Set the following items.
Setting field
Generation Type
Automatic Datalink Type
Power Up Run State
Automatic Data Link Area
Automatically Set Data Link Areas
If the following Controller Link Units/Support Boards are used, data links can be set
between a master and slaves using 1:N allocations. Any of the following four link
patterns can be used.
• Equality (same a previous automatic settings)
• Common type
• 1 to 1 type
• Chain type
Applicable Models:
• CS1W-CLK21-V1
• CS1W-CLK12-V1
• CS1W-CLK52-V1
• CJ1W-CLK21-V1
Note: Automatically set 1:N allocations are not possible for any models other than those
listed above. Refer to the Controller Link Unit Operation Manual for details.
4-4
4-4-2
Select Automatic.
Select Equality layout, Common type, 1 to 1 type, or Chain type to
set the data link areas. Refer to Automatically Set Data Link Areas
for details.
Select Start or Stop. Select Start to automatically start the data
links when power is turned ON without performing a specific startup
operation. If Start is set, it will be set in the Controller Link startup
node.
Set the area, start word, and
size for area 1.
Set the area, start word, and
size for area 2.
• 3G8F7-CLK21-V1(-EV1)
• 3G8F7-CLK12-V1(-EV1)
• 3G8F7-CLK52-V1(-EV1)
Automatically Set Data Links
Controller Link Automatic Setup
Setting
Set the status start word.
Set the nodes to
participate in the data
links.
4-45