Description and operation
Operating device of circuit- breaker
The closing spring (9) is loaded by means of the reducing gears (13) and the
motor (12).
D The auxiliary contacts (30) are activated by a rod and a lever (31), the
latter is activated by the main shaft (1).
D The limit switch of the motor (17) is activated by the cam (26)
The cam (26) is installed on the closing shaft (7).
D The closing latch (14) and the opening latch (6) are electrically activated
by coils (22) "Closing" and (27) "Opening".
D The operating mechanism can be activated by the manual levers (24)
"Closing" and (28) "Opening".
WARNING : Operating the mechanism by the manual levers (24) "Closing"
and (28) "Opening" overrides electrical interlocks. Ensure it is electrically safe
to operate the equipment when using these levers to defeat electrical inter-
locks and lockouts.
D The indicator (29) gives the "OPEN" or "CLOSED" positions of the circuit-
breaker. An operation counter gives the number of realized operations.
D The indicator (23) gives the "CHARGED" or "DISCHARGED" states of the
closing spring.
D If the auxiliary current supply fails, the hand- held crank (21) permits the
closing spring to be fully charged.