Operating Instructions Fire alarm system EBL512 G3, V1.1.x
control unit (main board 5010). Open the project in TLON Manager
and install (download) the project, see separate TLON network
documentation.
In case of a redundant TLON system a PC is connected to the modular
connector "J11" (Network no. 1) and the same procedure is repeated
for the redundant network.

Add a Control Unit in a TLON network

When adding a control unit to a "running" installation you have to
have the same software (S/W) version in all control units. Often the
new control unit has a newer version than the existing control units.
Normally the latest version is the best to use, i.e. the control units in
the "running" installation have to be upgraded. As an alternative, it is
possible to download an earlier S/W version in the new control unit.
Both alternatives are described in chapter "New system program
(S/W) version download", page 77.
Open the current project in TLON Manager, add one control unit and
install (download) it according to the separate TLON network
documentation. Also see 18.2.1 above.
Open the SSD for the current system via WinG3. Add one control
unit (and the units connected to it) and download the new SSD
according to chapter "Programming (SSD download)", page 75.

Make two TLON networks one.

It is very important that two or more presentation numbers (Zone-
Address) in the systems are not the same. The system properties have
to be the same.
Use one of the systems, e.g. the largest and add to it the control units
etc. from the other system.
If it is known from the beginning that two systems shall be one in the
future, it is possible to give the control units in the system
respectively, the "final" control unit numbers right from the beginning
in order to get the correct technical numbers in the system documents.
NOTE! Two or more presentation numbers (Zone-Address) in the
systems must not be the same.

Delete a Control Unit in a TLON network

Physically disconnect the control unit. This action will generate faults
in the other control units. Acknowledge the faults.
Open the current project in TLON Manager, delete the control unit
according to the separate TLON network documentation.
36
It is not possible to merge two TLON Networks into one or copy one
system and paste into another system.