Supported Grid Types; Functionalities - Goodwe SDT Series User Manual

Grid-tied pv inverter
Hide thumbs Also See for SDT Series:
Table of Contents

Advertisement

User Manual V1.3-2024-01-25

3.3 Supported Grid Types

TN-S
L1
L2
L3
N
PE
PE
Inverter
IT
L1
L2
L3
PE
Inverter

3.4 Functionalities

AFCI (Optional)
AFCI functionality is to detect the DC electric arc fault. If there is any, the inverter is able to
enable self-protection automatically.
Reasons why electric arcs occur:
• Damaged DC connectors or poor connected DC connectors in PV system.
• Wrong connected or broken cables.
• Aging connectors and cables.
Method to detect electric arcs:
• When the inverter detects an electric arc, users can check the fault via LCD or SolarGo App.
• When electric arc is detected, the inverter alarms and shuts down for protection. After
waiting around 60 S, the inverter will resume grid connection automatically. If the shutdown
protection repeats , please check the inverter wiring to eliminate the electric arc.For details,
refer to SolarGo App User Manual.
TN-C
L1
L2
L3
PEN
PE
Inverter
7
03 Product Introduction
TN-C-S
L1
L2
L3
N
PE
PE
Inverter
TT
L1
L2
L3
N
PE
Inverter