Technical details

8
Technical details
General
Approvals
Application range
Module's device code
Number of ST output bits
Application in system environment
A
From ST firmware version, other
head modules
From ST firmware version PSSu
H S PN
From ST firmware version PSSu
WR S IDN
Application in system environment
B
From ST firmware version, head
modules
Electrical data
Internal supply voltage (module
supply)
Module's power consumption
Periphery's supply voltage (peri-
phery supply)
Voltage range
Module's current consumption
with no load
Module's power consumption
with no load
Max. power dissipation of module
Permitted loads
Voltage outputs
Potential isolation between relay
contact and periphery supply
Relay outputs
Number of relay outputs
Utilisation category
In accordance with the standard EN 60947-4-1
Relay contacts, AC1 at
Min. current
Max. current
Max. power
Relay contacts, DC1 at
Min. current
Max. current
Max. power
Operating Manual PSSu E S 2DOR 10(-T)
22047-EN-05
312510
BG, CE, TÜV, cULus Listed
Standard
0403h
2
16
2
9
1.7.0
312510
0,09 W
16,8 - 30,0 V
60 mA
1,50 W
2,50 W
inductive, resistive
312510
4900 V (prot. separation)
312510
2
250 V
10,00 mA
10,0 A
2400 VA
24 V
10,00 mA
10,0 A
240 W
314510
CE, cULus Listed
Standard
0403h
2
16
2
9
1.7.0
314510
0,09 W
16,8 - 30,0 V
60 mA
1,50 W
2,50 W
inductive, resistive
314510
4900 V (prot. separation)
314510
2
EN 60947-4-1
250 V
10,00 mA
10,0 A
2400 VA
24 V
10,00 mA
10,0 A
240 W
27