● Wrench an anchor bolt clockwise to elevate the cabinet, or wrench it
● To prevent cabinet tilting, adjust the four anchor bolts instead of one anchor
● Use a measuring tape for measurement when leveling the cabinet to ensure
● Do not remove anchor bolts. Otherwise, you need to rework them for use.
Step 3 Insert four M12 bolt assemblies into the mounting holes on the UPS and support,
and tighten the bolts.
Figure 3-10 Leveling and tightening bolts
(1) Anchor bolt
----End

3.2.2 Installing an Enclosure Frame

Context
An enclosure frame can increase the UPS depth to 1200 mm, meeting the
requirements for routing cables from the bottom. The BOM number is 21242025.
Issue 01 (2022-09-26)
NO TICE
counterclockwise to lower the cabinet. The anchor bolts can be wrenched
within a range of 0–8 mm.
bolt.
that the height between the cabinet top and the floor is 2000 mm (tolerance
+3 mm).
Copyright © Huawei Digital Power Technologies Co., Ltd.
(2) Fixing bolt
3 Installation
(3) Level
61