Page 1
Equipment is to be installed and maintained by properly trained and qualified personnel only. General These instructions are applicable to retrofit of Spectra K-frame with ABB Tmax XT7 breaker. Table 1 lists the parts included in the bolt-on circuit breaker kits for single branch configurations.
Page 2
STEP 1 STEP 2 Prepare the breaker, install required lugs and identify the re- Remove flat cap and install foldable handle assembly (13) and quired mounting and termination accessories from circuit tighten the screw. breaker kit. Refer to breaker instruction document for more infor- mation.
Page 3
STEP 7 STEP 7 Continued Install breaker with L-shaped barrier assembly [from STEP 6]. Refer figure 7a. Tighten Socket head screw [7] and flange nut [6], torque the screw [7] to 22 lb-in. Torque the flange Nut [6] to 160 lb-in.
Page 4
ABB Inc. We reserve the right to make technical We reserve all rights in this document and in GE logo is licensed by General 305 Gregson Drive changes or modify the contents of this doc- the subject matter and illustrations con-...