6.1.3
the fire door closing function (ABDL) is to be used.
Normally low = The main power source
External power supply unit is okay.
Connections and examples, see drawings 128-21 & -28. The
unit's dimensions: (L x W x H) 90 x 70 x 32 mm. A plastic
protection cover is attached. The cover's dimensions: (L x W x
H) 129 x 73 x 45 mm. The unit is intended to be surface
mounted and for indoor use in dry premises. When required, the
unit can be mounted in a Waterproof box (IP66 / 67) 3362.
For more information, see the Technical Description and the
Product Leaflet.
The technical address is set with an Address setting tool (AST)
3314. The unit has an address label on which the programmed
technical address is to be written.
The Address setting tool 3314 is also used for mode setting:
NORMAL mode: Used for 3364 in EBL128.
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
NOTE! See also chapter "Limitations", page 144.

Alarm devices (addressable sounders)

3377 Addressable siren. The siren is connected directly to the COM
loop. It is power supplied via the COM loop, i.e. the number of
sirens is depending on the type and number of other units
connected to the COM loop.
sound types (tones) and two priority levels are available. For
each level an output control expression and a sound type is
programmed (via Win128). For more technical data, see the
Product Leaflet.
The technical address is set with an Address setting tool (AST)
3314. The siren has an address label on which the programmed
technical address is to be written.
The Address setting tool 3314 is also used for mode setting:
NORMAL mode: Used for 3377 in EBL128.
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
NOTE! See also chapter "Limitations", page 144.
3378 Addressable sounder base. 3378 consists of an analog base
(3312) mounted together with a sounder.
mounted in the ceiling. Two flying leads from the base are
plugged in the sounder. The base is thereafter mounted on the
sounder, so that the detector can be plugged in the base. The
base is connected directly to the COM loop. (Like base 3312.)
It is power supplied via the COM loop, i.e. the number of
sounder bases is depending on the type and number of other
units connected to the COM loop
47
The number of 3377 + 3378 units must be < 50.