when control is switched ON/OFF. • For standard control, "Hysteresis (heating)" is used. "Hysteresis (cooling)" cannot be used. Function • For heating/cooling control, the Hysteresis can be set separately for heating and cooling.
  • Page 220 8.4 Adjustment level (l.adj) l.adj Position proportional dead band Position proportional control type • This sets the output hold interval (the interval while switching the open output and close output ON and OFF) during position propor- Function tional control. Data range...
  • Page 221 Function (Completely open/Hold/Completely closed). • On a standard type, "MV at PV error" is set to the MV when an error occurs. On a position proportional control type, "MV at stop" is set to the position when an error occurs (Completely open/Hold/ Completely closed).
  • Page 222 • The MV change rate limit sets the maximum allowed change in the MV (or the opening on a position proportional control type) per second. If a change occurs in the MV that exceeds this limit, the MV Function will be changed at the set rate limit until the required change is attained.
  • Page 223 Input shift 2 Input shift can be performed at any two points. These settings are used to set input shift 1 and input shift 2 for any two points (input value 1 for input correction and input value 2 for input Function correction) (two-point correction).
  • Page 224 Disturbance time constant do-b Disturbance rectification band dojw Disturbance judgment width These settings are used to adjust overshoot to disturbances. • Disturbance gain is used to adjust the amount of overshoot caused by disturbances. Function Setting data Setting range Units...
  • Page 225: Adjustment 2 Level

    Adjustment level 2 contains supplemental settings for adjustment of control such as the time constant of first order lag operation, move average count, low-cut point of extraction of square root operations, and settings for proportional control. These functions only appear in the display if they are enabled in Control initial setting 2 level.
  • Page 226 Data following the move average is shown below. Function Input data Operation result Time • This function is used to reduce changes in the input due to distur- bances in the fluid surface when controlling fluid level. Setting range Units Default value...
  • Page 227 Extraction of square root 4 Low-cut point • These settings are used to set the low-cut point of each input. Data following extraction of square root operations are shown below. Function • This function is used for extraction of square root operations for fluid sensors.
  • Page 228 8.5 Adjustment 2 level (l.ad2) l.ad2 ap.1 Analog parameter 1 Proportional control This sets the proportion used for proportional control. Function Setting range Units Default value -1.999 to 9.999 1.000 Setting ● Related information "3.5 Ratio control of dyeing machines" (P.3-18)
  • Page 229: Bank Setting Level

    Section 8 Setting data l.bnk 8.6 Bank setting level This level includes SP, PID set, and alarm settings for each bank. To move to a bank, use "Display bank selection" which appears at the beginning of Bank setting level. Power on Bank setting level l.bnk...
  • Page 230 • When the PID Set No. is set to "0", the PID set auto select function Function automatically selects a PID set based on the PV or DV (deviation). If you wish to specify a PID set, set the number of the PID set (1 to 8). Setting data Setting range...
  • Page 231 Alarm function is enabled ( : 0 to 7) Use this setting to store alarm values for alarms 1 to 4 in each bank. • Set the values of alarms 1 to 4 in each of banks 0 to 7. Function Setting range...
  • Page 232 ( : 0 to 7) If an alarm mode with upper- and lower-limit settings is selected for "Alarm 1 type" through "Alarm 4 type", the upper limit and lower limit are set separately. • Set the upper and lower-limits of alarms 1 to 4 in banks 0 to 7.
  • Page 233: Pid Setting Level

    8.7 PID setting level ( This level contains the PID value, MV limit, and alarm settings for each PID set. To move to a PID set, use the "Display PID set select" setting at the beginning of PID setting level.
  • Page 234 Advanced PID control ( : 1 to 8) These settings are used to store PID values in each PID set. If AT is run, the values are set automatically. P action: Control action using an MV proportional to the deviation.
  • Page 235 PID Automatic selection range upper limit ( : 1 to 8) When using automatic selection of PID sets, use this setting to set an upper limit for each PID set. • Set the automatic selection range upper limit for PID Set Nos. 1 to 8.
  • Page 236: Approximation Setting Level

    1 and 2. Use normalized data for the Function values. • If Input 1 = Input 2, the setting will not be effective and will be regarded as straight-line approximation with input data = output data. Output value 2...
  • Page 237 Use normalized data for Function the values. • If Input n Input n + 1, the setting of point "n + 1" will not be effective. Operation result P5 disabled because Input 5 Input 4...
  • Page 238: Input Initial Setting Level

    8.9 Input initial setting level (l.0) 8.9 Input initial setting level This level contains initial settings for input, including input type, temperature units, and scaling settings. Power on Approximation Adjustment Adjustment 2 Bank setting PID setting Operation level setting level...
  • Page 239 -199.99 to 999.99 0 to 10V -19.999 to 99.999 ANALOG -1.9999 to 9.9999 Set the input type switch of each input to match the "Input type" setting of the corresponding input. The initial setting is "2". ("TC.PT") ● Related setting data Reference Reference "Input...
  • Page 240 • "Decimal point position" is used to specify the decimal point position of setting data (SP, etc.) for which the units are "EU". • Scaling settings for inputs 2 to 4 of multi-point input types are set in channels 2 to 4. Press the key to change to the desired analog input channel and then set the scaling.
  • Page 241 2, and the remote SP lower limit is set with respect to the lower input range limit of input 2. For example, if the input 2 type is 4 to 20 mA, the remote SP upper limit is set with respect to 20 mA and the remote SP lower limit is set with respect to 4 mA.
  • Page 242 PV decimal point display Temperature input This setting can be used to not show the digits of the PV after the decimal point. • When "PV decimal point display" is turned OFF, the digits of the PV after the decimal point are not shown. When turned ON, the digits Function after the decimal point are shown according to the input type setting.
  • Page 243 This function reduces induction noise from the power source in the input. • This reduces induction noise in the input according to the frequency of the power source. Function • Select 50 Hz or 60 Hz as appropriate for the power source used for the controller. Setting range Units...
  • Page 244: Control Initial Setting Level

    8.10 Control initial setting level (l.1) 8.10 Control initial setting level ( This level contains initial settings for control such as the control method, as well as the output type, SP limit, control mode, direct/reverse action, and closed/floating settings. Power on...
  • Page 245 • When pulse voltage output is selected, the output is 12 V DC, 40 Function • When linear current output is selected, use the "Linear current output type" setting to select an output of 0 to 20 mA or 4 to 20 mA. Setting data Setting range...
  • Page 246 SP upper limit sl-l SP lower limit • Use this setting to set upper and limits for the SP setting. The SP can only be set between these limits. Note that if the limits are Function changed and a previously set SP falls outside of the limits due to the change, the SP will automatically change to the upper or lower limit.
  • Page 247 Setting 3: Remote SP heating/cooling 4: Proportional 5: Cascade standard 6: Cascade heating/cooling The setting range is 0 to 1 on a single- or 4-input type, or 0 to 6 on a 2- input type. ● Related information Reference Reference "Section 3 Typical Control Examples"...
  • Page 248: Control Initial Setting 2 Level

    8.11 Control initial setting 2 level (l.2) 8.11 Control initial setting 2 level This level contains initial settings for computational functions, including Control/Transfer output assignment, event input assignment, auxiliary output assignment, and first order lag operation enable/ disable. Power on...
  • Page 249 CH3 (17 to 23) CH4 (25 to 31) * The default value is set according to the control mode setting. If transfer output is assigned to a bank output (3 to 8 in the case of CH1), the output will be OFF. Control/Transfer...
  • Page 250 • If the same setting is selected for different event input assignments, the event input for which ON/OFF is determined last will be effective. Note that when the power is turned on and the same bank No. assignment is repeated, the event input with the higher number is given priority.
  • Page 251 * On a multi-point input type, assignment data can be set for channels 2 and higher as appropriate for the number of channels. U-ALM output will be OR output of alarm functions 1 to 4 of all channels. ● Related information...
  • Page 252 Transfer output lower limit Transfer output using output assignment ( : 1 to 4) • These settings can only be used for outputs selected for transfer output using output assignment. Function Default value Control/ (upper limit/ Decimal...
  • Page 253 First order lag operation 3 enable lag.2 lag.4 First order lag operation 2 enable First order lag operation 4 enable • Use these settings to enable or disable first order lag operation for each input. Function Setting range Units Default value...
  • Page 254 Extraction of square root 3 enable sqr.2 sqr.4 Extraction of square root 2 enable Extraction of square root 4 enable • Use these settings to enable or disable extraction of square root operations for each input. Function Setting range Units...
  • Page 255 1 Output 20" (Approximation setting level) (P.8-34) calb Motor calibration Position proportional type • Use this setting to run motor calibration. If you are going to monitor the valve opening, be sure to execute this setting. (During execution Function the display cannot be changed.) •...
  • Page 256: Alarm Setting Level

    8.12 Alarm setting level (l.3) 8.12 Alarm setting level This level contains settings for the type and output operation of alarms, including alarm type, close in alarm/open in alarm, and latch settings. Power on Approximation Adjustment Bank setting PID setting...
  • Page 257 Alarm 2 type alt3 Alarm 3 type alt4 Alarm is assigned to auxiliary output. Alarm 4 type • These settings are used to select the type of alarms 1 through 4. Function Setting data Setting range Units Default value 0: No alarm function...
  • Page 258 "No alarm". Alarm 4 latch • When this setting is set to "ON", a latch function is added to the alarm function. Once an alarm goes on, the alarm output is held on Function until the power is turned off.
  • Page 259 Alarm is assigned to auxiliary output and Alarm 3 hysteresis alh4 alarm type is set to other than "No alarm". Alarm 4 hysteresis • These settings are used to enable hysteresis for alarms 1, 2, 3, and Function Default Setting data Setting range...
  • Page 260 Alarm output: Condition A Alarm output: Condition B • After changing the standby sequence restart setting, a software reset must be executed or the power turned off and on to make the change take effect. Setting range Units...
  • Page 261 Auxiliary output 3 non-exciting sb4n Auxiliary output 4 non-exciting • These settings are used to select the output state of alarms 1, 2, 3, and 4. Function • When close in alarm is selected, the state of the alarm output function is output without change.
  • Page 262: Display Adjustment Level

    8.13 Display adjustment level (l.4) 8.13 Display adjustment level This level contains settings for adjustment of the display contents, including selection of the "PV/SP" display screen, bar graph display item, display refresh period, monitor item level setting, and display scan. Power on Approximation...
  • Page 263 Section 8 Setting data spdp "PV/SP" display screen selection • This setting is used to select the order of display of the "PV/SP" display screen (Operation level). Function Setting range Units Default value Display in the order:"PV/SP/Bank" "PV/SP/MV" Setting Display in the order: "PV/SP/MV"...
  • Page 264 8.13 Display adjustment level (l.4) bart Bar graph display item E5AR • Use this setting to select the contents of the bar graph display of the E5AR. Function • The bar graph of the E5AR is 10 segments. Setting range...
  • Page 265: Communication Setting Level

    Section 8 Setting data monl Monitor item level setting • One of the following levels can be selected as the monitor item level setting: Input initial setting level, Control initial setting level, Control Function initial setting 2 level, Alarm setting level, Display adjustment level, Communication setting level, Advanced function setting level, Expansion control setting level.
  • Page 266: Communication Setting Level

    8.14 Communication setting level (l.5) 8.14 Communication setting level This level contains initial settings for communication such as protocol selection, communication unit No., and communication speed. Power on Approximation Adjustment Adjustment 2 Bank setting PID setting Operation level setting level...
  • Page 267 CompoWay/F mod: Modbus Setting u-no Communication Unit No. • After changing the communication unit No. setting, execute a software reset or turn the power off and on to make the change Function effective. Setting range Units Default value 0 to 99...
  • Page 268 8.14 Communication setting level (l.5) Communication data length Protocol is CompoWay/F • After changing the communication data length setting, execute a software reset or turn the power off and on to make the change Function effective. Setting range Units Default value...
  • Page 269 Section 8 Setting data sdwt Transmission wait time • After changing the transmission wait time setting, execute a software reset or turn the power off and on to make the change effective. Function Setting range Units Default value 0 to 99...
  • Page 270: Advanced Function Setting Level (L.adf)

    8.15 Advanced function setting level (l.adf) l.adf 8.15 Advanced function setting level This level includes setting initialization, PF key, and number of enabled channels settings. Power on Approximation Adjustment 2 Bank setting PID setting Adjustment Operation level setting level level...
  • Page 271 PF1 setting PF2 setting • This setting is used to assign functions to the PF1 and PF2 keys to enable them to be used as function keys. Function • When performing multi-channel control, the PF2 key functions as a CH key, and thus cannot be used as a function key ("PF2 setting"...
  • Page 272 1" through "Monitor/setting item 5" of each key must be Function set to the desired values among 0 to 19 below. • Each time a PF key is pressed, the display scrolls to the next monitor/setting item in order from "Monitor/setting item 1" to "Monitor setting item 5".
  • Page 273 Section 8 Setting data l.adf ch-n Number of enabled channels Multi-point input type • This setting is used to set the number of enabled channels when using multiple channels on a multi-point input type. Function Setting range Units Default value...
  • Page 274 8.15 Advanced function setting level (l.adf) l.adf cmov Move to calibration level This setting is used to move to calibration level. • Use this setting to enter the password to access calibration level. Function Setting range Units Default value -1999 to 9999 Setting ●...
  • Page 275: Expansion Control Setting Level (L.exc)

    Section 8 Setting data l.exc 8.16 Expansion control setting level This level includes advanced control settings such as operation after power ON, PID set auto selection, and position proportional settings. Power on Approximation Adjustment Adjustment 2 Bank setting PID setting...
  • Page 276 SP mode to local SP mode. Function • When remote SP tracking is enabled (ON), the value of the remote SP is transferred to the local SP. • When remote SP tracking is disabled (OFF), the local SP is not affected by the remote SP.
  • Page 277 PV dead band Position proportional type • This setting is used on a position proportional type to have PV = SP when the PV is within the PV dead band. Function • This function prevents unnecessary output when the PV is near the...
  • Page 278 Input 3 cold junction compensation cjc.4 Input type is thermocouple input Input 4 cold junction compensation • When the input type is thermocouple input, this setting is used to specify whether cold junction compensation is performed inside the Function controller or outside the controller.
  • Page 279 Setting l.exc pvtr PV tracking • This setting is used to have the local SP track the PV when in manual mode. Function • The setting prevents abrupt changes in the MV when switching from manual mode to auto mode.
  • Page 280 Manual MV initial value This setting is used to specify how the MV is output when switching from auto mode to manual mode. • When "Hold MV" is selected, the MV at the time of switching is held, after which it can be changed using "Manual MV" (Operation level).
  • Page 281 Section 8 Setting data l.exc orlm MV change rate limit mode • Use this setting to select Mode 0 or Mode 1 for the MV change rate limit. Function • When Mode 1 is selected, the MV change rate limit only functions with respect to increases in the MV.
  • Page 282 Operation at potentiometer input error Position proportional type Closed control • This setting is used to select whether control is stopped or changed to floating control when a potentiometer error occurs during closed Function control in position proportional control.
  • Page 283 Section 8 Setting data l.exc dost Disturbance overshoot adjustment function • This setting is used to enable or disable disturbance overshoot adjustment. Function Setting range Units Default value off: Disable off: Disable on : Enable Setting ● Related information Reference Reference "5.2 Control functions ■...
  • Page 284 Section 9 User calibration Setting data for user calibration ......... 9-2 User calibration..............9-4 Thermocouple input calibration ......... 9-5 Analog input calibration ............. 9-8 Resistance temperature input sensor calibration..... 9-10 Output calibration............. 9-12 Inspecting indicator accuracy .......... 9-13...
  • Page 285: Setting Data For User Calibration

    • To perform user calibration, enter "1201" in "Move to user calibration" in Special setting level. The controller will enter calibration mode and "adj" will appear in the display. • If the "Move to user calibration" setting does not appear, set "Initial setting protect" to "0" in Protect level and then move to Special setting level.
  • Page 286: Setting Data For User Calibration

    9.1 Setting data for user calibration If user calibration was performed on any of inputs 1 to 4 or outputs 1 to 6 following purchase of the controller, user calibration completion infor- mation will appear as shown below when you move to Calibration level.
  • Page 287: User Calibration

    Section 9 User calibration 9.2 User calibration The E5AR/ER is calibrated before shipment from the factory and thus there is normally no need for the user to calibrate the controller. In the event that user calibration is necessary, use the calibration functions for temperature input, analog input, and output that are provide in the controller.
  • Page 288: Thermocouple Input Calibration

    • Thermocouples are calibrated in two groups according to thermocouple type: Group 1 (input types 2, 4, 7, 8, 10, 14) and Group 2 (input types 3, 5, 6, 9, 11, 12, 13). • Do not cover the bottom of the thermocouple during calibration. Also, do not touch the input terminal or compensation wire.
  • Page 289 • For input types 3, 5, 6, 11,12, and 13: 22 mV Input types 3, 5, 6, 9, 11, 12, 13 Wait until the count in Display 2 is sufficiently stable and then press the D key. This tentatively saves the calibration data at this point.
  • Page 290 9. Wait until the count in Display 2 is sufficiently stable and then press the D key. This tentatively saves the calibration data at this point. 10. Press the key M to obtain the display at left. Note that this display will not str.i1 appear if not all of the required data has been tentatively saved.
  • Page 291: Analog Input Calibration

    E5AR/E5ER Input power supply 1. Connect the power supply. 2. Connect the STV and DMM to the input terminals of the analog input as shown above. Note that different input terminals are used for current input and voltage input. Make sure the connections are correct.
  • Page 292 8. Wait until the count in Display 2 is sufficiently stable and then press the D key. This tentatively saves the calibration data at this point. 9. Press the key M to obtain the display at left. Note that this display will not str.i1 appear if not all of the required data has been tentatively saved.
  • Page 293: Resistance Temperature Input Sensor Calibration

    • Input type 0: 390 l.cal • Input type 1: 160 Input type 1 p160.1 76288 l.cal 6. Wait until the count in Display 2 is sufficiently stable and then press the D key. This tentatively saves the calibration data at this point. 9-10...
  • Page 294 8. Wait until the count in Display 2 is sufficiently stable and then press the D key. This tentatively saves the calibration data at this point. 9. Press the M key to obtain the display at left. Note that this display will not str.i1 appear if not all of the required data has been tentatively saved.
  • Page 295: Output Calibration

    02a87 l.cal 7. Press the M key to obtain the display at left. Note that this display will not str.01 appear if not all of the required data has been tentatively saved, or if the data has not been changed.
  • Page 296: Inspecting Indicator Accuracy

    9.7 Inspecting indicator accuracy 9.7 Inspecting indicator accuracy • After calibrating input, be sure to inspect the indicator accuracy to verify that the input was calibrated correctly. • Run the E5AR/ER in the PV/SP state. • Check the upper limit, lower limit and mid-range limit of the indicator range (3 values).
  • Page 297 Section 9 User calibration ● Analog input • Preparations Connect as follows to the required devices. E5AR/E5ER Input power supply • Operation Set the STV output to the inspection value voltage or current. E5AR/E5ER Input power supply 9-14...
  • Page 298 10.2 Error messages ............... 10-3 10.3 Inferring causes from conditions (abnormal measured values) ........... 10-4 10.4 Inferring causes from conditions (abnormal control) ..10-5 10.5 Inferring causes from conditions (abnormal output) ..10-7 10.6 Inferring causes from conditions (communication problems) ..........10-8...
  • Page 299: Troubleshooting Checklist

    Section 10 Troubleshooting 10.1 Troubleshooting checklist If you encounter difficulty with the controller, use the following checklist to solve the problem. Check the operating state of the E5AR/ER as indicated by the display. Check the display Error messages and indicators are explained in "10.2 Error messages"...
  • Page 300: Error Messages

    10.2 Error messages 10.2 Error messages When an error occurs, Displays 1 and 2 show error messages. Refer to the following table to check the meaning of the message and how to solve the problem. Output state at error Display 1...
  • Page 301: Inferring Causes From Conditions (Abnormal Measured Values)

    The terminal plate of the E5AR/ER is exposed to strong air flow. Prevent air flow from blowing on the terminal plate. The input type switch setting is not correct. Set the input type switch to the correct setting for the input.
  • Page 302: Inferring Causes From Conditions (Abnormal Control)

    The heater has a broken wire or has deteriorated. Replace the heater. The heater has a low heat capacity. • Change to a heater with a high heat capacity. • If using two or more heaters, replace any heaters that have broken wires.
  • Page 303 Overlap band is mistakenly set as a dead band in Set to overlap band. heating/cooling control. ● Hunting occurs Check connections and settings as explained above in "Overshoot or undershoot occurs". Possible cause Solution The heat capacity of the heater is too large for the Use a heater with a heat capacity suitable for the heat capacity of the object of control.
  • Page 304: Inferring Causes From Conditions (Abnormal Output)

    The connected load exceeds the output rating. • Do not exceed the rating. • Repair in the event of a failure. A load power supply is not connected to a transistor Use a power supply suitable for the output rating output.
  • Page 305: Inferring Causes From Conditions

    E5AR/ER. response after sending a command. The interval between receiving a response and Allow an interval of at least 5 ms after receiving a sending the next command from the host system is response before sending a command.
  • Page 306 Appendix Specifications................A-2 Sensor input setting ranges · Indicator (control) ranges ....A-4 ASCII Codes ................A-5 Setting list ..................A-6 Setting data list ................A-30...
  • Page 307: Specifications

    Current input: 4 to 20 mA DC, 0 to 20 mA DC (including remote SP input) Voltage input: 1 to 5 V DC, 0 to 5 V DC, 0 to 10 V DC (including remote SP input) (Input impedance: 150 using current input, approx.
  • Page 308: Unit Performance Specifications

    Ambient temperature: 10 C to 23 C to 55 C Voltage range: 15% to +10% of rated voltage EU stands for "Engineering Units" and is regarded as the units after scaling. In the case of a temperature sensor, this is °C or °F.
  • Page 309: Sensor Input Setting Ranges · Indicator (Control) Ranges

    -300.0 to 1500.0 -305.0 to 955.0 -480.0.0 to 1680.0 resistance temperature Pt100 -150.00 to 150.00 -199.99 to 300.00 -180.00 to 180.00 -249.99 to 350.00 sensor -200.0 to 1300.0 -300.0 to 2300.0 -350.0 to 1450.0 -560.0 to 2560.0 -20.0 to 500.0 0.0 to 900.0...
  • Page 310: Ascii Codes

    ASCII Codes ASCII Codes Upper Lower SPACE ‘‘ & ‘ < ¥ >...
  • Page 311: Setting List

    The monitor and setting values can be specified for each channel, and addresses include a channel identifier. The addresses in the variable area map are for channel 1. To specify addresses of other channels on a multi-point input type, refer to the table below.
  • Page 312 Setting list...
  • Page 313 RSP input error Not occurred Occurred Not occurred Occurred Potentiometer error Exceeds display range Not occurred Occurred Not occurred Occurred Input error Free Control output (heat side) Control output (cool side) Free Free Alarm 1 Alarm 2 Alarm 3 Alarm 4...
  • Page 314 * Control output (heating) and control output (cooling) are respectively open output and close output during position proportional control. * Control output (heating) and control output (cooling) are normally OFF during linear output. * The control output heating type and/or control output cooling type is off when the corresponding output is pulse voltage output.
  • Page 315 Appendix A-10...
  • Page 316 Setting list A-11...
  • Page 317 Appendix A-12...
  • Page 318 Setting list A-13...
  • Page 319 Appendix A-14...
  • Page 320 Setting list A-15...
  • Page 321 Appendix A-16...
  • Page 322 Setting list A-17...
  • Page 323 Appendix A-18...
  • Page 324 Setting list A-19...
  • Page 325 Appendix A-20...
  • Page 326 Setting list A-21...
  • Page 327 Appendix A-22...
  • Page 328 Setting list A-23...
  • Page 329 Appendix A-24...
  • Page 330 Setting list A-25...
  • Page 331 Appendix A-26...
  • Page 332 Setting list A-27...
  • Page 333: Initialization Due To Setting Changes

    Appendix ■ Initialization due to setting changes Settings that are initialized when related settings are changed are shown in "Related settings that are initialized". Meaning of symbols: O: Initialized, : Not initialized, : Added channels initialized position point Decimal type...
  • Page 334 "Input type" ( on previous page). *3: Based on the PID set selection data, this is (setting upper limit + setting range 0.1) in the case of PV and (setting range 1.1) in the case of DV.
  • Page 335: Setting Data List

    0.01-99.99 ma p. 1 bnk.0 Move average count 0.0-100.0 C-DB: Dead band c-db 1 / 2 / 4 / 8 / 16 / 32 corl CORL: MV change rate limit -199.99-999.99 RSP: Remote SP monitor 0.00 (cooling) MAVP.2: Move average 2 ma p.2...
  • Page 336 ∗1 Position proportional type: 0.01-999.99 approximation 1 0.000 ∗2 Position proportional (floating control) type: 0.1-3999.9 Output 20 -1.999-9.999 ∗3 Analog type: -10% to 110% of scaling display range, with a maximum of-19999 to 99999 L key 1 second or more Control starts A-31...
  • Page 337 Floating: FLOAT / Closed: CLOSE float Transfer output 3 upper limit Scaling display value 1 + OFF / ON 1-99999 1 Temperature: SP lower limit + 1 to upper limit of CALB: Motor calibration calb DP: Decimal point position TRL.3: trl.3...
  • Page 338 0.02 Communication speed 0.01-99.99 BART: Bar graph display item bart 9.6 / 19.2 / 38.4 OFF / Deviation: 1 EU, 10 EU 20 EU, 100 EU / alt2 ALT2: Alarm 2 type MV (heating) Valve opening: O / LEN: 0-11...
  • Page 339 Appendix A-34...
  • Page 340 Control/Transfer output allocation .. 1-10, 8-46 Cooling coefficient ......3-8, 8-15 Bank change ........6-22, 7-22 Bank No..........8-13 Bank No. (Bits 0 to 2) ......5-30 Dead band ........3-8, 8-15 Bank setting level ......8-26, A-14 Decimal point position ......8-37 Banks ..........
  • Page 341 Expansion control setting level ..8-72, A-27 Location of input type switch ..... 1-8 Explanation of the keys ......1-6 Extraction of square root low-cut point ..8-24 Extraction of square root operations ..5-7 MANU (operation indicator) ....... 1-5 Manual ............ 4-29 Manual mode ..........
  • Page 342 Move to protect level ...... 6-26, 7-26 PID set automatic selection data ..... 8-74 Move to setting area 1 ....6-26, 7-26 PID set automatic selection hysteresis ... 8-74 Movement average enable ..... 8-50 PID Set No........5-10, 8-27 MV at error ........
  • Page 343 Specifications ..........A-2 Square root extraction enable ....8-51 Standard control ......1-9, 3-2, 4-13 Standard control with remote SP ..1-9, 4-13 Standby sequence ........5-26 Standby sequence restart ....... 8-57 Start display scan after power ON ..8-62 Status read (Communication/CompoWay/F) ....

This manual is also suitable for:

E5er

Table of Contents