Goodwe ES Series User Manual

Goodwe ES Series User Manual

Hybrid inverter
Hide thumbs Also See for ES Series:

Advertisement

Quick Links

User Manual
Hybrid Inverter
ES Series
5.0-11.4kW G2(US)
AC-Coupled Inverter
SBP Series
5.0-11.4kW G2(US)
V1.0-2022-07-30

Advertisement

Table of Contents
loading

Summary of Contents for Goodwe ES Series

  • Page 1 User Manual Hybrid Inverter ES Series 5.0-11.4kW G2(US) AC-Coupled Inverter SBP Series 5.0-11.4kW G2(US) V1.0-2022-07-30...
  • Page 2 CONTENT User Manual V1.0-2022-07-30 Trademarks and other GOODWE trademarks are trademarks of GoodWe Technologies Co.,Ltd. All other trademarks or registered trademarks mentioned in this manual are owned by GoodWe Technologies Co.,Ltd. NOTICE The information in this user manual is subject to change due to product updates or other reasons.
  • Page 3: Table Of Contents

    CONTENT User Manual V1.0-2022-07-30 CONTENT 1 About This Manual ���������������������������������������������������������������������������� 1 1.1 Applicable Model ........................1 1.2 Target Audience ........................1 1.3 Symbol Definition ........................2 1.4 Updates ............................2 2 IMPORTANT SAFETY INSTRUCTIONS �������������������������������������������������� 3 2.1 General Safety ..........................3 2.2 PV String Safety ........................3 2.3 Inverter Safety ..........................4 2.4 Battery .............................5 2.5 Personnel Requirements ......................5...
  • Page 4 CONTENT User Manual V1.0-2022-07-30 6.3 Opening the wiring cover ...................... 36 6.4 Connecting the DC Input Cable(PV) ..................36 6.5 Connecting the battery cable ....................38 6.6 Connecting the AC Cable ....................... 39 6.7 Connecting the EV cables ...................... 40 6.8 Communication ........................
  • Page 5: About This Manual

    All the installers and users have to be familiar with the product features, functions, and safety precautions. This manual is subject to update without notice. For more product details and latest documents, please visit https://en.goodwe.com. 1.1 Applicable Model...
  • Page 6: Symbol Definition

    01 About This Manual User Manual V1.0-2022-07-30 1.3 Symbol Definition Different levels of warning messages in this manual are defined as follows: DANGER Indicates a high-level hazard that, if not avoided, will result in death or serious injury. WARNING Indicates a medium-level hazard that, if not avoided, could result in death or serious injury. CAUTION Indicates a low-level hazard that, if not avoided, could result in minor or moderate injury.
  • Page 7: Important Safety Instructions

    • Strictly follow the installation, operation, and configuration instructions in this manual. The manufacturer shall not be liable for equipment damage or personal injury if you do not follow the instructions. For more warranty details, please visit: https://en.goodwe.com/ warranty 2.2 PV String Safety DANGER Connect the DC cables of the inverter to the delivered DC terminals.
  • Page 8: Inverter Safety

    User Manual V1.0-2022-07-30 02 Safety Precaution 2.3 Inverter Safety WARNING • The voltage and frequency at the connecting point should meet the on-grid requirements. • Additional protective devices like circuit breakers or fuses are recommended on the AC side. Specification of the protective device should be at least 1.25 times the AC rated output current.
  • Page 9: Battery

    User Manual V1.0-2022-07-30 02 Safety Precaution 2.4 Battery WARNING • The battery used with the inverter shall be approved by the inverter manufacturer. The approved battery list can be obtained through the official website. • Before installations, read through the corresponding battery's User Manual to learn about the product and the precautions.
  • Page 10: Product Introduction

    The power generated in the PV system can be used, stored in the battery, output to the Utility Grid, etc. Model This manual applies to the listed inverters below: ES Series: Hybrid Inverter SBP Series: AC-Coupled Inverter • GW5000-ES-US20 • GW5000-SBP-US20 •...
  • Page 11: Application Scenarios

    03 Product Introduction User Manual V1.0-2022-07-30 Supported Grid Types The inverter supports 120/240V split phase Grid. 120V 240V 120V 3.2 Application Scenarios WARNING • PV system is not suitable to connect equipment that relies on a stable power supply, such as: medical equipment to sustain life.
  • Page 12 03 Product Introduction User Manual V1.0-2022-07-30 Strictly follow below requirements to realize anti reverse current: WARNING The anti reverse current functionality can be realized when the inverter are used together with ABD or Smart Meter. The application scenarios for the inverter includes: self consumption, Whole Home Backup System and microgrid.
  • Page 13 Description PV string • PV String: only for ES series. & rapid • Rapid shutdown module: only for ES series. Configure the RSD shutdown module externally to realize RSD functionality. You can purchase module the RSD module from the inverter manufacturer or select RSD-D- XX or Tigo TS4 series from AP Systems.
  • Page 14 03 Product Introduction User Manual V1.0-2022-07-30 Self Consumption System(AC-Coupled Scenarios) Emergency stop button Battery Battery breaker Coupled Smart meter Inverter Utility meter Utility Grid breaker Electric vehicle Grid- Tied PV Inverter AC breaker PV String Main power Household Circuit distribution unit loads Breaker Power cable...
  • Page 15 Description PV string • PV String: only for ES series. & rapid • Rapid shutdown module: only for ES series. Configure the RSD shutdown module externally to realize RSD functionality. You can purchase the module RSD module from the inverter manufacturer or select RSD-D-XX or Tigo TS4 series from AP Systems.
  • Page 16 03 Product Introduction User Manual V1.0-2022-07-30 Parts Description Generator The inverter supports to connect with generators. Configure it according to users’ demanding. An fully automatic split-phase generator is recommended. Automatic When the system is configured with a generator, it shall also use an Transfer automatic transfer switch.
  • Page 17 03 Product Introduction User Manual V1.0-2022-07-30 Emergency stop button Battery Battery breaker ABD box Coupled Inverter Utility meter Utility Grid Electric vehicle Grid- Tied PV Inverter AC breaker PV String Main power Load Household distribution unit Breaker loads Power cable Signal cable Parts Description...
  • Page 18: Working Mode

    03 Product Introduction User Manual V1.0-2022-07-30 3.3 Working Mode 3�3�1 System working mode Economic mode NOTICE • Select Economy mode only when it meets the local laws and regulations, e.g., whether the grid is allowed to charge the battery. If not, do not use this mode.
  • Page 19 03 Product Introduction User Manual V1.0-2022-07-30 Self consumption mode NOTICE • For solar power, consider self consumption mode as priority: the excess power charges the battery in day time; the battery supplies power to the load when there is no solar power generated at night.
  • Page 20 03 Product Introduction User Manual V1.0-2022-07-30 Back-up mode NOTICE • The back-up mode is mainly applied to the scenario where the grid is unstable and there is an important load. When the grid is power off, the inverter turns to off-grid mode to supply power to the load;...
  • Page 21: Ev Charger Working Mode

    03 Product Introduction User Manual V1.0-2022-07-30 3.3.2 EV Charger Working Mode NOTICE • The power to charge the EV may come from the PV system, the battery or the grid. The specific power source is determined by the system working mode. •...
  • Page 22: Inverter Operation Mode

    03 Product Introduction User Manual V1.0-2022-07-30 3.3.3 Inverter operation mode Waiting mode Off-grid mode Self-check mode Grid-Tied mode Fault mode Parts Description Waiting Waiting stage after the inverter is powered on. mode • When the conditions are met, it enters the self-check mode. •...
  • Page 23: Functionality

    03 Product Introduction User Manual V1.0-2022-07-30 3.4 Functionality EV Charger • The inverter has a built-in connection port for charging EV. This port is compatible with the J1772 (Type1) specification and meets the AC Level 2 standard. It is applicable to EVs with J1772 (Type1) sockets.
  • Page 24 03 Product Introduction User Manual V1.0-2022-07-30 Load Control The inverter reserves a dry contact controlling port, which supports connecting additional contactors to enable/disable the load. The load control methods are as follows: • Time control: set the time to enable/disable the load, and the load will be turned on or off automatically within the setting time period.
  • Page 25: Appearance

    03 Product Introduction User Manual V1.0-2022-07-30 3.5 Appearance 3.5.1 Parts Back view of ES inverter Back view of SBP inverter Parts Description Restarting button for the Restart the communication module communication module LED Indicator Refers to the inverter's working status Port for WiFi/BT antenna To connect with WiFi/BT antenna Port for 4G antenna...
  • Page 26: Dimension

    03 Product Introduction User Manual V1.0-2022-07-30 3.5.2 Dimension 860mm 33.86in 3.5.3 Indicators Indicator Status Explanation The inverter is power on and in the standby mode. The inverter is starting up and in the self-check mode. The inverter is in normal operation under grid-tied or off- grid modes.
  • Page 27: Nameplate

    03 Product Introduction User Manual V1.0-2022-07-30 3.5.4 Nameplate The nameplate is for reference only. GW trademark, product type, and product model Technical parameters Safety symbols and certification marks Contact information and serial number...
  • Page 28: Check And Storage

    04 Check and Storage User Manual V1.0-2022-07-30 Check and Storage 4.1 Check Before Receiving Check the following items before receiving the product. 1. Check the outer packing box for damage, such as holes, cracks, deformation, and others signs of equipment damage. Do not unpack the package and contact the supplier as soon as possible if any damage is found.
  • Page 29: Storage

    04 Check and Storage User Manual V1.0-2022-07-30 4.3 Storage If the equipment is not to be installed or used immediately, please ensure that the storage environment meets the following requirements: 1. Do not unpack the outer package or throw the desiccant away. 2.
  • Page 30: Installation

    05 Installation User Manual V1.0-2022-07-30 5 Installation 5.1 Installation Requirements Installation Environment Requirements 1. Do not install the equipment in a place near flammable, explosive, or corrosive materials. 2. Do not install the equipment in a place that is easy to touch, especially within children’s reach. High temperature exists when the equipment is working.
  • Page 31 User Manual V1.0-2022-07-30 05 Installation ALT: 3000m 9842ft -31°F~140°F TYPE 4X (-35°C~60°C) 0%~95%RH Mounting Support Requirements • The mounting support shall be nonflammable and fireproof. • Install the equipment on a surface that is solid enough to bear the inverter weight. •...
  • Page 32 05 Installation User Manual V1.0-2022-07-30 Installation Tool Requirements The following tools are recommended when installing the equipment. Use other auxiliary tools on site if necessary. Goggles RJ45 crimping Safety shoes Safety gloves Dust mask tool Diagonal pliers Vacuum cleaner Wire stripper Hammer drill Heat gun M3/M5...
  • Page 33: Inverter Installation

    User Manual V1.0-2022-07-30 05 Installation 5.2 Inverter Installation 5.2.1 Moving the Inverter CAUTION • Operations such as transportation, turnover, installation and so on must meet the requirements of the laws and regulations of the country or region where it is located. •...
  • Page 34 05 Installation User Manual V1.0-2022-07-30...
  • Page 35: Electrical Connection

    06 Electrical Connection User Manual V1.0-2022-07-30 Electrical Connection 6.1 Safety Precaution DANGER INSTRUCTIONS PERTAINING TO A RISK OF FIRE OR ELECTRIC SHOCK • All operations, cables and parts specification during the electrical connection shall be in compliance with local laws and regulations. •...
  • Page 36: Preparations Before Installation

    06 Electrical Connection User Manual V1.0-2022-07-30 6.2 Preparations before Installation 6.2.1 Terminal introduction WARNING • The watertight conduit needs to be provided by the user, and the specification of the watertight conduit used shall match the specification of the waterproof plug. •...
  • Page 37: Cable Specification

    06 Electrical Connection User Manual V1.0-2022-07-30 6.2.2 Cable Specification Generator EMS Device Router conditioner Base station ABD box PV string & Emergency Battery Smart Electric vehicle ABD box rapid shutdown stop button meter module Power cable Signal cable Wireless Signal cable Port Screen print Explanation...
  • Page 38 06 Electrical Connection User Manual V1.0-2022-07-30 Port Screen print Explanation Load control port LOAD CNTL • Connect with the load controlling cable • Recommended cable specification: 24-16AWG, communication ables for outdoors which are satisfying UL2919, CM/CMG(NEC type) or CMH (CSA type) standards USB COM Port U DISK The inverter supports connecting with U Disk to...
  • Page 39 06 Electrical Connection User Manual V1.0-2022-07-30 Port Screen print Explanation LAN COM Port • Connect with the router's communication cable, then connect with the monitoring platform on the server • Recommended cable specification: CAT 5E outdoor shielded network cable and shielded RJ45 connector SIM card 4G SIM...
  • Page 40: Opening The Wiring Cover

    06 Electrical Connection User Manual V1.0-2022-07-30 6.3 Opening the wiring cover NOTICE • The wrench for opening the inverter lower case cover is distributed with the inverter. After removing the inverter lower case cover, please keep the wrench and fastening screws properly for later use.
  • Page 41 06 Electrical Connection User Manual V1.0-2022-07-30 DANGER INSTRUCTIONS PERTAINING TO A RISK OF FIRE OR ELECTRIC SHOCK • Do not connect one PV string to more than one inverter at the same time. Otherwise, it may cause damage to the inverter. •...
  • Page 42: Connecting The Battery Cable

    06 Electrical Connection User Manual V1.0-2022-07-30 6.5 Connecting the battery cable DANGER INSTRUCTIONS PERTAINING TO A RISK OF FIRE OR ELECTRIC SHOCK • The battery used with the inverter shall be approved by the inverter manufacturer. The approved battery list can be obtained through the official website. •...
  • Page 43: Connecting The Ac Cable

    06 Electrical Connection User Manual V1.0-2022-07-30 6.6 Connecting the AC Cable WARNING Do not connect loads between the inverter and the AC switch directly connected to the inverter. NOTICE • Install one AC circuit breaker for each inverter. Multiple inverters cannot share one AC circuit breaker.
  • Page 44: Connecting The Ev Cables

    06 Electrical Connection User Manual V1.0-2022-07-30 6.7 Connecting the EV cables DANGER INSTRUCTIONS PERTAINING TO A RISK OF FIRE OR ELECTRIC SHOCK • Before installations, read through the EV’s user manual to learn about the product and the precautions. Strictly follow its requirements. •...
  • Page 45: Communication

    06 Electrical Connection User Manual V1.0-2022-07-30 6.8 Communication NOTICE Make sure that the communication device is connected to the right COM port. Route the communication cable far away from any interference source or power cable to prevent the signal from being influenced. 6.8.1 Connecting the Communication Cable (Use pin connectors) The wiring of the battery, meter, EMS, dry contact, E-stop switch I/Ocommunication cables are the same.
  • Page 46 06 Electrical Connection User Manual V1.0-2022-07-30 NOTICE • Connect with the meter for anti reverse current function in the system when there is no ABD box. • Pay attention to CT connecting direction during the meter cable connection. It will display CT reverse fault on the inverter if it is the opposite direction.
  • Page 47: Connecting The Communication Cable (For Rj45 Crystal Terminal Connection)

    06 Electrical Connection User Manual V1.0-2022-07-30 The wiring of the generator and load control communication cables are the same. Below is taking the generator communication cable connection as an example. 20mm (0.79in) 20mm (0.79in) 6.8.2 Connecting the Communication Cable (for RJ45 crystal terminal connection) The wiring of ABD/MPD, LAN and parallel communication cables are the same.
  • Page 48: Installing The Sim Card (Optional)

    06 Electrical Connection User Manual V1.0-2022-07-30 6.8.3 Installing the SIM card (optional) NOTICE • SIM cards shall be installed for inverters supporting 4G. The SIM service providers can be obtained by scanning the following QR. • SIM cards shall be prepared by customers. It is recommended to use SIM cards with standard size(dimension: 25mm×15mm, capacity is ≥64KB) and more than 150M monthly data package .
  • Page 49: Equipment Commissioning

    User Manual V1.0-2022-07-30 07 Equipment Commissioning 7 Equipment Commissioning 7.1 Check Before Power ON Check Item The product is firmly installed at a clean place that is well-ventilated and easy-to operate. The PE, DC input, AC output, and communication cables are connected correctly and securely.
  • Page 50: System Commissioning

    08 System Commissioning User Manual V1.0-2022-07-30 System Commissioning 8.1 Indicators and Buttons Indicator Status Explanation The inverter is power on and in the standby mode. The inverter is starting and in the self-check mode. The inverter is in normal operation under grid-tied or off- grid modes.
  • Page 51: Setting Inverter's Parameters Via Pv Master App

    3. Maintain the equipment. 4. Update the software version of products. For more details, refer to the PV Master User Manual. Scan the QR code or visit https:// en.goodwe.com/Ftp/EN/Downloads/User%20Manual/GW_PV%20Master_User%20Manual-EN. to get the user manual. PV Master App PV Master User Manual 8.3 Monitoring via SEMS Portal...
  • Page 52: Maintenance

    09 Maintenance User Manual V1.0-2022-07-30 9 Maintenance 9.1 Power Off the Inverter DANGER INSTRUCTIONS PERTAINING TO A RISK OF FIRE OR ELECTRIC SHOCK • Power off the inverter before operations and maintenance. Otherwise, the inverter may be damaged or electric shocks may occur. •...
  • Page 53: Troubleshooting

    09 Maintenance User Manual V1.0-2022-07-30 9.4 Troubleshooting Perform troubleshooting according to the following methods. Contact the after-sales service if these methods do not work. Collect the information below before contacting the after-sales service, so that the problems can be solved quickly. 1.
  • Page 54 09 Maintenance User Manual V1.0-2022-07-30 Fault Cause Solutions 1. If the problem occurs occasionally, the utility grid may be abnormal temporarily. The inverter will recover automatically after detecting that the utility grid is normal. 2. If the problem occurs frequently, check whether the grid voltage is within the The grid voltage is Grid Rapid...
  • Page 55 09 Maintenance User Manual V1.0-2022-07-30 Fault Cause Solutions 1. If the problem occurs occasionally, the utility grid may be abnormal temporarily. The inverter will recover automatically after detecting that the utility grid is normal. The moving 2. If the problem occurs frequently, check average of grid whether the grid voltage is within the Grid 10min...
  • Page 56 09 Maintenance User Manual V1.0-2022-07-30 Fault Cause Solutions 1. If the problem occurs occasionally, the utility grid may be abnormal temporarily. The inverter will recover automatically after detecting that the utility grid is normal. 2. If the problem occurs frequently, check Utility grid whether the grid frequency is within the exception.
  • Page 57 09 Maintenance User Manual V1.0-2022-07-30 Fault Cause Solutions The utility grid is disconnected. The utility grid 1. Check whether the utility grid is is disconnected disconnected. Anti-islanding according to the 2. Contact the dealer or the after-sales safety regulations, service. but the grid voltage is maintained due to the loads.
  • Page 58 09 Maintenance User Manual V1.0-2022-07-30 Fault Cause Solutions 1. The PV string is short-circuited 1. Check whether the resistance of the PV to PE. string to PE exceeds 50kΩ. If no, check the 2. The PV system short circuit point. Low Insulation is in a moist 2.
  • Page 59 09 Maintenance User Manual V1.0-2022-07-30 Fault Cause Solutions Disconnect the AC output switch and DC The sampling AC HCT Check input switch, then connect them 5 minutes of the AC HCT is abnormal later. Contact the dealer or the after-sales abnormal.
  • Page 60 09 Maintenance User Manual V1.0-2022-07-30 Fault Cause Solutions 1. The inverter is installed in a 1. Check the ventilation and the ambient place with poor temperature at the installation point. ventilation. 2. If the ventilation is poor or the ambient Cavity 2.
  • Page 61: Routine Maintenance

    09 Maintenance User Manual V1.0-2022-07-30 9.5 Routine Maintenance WARNING • Make sure that the inverter is powered off. • Wear proper PPE before any operations. Maintaining Item Maintaining Method Maintaining Period Check the heat sink, air intake, and air System Clean Once 6-12 months outlet for foreign matter or dust.
  • Page 62: Technical Parameters

    User Manual V1.0-2022-07-30 10 Technical Parameters 10 Technical Parameters 10.1 ES Inverter Parameters Technical Data GW5000-ES- GW6000- GEH7.6-1U- GEH9.6-1U- GEH11.4-1U- US20 ES-US20 US20 US20 US20 Battery Input Data Battery Type Li-Ion Li-Ion Li-Ion Li-Ion Li-Ion Nominal Battery Voltage Battery Voltage Range (V) 80~495 80~495 80~495...
  • Page 63 User Manual V1.0-2022-07-30 10 Technical Parameters Technical Data GW5000-ES- GW6000- GEH7.6-1U- GEH9.6-1U- GEH11.4-1U- US20 ES-US20 US20 US20 US20 Nominal Apparent Power 5,000 6,000 7,600 9,600 11,400 from Utility Grid (VA) Max. Apparent Power from 5,000 6,000 7,600 9,600 11,400 Utility Grid (VA) Max.
  • Page 64 User Manual V1.0-2022-07-30 10 Technical Parameters Technical Data GW5000-ES- GW6000- GEH7.6-1U- GEH9.6-1U- GEH11.4-1U- US20 ES-US20 US20 US20 US20 Maximum Output Overcurrent Protection Without EV Charger (A) Maximum Output Overcurrent Protection With EV Charger (A) Type of Voltage (a.c. or a.c. a.c.
  • Page 65 User Manual V1.0-2022-07-30 10 Technical Parameters Technical Data GW5000-ES- GW6000- GEH7.6-1U- GEH9.6-1U- GEH11.4-1U- US20 ES-US20 US20 US20 US20 Max. Battery to AC 97.0% Efficiency MPPT Efficiency 99.9% Protection PV String Current Integrated Monitoring PV Insulation Resistance Integrated Detection Residual Current Integrated Monitoring PV Reverse Polarity...
  • Page 66 User Manual V1.0-2022-07-30 10 Technical Parameters Technical Data GW5000-ES- GW6000- GEH7.6-1U- GEH9.6-1U- GEH11.4-1U- US20 ES-US20 US20 US20 US20 Max. Operating Altitude (ft) 9842ft (3000m) Cooling Method Natural Convection User Interface LED, APP LED, APP LED, APP LED, APP LED, APP Communication with BMS RS485, RS485,...
  • Page 67 User Manual V1.0-2022-07-30 10 Technical Parameters Technical Data GW5000-ES- GW6000- GEH7.6-1U- GEH9.6-1U- GEH11.4-1U- US20 ES-US20 US20 US20 US20 Country of Manufacture China General Data UL1741 SB, California Rule 21, HECO Rule 14, IEEE 1547, IEEE Grid Standards 1547.1 Safety Regulation UL 1741, CSA 22.2 No.
  • Page 68: Sbp Inverter Parameters

    User Manual V1.0-2022-07-30 10 Technical Parameters 10.2 SBP Inverter Parameters Technical Data GW5000- GW6000- GW7600- GW9600- GW11K4- SBP-US20 SBP-US20 SBP-US20 SBP-US20 SBP-US20 Battery Input Data Battery Type Li-Ion Li-Ion Li-Ion Li-Ion Li-Ion Nominal Battery Voltage (V) Battery Voltage Range (V) 80~495 80~495 80~495...
  • Page 69 User Manual V1.0-2022-07-30 10 Technical Parameters Technical Data GW5000- GW6000- GW7600- GW9600- GW11K4- SBP-US20 SBP-US20 SBP-US20 SBP-US20 SBP-US20 Max. AC Current From Utility Grid Without EV 20.8 25.0 31.7 40.0 47.5 Charger (A) Max. AC Current From Utility Grid With EV Charger 40.0 40.0 40.0...
  • Page 70 User Manual V1.0-2022-07-30 10 Technical Parameters Technical Data GW5000- GW6000- GW7600- GW9600- GW11K4- SBP-US20 SBP-US20 SBP-US20 SBP-US20 SBP-US20 Maximum Output Overcurrent Protection Without EV Charger (A) Maximum Output Overcurrent Protection With EV Charger (A) Nominal Output Voltage 240/120 240/120 240/120 240/120 240/120 Nominal Output...
  • Page 71 User Manual V1.0-2022-07-30 10 Technical Parameters Technical Data GW5000- GW6000- GW7600- GW9600- GW11K4- SBP-US20 SBP-US20 SBP-US20 SBP-US20 SBP-US20 Max. Operating Altitude (ft) 9842ft (3000m) Cooling Method Natural Convection User Interface LED, APP LED, APP LED, APP LED, APP LED, APP Communication with BMS RS485, RS485,...
  • Page 72 User Manual V1.0-2022-07-30 10 Technical Parameters Technical Data GW5000- GW6000- GW7600- GW9600- GW11K4- SBP-US20 SBP-US20 SBP-US20 SBP-US20 SBP-US20 General Data UL1741 SB, California Rule 21, HECO Rule 14, IEEE 1547, IEEE Grid Standards 1547.1 Safety Regulation UL 1741, CSA 22.2 No. 107.1, UL 1998, UL1699B FCC part15 CLASS B *1: Battery discharge/charge power limited by voltage.
  • Page 73: Technical Parameters For Ev Charger

    User Manual V1.0-2022-07-30 10 Technical Parameters 10.3 Technical Parameters for EV Charger Technical Data EV Charger AC Output Data Charging Level AC Level 2 Nominal AC Power Output (W) 9600 Nominal AC Frequency(Hz) Maximum Continuous Output Current (A) EV Charger Configuration & Indicator APP (WiFi, Bluetooth) EV Charger Cable Length* 7.6m...
  • Page 74: Appendix

    11 Index User Manual V1.0-2022-07-30 11 Appendix 11.1 Inverter Parameter Precision For parameter, which used in grid support and protection function, adjustable requirement of CA Rule 21, HECO 14H and IEEE1547, the relevant explanations and setting methods can obtain by reading, <Parameter Adjustable Method Of Grid Support Utility Interactive Inverter>, the document can be obtained by contacting the after-sales.
  • Page 75 User Manual V1.0-2022-07-30 11 Appendix Official Website GoodWe Technologies Co.,Ltd. No. 90 Zijin Rd., New District, Suzhou, 215011, China www.goodwe.com service@goodwe.com Contact Information...