Section 9 User Calibration

9.1 Parameters for User Calibration

• To perform user calibration, enter 1201 for the Move to Calibration Level parameter in the Advanced
Function Setting Level. The Controller will enter Calibration Mode and adj will be displayed on the
display.
• If the Move to Calibration Level parameter does not appear, set the Initial Setting Protection parameter
to 0 in the Protect Level and then move to Advanced Function Setting Level.
• Calibration is ended by turning OFF the power.
• The parameters for input calibration are shown below.
(The last digit of Display No. 1 shows the input number. The example below shows 1 for input 1. For
input 2, the display would show p390.2.)
adj
(Aging Timer)
Input Type (See note.)
PT100 (1) <0>
PT100 (2) <1>
p390.1
p160.1
p 20.1
p 40.1
str.i1
Note: < > The setting of the Input Type parameter is given in pointed brackets.

■ Output Calibration Parameters

9-2
K (1)<2>, J (1)<4>
K (2)<3>, J (2)<5>
E (1)<7>, L (1)<8>
T (2)<6>, U (2)<9>
N (1)<10>, W (1)<14>
R (2)<11>, S (2)<12>
B (2)<13>
1t53.1
2t22.1
a 20.1
1t-6.1
2t-6.1
a
bia5.1
bia5.1
The parameters for output calibration are shown below. The display
depends on the output type setting for each output.
(In the following example, the last digit of Display No. 1 shows 1 for
output 1. For output 2, this would be oa20.2.)
str.i1
oa20.1
oa 4.1
str.o1
4 to 20 mA <15>
1 to 5 V <17>
0 to 10 V <19>
0 to 20 mA <16>
0 to 5 V <18>
1V 5.1
2V10.1
1.1
1V 1.1
2V 1.1
(Input calibration values registered.)
For linear current output