Ac Output/Input - Energizer Solar Force HS-3.0 User Manual

Table of Contents

Advertisement

4.3 AC Output/Input

Model
AC OUTPUT
Nominal AC
Power [VA]
Max. Apparent AC
Power [VA]
Rated Grid
Voltage
(AC Voltage
Range) [V]
Rated Grid
Frequency [Hz]
Nominal AC
Current [A]
Max. AC Current
[A]
Inrush Current [A]
Maximum Output
Fault Current[A]
Maximum Output
Over Current
Protection(A)
Displacement
Power Factor
Total Harmonic
Distortion
(THDi, Rated
Power)
AC INPUT
Max. AC Power
[VA]
Max. AC
Current[A]
Note: [1]3680 for G98, 4048 for other country
HS-3.0
HS-3.7
AS-3.0
AS-3.7
3000
3680
3300
4048 /3680
13.6
16.7/16
15.0
18.4
35
36.7
6000
7680
27.3
34.9
[2]16 for G98, 16.7 for other country
HS-4.6
AS-4.6
4600
[1]
5060
220 / 230 / 240 (180 to 270)
50 / 60
[2]
20.9
23.0
9.6A@50us
130A@ 10us
45.8
1 ( adjustable from 0.8 leading to 0.8 lagging )
<3%@ rated power
9200
41.8
9
HS-5.0
HS-6.0
AS-5.0
AS-6.0
5000
6000
5500
6600
22.7
27.3
25.0
30.0
47.7
57.4
10000
12000
45.5
54.5

Advertisement