Separate the DC connector (battery) as below.
Plug
•
Insert striped cable into pin contact and ensure all conductor strands are captured in the pin contact.
•
Crimp pin contact by using a crimping plier. Put the pin contact with striped cable into the
corresponding crimping pliers and crimp the contact.
•
Insert pin contact through the cable nut to assemble into back of the male or female plug. When you
feel or hear a "click" the pin contact assembly is seated correctly.
•
Unlock the DC connector
- Use the specified wrench tool.
- When separating the DC + connector, push the tool down from the top.
- When separating the DC - connector, push the tool down from the bottom.
- Separate the connectors by hand.
6.3 AC Connection
Step 1: AC String Connection
HS/AS series inverters are designed for single-phase grid. Voltage range is 220/230/240V; frequency is
50/60Hz. Other technical requests should comply with the requirement of the local public grid.
Table1: Without EPS Function (internal)
HS-3.0
Model
AS-3.0
Cable (GRID)
4.0mm²
Cable (EPS)
4.0mm²
Micro-Breaker
Table2: With EPS Function (internal)
HS-3.0
Model
AS-3.0
Cable (GRID)
8.0-10.0mm²
Cable (EPS)
4.0mm²
Micro-Breaker
50A
Pin contact cable nut
HS-3.7
AS-3.7
4.0mm²
4.0mm²
25A
25A
HS-3.7
AS-3.7
8.0-10.0mm²
4.0mm²
50A
HS-4.6
HS-5.0
AS-4.6
AS-5.0
6.0mm²
6.0mm²
6.0mm²
6.0mm²
32A
HS-4.6
AS-4.6
8.0-10.0mm²
8.0-10.0mm²
6.0mm²
6.0mm²
63A
18
HS-6.0
AS-6.0
6.0mm²
6.0mm²
32A
40A
HS-5.0
HS-6.0
AS-5.0
AS-6.0
8.0-10.0mm²
6.0mm²
63A
63A