Huawei UPS5000-E-125 kVA User Manual page 61

Hide thumbs Also See for UPS5000-E-125 kVA:
Table of Contents

Advertisement

UPS5000-E-125 kVA
User Manual (Integrated UPS 3.0, 02291136)
Table 3-4 Power cable terminal requirements
Port
AC input
Battery
input
PE
Safe
grounding
Issue 01 (2022-09-26)
NO TE
When selecting, connecting, and routing cables, follow local safety regulations and rules.
When the external conditions change, for example, the cable layout or ambient
temperatures, perform verification in accordance with the IEC-60364-5-52 or the local
regulations.
The currents listed in the table "Recommended cross-sectional areas for power cables" are
measured at a rated voltage of 380 V; if the rated voltage is 400 V, multiply the currents by
0.95; if the rated voltage is 415 V, multiply the currents by 0.92.
When the primary loads are non-linear loads, increase the cross-sectional areas of the
neutral wires by 1.5–1.7 times.
Signal cables must be double-insulated twisted cables. If the cable length is within 25–50
m, the cross-sectional area must be 0.5–1.5 mm
The recommended cables are applicable only when the following requirements are met:
● Routing mode: The cables are routed over a tray or bracket in a single layer (E or F in
IEC 60364-5-523).
● The ambient temperature is 30°C.
● The AC voltage loss is less than 3%, and the DC voltage loss is less than 1%.
● Single- or multi-core 90°C-resistant copper flexible cables are used.
● It is recommended that AC power cables be no longer than 30 m and DC power cables
be no longer than 40 m.
Connectio
n Method
Crimped
OT/DT
terminals
Crimped
OT/DT
terminals
Crimped
OT/DT
terminals
Crimped
OT/DT
terminals
Copyright © Huawei Digital Power Technologies Co., Ltd.
2
.
Bolt
Bolt Hole
Specificati
Diameter
ons
M12
13.5 mm
M10
Rivet
threaded
hole
diameter
M12
Rivet
threaded
hole
diameter
M6
Rivet
threaded
hole
diameter
3 Installation
Bolt
Torque
Length
45 mm
46 N·m
30 mm
26 N·m
45 mm
46 N·m
16 mm
4.5 N·m