Huawei UPS5000-E-125 kVA User Manual page 128

Hide thumbs Also See for UPS5000-E-125 kVA:
Table of Contents

Advertisement

UPS5000-E-125 kVA
User Manual (Integrated UPS 3.0, 02291136)
Table 6-1 Troubleshooting
Case
The
rectifier is
abnormal.
The
inverter is
abnormal.
The
charger
generates
an alarm.
The UPS
works in
bypass
mode and
does not
transfer to
inverter
mode.
Issue 01 (2022-09-26)
Symptom
The UPS rectifier fails
to work, and the bus
voltage is not boosted.
The buzzer buzzes, the
fault indicator is on,
the inverter is faulty,
and the UPS transfers
to bypass mode.
The buzzer buzzes, the
fault indicator is on,
and the charging
function fails.
When the mains is
normal, the UPS
works in bypass mode
and does not transfer
to inverter mode.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Possible Cause
The mains voltage
exceeds the upper
threshold 280 V or
is less than the
lower threshold 80
V.
PFC soft-start fails. Replace the power
The power
module is faulty.
Output overload
or short-circuit
exists.
The inverter is
overheated.
The power
module is faulty.
The charger fails.
The charger
experiences
overcurrent.
The charger
experiences
undervoltage.
The UPS is set to
ECO mode.
The number of
bypass transfer
times reaches the
upper limit.
6 Troubleshooting
Measure
Check whether the
mains voltage is
beyond the allowed
range. If so, contact
the electric power
company.
module.
Replace the power
module.
Reduce the load or
troubleshoot the
short circuit.
Install more smart
cooling products or
ventilation devices to
ensure normal
temperature inside
the data center.
Replace the power
module.
Replace the power
module.
Replace the power
module.
Check whether the
number of batteries
is correct. If the
number of batteries
is correct but the
alarm persists,
replace the power
module.
Set the working
mode correctly.
Reset the bypass
transfer times on the
LCD.
121

Advertisement

Table of Contents
loading

Table of Contents