The electricity meter is connected as follows:
Note: Meter type: DDSU666 (CHINT)
Export limitation setting:
Settings
On-Grid Parm
After enabling Export Control, the inverter will respond to the export power control in real time according
to the CT or meter to control the active power export level. By default, the Export Control function is
disabled.
Soft Limit:
The inverter export power is limited to below the set Soft Limit value. If the CT or meter communication is
lost, the inverter export power is limited to the set Soft Limit value.
Hard Limit:
After setting the Hard Limit value, if the Soft Limit time requirement is not met or if the CT or meter
communication is lost, the inverter will also disconnect from the grid and shut down.
Generation limitation setting:
Settings
On-Grid Parm
After enabling the Generation Control, the inverter will response to the generation power control in real
time according to the CT or meter to control the apparent power level. By default, the Generation Control
function is disabled.
Soft Limit:
The inverter generation power is limited to the set Soft Limit value. If the CT or meter communication is
Export Control
Generation
Control
27
Soft Limit
xxxxxW
Hard Limit
xxxxxW
xxxxxVA
Soft Limit
Hard Limit
xxxxxVA