Installer Manual
FORCE S SERIES
GRID-TIED INVERTERS
This guide describes how to use and install Energizer Solar Inverters.
To prevent improper operation before use, please carefully read this manual.

Advertisement

Table of Contents
loading

Summary of Contents for Energizer FORCE S Series

  • Page 1 Installer Manual FORCE S SERIES GRID-TIED INVERTERS This guide describes how to use and install Energizer Solar Inverters. To prevent improper operation before use, please carefully read this manual.
  • Page 2: Table Of Contents

    Table of Contents Important Notes ................................1 Scope ..................................1 Target Group ..............................1 Symbols Used ..............................1 Symbols Explanation ............................1 Safety ....................................2 Appropriate Usage ............................2 PE Connection and Leakage Current ..................... 3 Surge Protection Devices (SPDs) for PV Installation ...............3 About Product ................................4 About Inverter ..............................
  • Page 3: Important Notes

    1. Important Notes 1.1 Scope This manual describes the assembly, installation, commissioning, maintenance and troubleshooting of the following model(s) of Energizer Force S Series products: Energizer Force 7S Energizer Force 8S Energizer Force 9S Energizer Force 10S Energizer Force 10.5S Note: Please keep this manual where it will be accessible at all times.
  • Page 4: Safety

    Danger. Risk of electric shock! Danger to life due to high voltage. There is residual voltage in the inverter which needs 5 min to discharge. Wait 5 min before you open the upper lid or the DC lid. Read the manual. Product should not be disposed as household waste.
  • Page 5: Pe Connection And Leakage Current

    PV array, cables or inverter (DC). The RCD in the Energizer Force S Series inverter can detect leakage on the DC side. There are 2 trip thresholds for the RCD as required by the DIN VDE 0126-1-1 standard. A low threshold is used to protect against rapid changes in leakage typical of direct contact by people.
  • Page 6: About Product

    Induced surges are the most likely cause of lightning damage in majority or installations, especially in rural areas where electricity is usually provided by long overhead lines. Surges may impact on both the PV array conduction and the AC cables leading to the building. Specialists in lightning protection should be consulted during the end use application.
  • Page 7: Terminals Introduction

    3.3 Terminals Introduction Item Description DC Switch (Optional) WiFi/GPRS/4G/USB Waterproof Lock Valve Communication Port AC Connector Grounding Screw Note: Only authorized personnel are permitted to set the connection. 3.4 Dimensions...
  • Page 8: Technical Data

    No. of MPP trackers Strings per MPP tracker Max. Inverter backfeed current to the array (mA) 4.2 AC Output Energizer Energizer Energizer Energizer Energizer Force Model Force 7S Force 8S Force 9S Force 10S 10.5S Norminal AC power [W] 7000...
  • Page 9: Efficiency, Safety And Protection

    4.3 Efficiency, Safety and Protection Energizer Energizer Energizer Energizer Energizer Model Force 7S Force 8S Force 9S Force 10S Force 10.5S MPPT efficiency 99.00% 99.00% 99.00% 99.00% 99.00% Euro efficiency 97.40% 97.40% 97.40% 97.40% 97.40% Max. efficiency 97.80% 97.80% 97.80% 97.80%...
  • Page 10: Installation

    5. Installation 5.1 Packing List Please un-pack the box, check and make sure you received all items as listed below before installation (excluding optional items): Object Quantity Description Object Quantity Description Inverter Communication connector Bracket Product manual DC connector (F/M) Quick installation guide AC connector CT (optional)
  • Page 11: Installation Space Required

    5.3 Installation Space Required Position Min Size Left 300mm 300mm Right 300mm 300mm Bottom 300mm Front 5.4 Tools Required • Manual wrench; • Electric drill (drill bit set 8mm); • Crimping pliers; • Stripping pliers; • Screwdriver. 5.5 Installation Steps Step 1: Fix the bracket on the wall Choose the place you want to install the inverter.
  • Page 12: Wiring Steps

    Insert the expansion tubes into the holes and tighten them. Install the bracket with the expansion screws. Step 2: Match the inverter with wall bracket Mount the inverter to the bracket. Secure the inverter with the M5 screw and washer. 5.6 Wiring Steps Step 1: PV String Connection This series inverters can be connected with 2-strings of PV modules.
  • Page 13 Note: PV connection mode below is not allowed. Step 2: DC Wiring • Turn off the DC switch. • Choose 12 AWG wire to connect the PV module. • Trim 6mm of insulation from the wire end. • Separate the DC connector as below. •...
  • Page 14 • Grid Connection This series inverters are designed for single-phase grid. Voltage range is 220/230/240V; frequency is 50/60Hz. Other technical requests should comply with the requirement of the local public grid. Energizer Energizer Energizer Energizer Energizer Model (kW) Force 7S...
  • Page 15: Earth Connection

    • Push the threaded sleeve into the socket, tighten up the cap on the terminal. • Push the threaded sleeve to connection terminal until both are locked tightly on the inverter. • Remove the AC connector, press the bayonet out of the slot with a small screwdriver or the unlock tool and pull it out, or unscrew the threaded sleeve, then pull it out.
  • Page 16 • WiFi/LAN/GPRS (optional) The inverter has an interface for WiFi/LAN/GPRS devices that allow this device to collect information from inverter; including inverter working status, performance etc., and update that information to monitoring platform (the WiFi/LAN/GPRS device is available to purchase from your local supplier). Connection steps: For GPRS device: Please insert the SIM Card (please refer to the GPRS product manual for more details).
  • Page 17 Note! For a precise reading and control of power, a meter can be used instead of a CT. If the CT is fitted in the wrong orientation, anti-backflow function will fail. • S485/Meter RS485 RS485 is a standard communication interface which can transmit the real time data from inverter to PC or other monitoring devices.
  • Page 18 DRM0 setting Short press the touch key to switch display or make the value+1. Long press the touch key to confirm your setting. The PIN definitions of CT/RS485/DRM0/ESTOP interface are as below. GND DRM0 NC ESTOP Definition METER 485- METER 485+ •...
  • Page 19 Wait until the LCD is off, then insert the U-disk to "WiFi/GPRS/4G/USB" port and turn on the DC switch or re-connect the PV connector, the LCD will show picture as below. Update Master/Slave/Manager/All Short press on the button to select the type of firmware you want to upgrade, then long press on the button, the inverter will start the upgrade process automatically.
  • Page 20: Inverter Start-Up

    After the initial commission, the setting will be locked and the Country code and Power Quality Response Mode will be viewed only. Please contact Energizer local service team to get the password to change that setting.(Authorized people only)
  • Page 21 Firm ware version: Please short press the button 8 times. Region Code: Please short press the button 9 times. Power Quality Response Modes: Please short press the button 10 times. *Please ask the Energizer local service team for the password. Authorized people only.
  • Page 22: Inverter Switch Off

    Note! Please set-up the inverter if it is the first time to start-up. The above steps are for the regular start-up of the inverter. If it is the first time to start up the inverter, you need to carry-out the initial set-up of the inverter.
  • Page 23: Operation

    6. Operation 6.1 Control Panel Object Name Function LCD Screen Display the information of the inverter. Red: The inverter is in fault mode. Indicator LED Green: The inverter is in normal state. The touch key is used to set the LCD to display different parameters. Press time <1s (short press): Next;...
  • Page 24: Maintenance

    7. Maintenance This section contains information and procedures for solving possible problems with the inverters and provides you with troubleshooting tips to identify and solve most problems that can occur. 7.1 Alarm List Fault Code Solution - Turn off the PV and grid, reconnect them. SPS Fault - Please seek help from us if it does not go back to normal state.
  • Page 25 Fault Code Solution - Wait for one minute, grid may go back to normal working state. Grid Voltage Fault - Make sure that grid voltage and frequency complies with standards. - Or, please seek help from us. - Disconnect PV (+), PV (-) with DC. Consistent Fault - After the LCD switches off, reconnect and check again.
  • Page 26: Troubleshooting

    7.2 Troubleshooting Please check the fault message on the System Control Panel or the fault code on the inverter information panel. If a message is displayed, record it before doing anything further. Attempt the solution indicated in table above. If your inverter information panel is not displaying a fault light, check the following to make sure that the current state of the installation allows for proper operation of the unit: Is the inverter located in a clean, dry, adequately ventilated place? Have the DC input breakers opened?
  • Page 27: Decommissioning

    8. Decommissioning 8.1 Dismantling the Inverter Disconnect the inverter from DC Input and AC output. Wait for 5 minutes for the inverter to fully de-energize. Disconnect communication and optional connection wirings. Remove the inverter from the bracket. Remove the bracket if necessary. 8.2 Packaging If possible, please pack the inverter with the original packaging.
  • Page 29 Website: www.energizersolar.com © 2022 Energizer. Energizer and certain graphic designs are trademarks of Energizer Brands, LLC and related subsidiaries and are used under license by 8 Star Energy Pty Ltd. All other brand names are trademarks of their respective owners. Neither 8 Star Energy Pty Ltd nor Energizer Brands is affiliated with the respective owners of their trademarks.