Certification
6.2 EMC and Environmental Type Tests
Environmental Type Tests
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEC 60068-2-78
IEC 60068-14
IEC 60255-21-1
IEC 60255-21-2
IEC 60255-21-3
44
Description
Damped Oscillatory Wave
Dielectric Strength
Damped Oscillatory
Magnetic Field
Test
Cold Temperature
Dry Heat
Humidity (Damp
Heat, Cyclic)
Damp Heat
Steady State
Change of
Temperature
Earth
Ground Ports
Signal Ports
2.5 kV Common Mode at 1 MHz
DC Power Port
2.5 kV Common and
Differential Mode at 1 MHz
AC Power Port
2.5 kV Common and
Differential Mode at 1 MHz
Signal Ports
DC Power Port
AC Power Port
Enclosure Ports
100 A/m (Peak) at
100 kHz and 1 MHz
Description
Test Ad
Test Bd
Test Db
Test Cab
Test Nb
Vibration
Shock
Bump
Seismic
Test Levels
±4 kV
2 kV
2 kV
2 kV
Test Levels
Severity Levels
-40 °C (-40
°F), 16 Hours
85 °C (185
°F), 16 Hours
95% Relative
Humidity, 55 °C
(131 °F), 6 Cycles
93% Humidity,
10 Days
5 Cycles
2 g at 10-150 Hz
30 g at 11 ms
10 g at 16 ms
Method A, Class 2
RUGGEDCOM RSG920P
Equipment Manual, 10/2023, C79000-G8976-1172-09
Severity
Levels
5
Class 1
Class 1
Class 1
Class 1
Need help?
Do you have a question about the SIMATIC NET RUGGEDCOM RSG920P and is the answer not in the manual?
Questions and answers