Energizer Solar Force HS-3.0 User Manual page 20

Table of Contents

Advertisement

Note:
1.
If you don't use the EPS function, the wiring conduct core section can refer to the parameters of
table 1.
2.
If you use the EPS function, the wiring conduct core section can refer to the parameters of table 2.
3.
A micro-breaker for max output overcurrent protection device shall be installed between inverter and
grid, and the current of the protection device is referred to the table above, any load SHOULD NOT
be connected with the inverter directly.
Step 2: Grid Wiring
Check the grid voltage and compare with the permitted voltage range (refer to technical data).
Disconnect the circuit-breaker from all the phases and secure against re-connection.
Trim the wires
:
- Trim all the wires to 52.5mm and the PE wire to 55mm.
- Use the crimping pliers to trim 12mm of insulation from all wire ends as below.
Note: Please refer to local cable type and color for actual installation.
A.
EPS Wiring
Run the cable into the sleeve assembly.
Install the cable into the plug terminal and lock the screw, torque is (0.8 + / - 0.1 N·m).
Insert the plastic core into the main body.
L: Brown/Red Wire
N: Blue/Black Wire
PE: Yellow & Green Wire
19