Appendix E: Compliance with UL Standards
UL COMM FIRE
Optional
Encolsure Tamper Switch connected to 24-hour circuit
Yes
AC adapter lines in conduit (length limits apply)
Yes
AC adapter plugged into unswitched outlet
Yes
AC adapter plugged into dedicated branch circuit
Yes
Antenna cable in flexible conduit concealed
24-hour
Battery Backup requirement if using AC
Yes
Flexible or Rigid conduit required to protect connections #
All conductors of a fire alarm system shall be installed in metal raceway of the totally enclosed type or incorporated in a cable
having a metal armor or sheath; these metal elements must be grounded
INTELLICOM • 5403797 • REV A • 8/23
E-36