3-2 Setting the Routing Tables
3-2-10 Transferring Routing Tables to a Network PLC through a Direct Serial Connection
Setting Example:
In this example, the tables are transferred to node address 2 in the Controller Link
network connected to the Controller Link Unit with unit number 1.
Computer (CX-Integrator)
Make the settings in the Switching the target PLC Dialog Box, as shown in the
following diagram.
7. Select Options – Transfer to PLC.
8. The following dialog box will be displayed to confirm the transfer. Verify that it is all
right to proceed with the transfer to the PLC, click the Yes Button.
Note
If routing tables were previously set in the target PLC, those tables will be overwritten
with the routing table that is being edited. Verify that the routing tables are being
written to the correct PLC.
9. The routing tables (local network table and relay network table) will be transferred
from the CX-Integrator to PLC2.
The following dialog box will be displayed after the transfer is completed.
3-30
• Controller Link or SYSMAC Link data link network:
The nodes connected to the network are listed in the pull-down list in the
Node Field. Select the destination node address from the pull-down list.
• Ethernet or DeviceNet network
Specify the destination node's node address directly in the Node Address
Field.
If a node address is specified and that node is connected even once, the
node will be added to the pull-down list in the Node Field the next time the
dialog box is opened.
Direct serial connection
Connect online with
network address = 0, and
node address = 0.
Unit number 1:
Controller Link Unit
Node address 2
Select the Connect to the PLC
on the Network Option.
Select 01 Controller Link from
the pull-down list.
Select 2.
Transfer destination
is this PLC.
Controller Link