Technical details

10
Technical details
General
Certifications
Application range
Module's device code
Electrical data
Supply voltage
for
Voltage
Kind
Voltage tolerance
Max. continuous current that the external power
supply must provide
Inrush current that the external power supply must
provide
External unit fuse protection F1
Supply voltage
for
Voltage
Kind
Voltage tolerance
Max. continuous current that the external power
supply must provide
External unit fuse protection F2
Potential isolation
Supply voltage
Current consumption
Power consumption
Max. power dissipation of module
Status indicator
Permitted loads
Configurable inputs/outputs (inputs or auxiliary
outputs)
Quantity
Potential isolation
Configurable inputs
Input voltage in accordance with EN 61131-2 Type
1
Input current at rated voltage
Input current range
Pulse suppression
Maximum input delay
Operating Manual PNOZ m B0.1
1005720-EN-04
CE, EAC, KOSHA, TÜV, UKCA, cULus Listed
Failsafe
0x5F
Supply to the system
24 V
DC
-20 %/+25 %
1,6 A
3 A
6 A, circuit breaker 24 VDC, characteristic B / 6 A,
60 VDC, SCCR: 10 kA, [UL 498/CSA C22.2 No. 5,
DIVQ/7]
Supply to the SC outputs
24 V
DC
-20 %/+25 %
8 A
10 A, circuit breaker 24 VDC, characteristic B/C /
10 A, 60 VDC, SCCR: 10 kA, [UL 498/CSA C22.2
No. 5, DIVQ/7]
Yes
32 mA
0,8 W
7,4 W
Display, LED
inductive, capacitive, resistive
8
No
24 V
5 mA
2,5 - 5,3 mA
0,5 ms
2 ms